• Title/Summary/Keyword: Refrigeration

Search Result 3,993, Processing Time 0.032 seconds

Performance Analysis of R404A Refrigeration System with Internal Heat Exchanger Using R744 as a Secondary Refrigerant (R744를 2차 냉매로 사용하는 내부열교환기 부착 R404A 냉동시스템의 성능 분석)

  • Oh, Hoo-Kyu;Son, Chang-Hyo;Yi, Wen-Bin;Jeon, Min-Ju
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.25 no.10
    • /
    • pp.548-554
    • /
    • 2013
  • A thermodynamic analysis of the R404A refrigeration system with an internal heat exchanger using R744 as a secondary refrigerant is presented in this paper to optimize the design for operating parameters of the system. The main results are summarized as follows: The COP increases with increasing subcooling and superheating degree of R404A, internal heat exchanger and compression efficiency of the R404A cycle and evaporating temperature of the R744 cycle and decreasing temperature difference of the cascade heat exchanger and condensing temperature of the R404A cycle. The mass flow ratio decreases with increasing evaporating temperature of the R744 cycle and internal heat exchanger efficiency of the R404A cycle and decreasing subcooling and superheating degree of the R744 cycle, temperature difference of the cascade heat exchanger and condensing temperature of the R404A cycle.

Performance Characteristics of Refrigeration System Using R744 as a Secondary Refrigerant (2차 냉매로 천연냉매 R744를 사용하는 냉동시스템의 성능 특성)

  • Yi, Wen-Bin;Jo, Hwan;Yoon, Jung-In;Choi, In-Soo;Son, Chang-Hyo
    • Journal of Power System Engineering
    • /
    • v.18 no.4
    • /
    • pp.17-22
    • /
    • 2014
  • In this paper, the performance characteristics of R404 indirect refrigeration system using R744 as a secondary refrigerant were investigated experimentally to obtain a optimum design data for this system. First, for the constant experimental conditions, the COP of R404A indirect refrigeration system using R744 as secondary refrigerants decreases with respect to the increases in R404A condensation temperature and temperature difference in R744 cooler. And, the COP of indirect refrigeration system using R744 as secondary refrigerants decreases slightly with decreasing the mass flowrate of R744.

Heat Transfer and Pressure Drop Characteristics of Secondary Refrigerants Applying to Indirect Refrigeration System (간접 냉동 시스템용 2차 냉매의 열전달과 압력강하 특성)

  • Oh, Hoo-Kyu;Son, Chang-Hyo;Jo, Hwan;Yi, Wen-Bin;Jeon, Min-Ju
    • Journal of Power System Engineering
    • /
    • v.17 no.4
    • /
    • pp.45-50
    • /
    • 2013
  • This paper presents the comparison of heat transfer and pressure drop of various secondary refrigerants (single-phase and two-phase) in the indirect refrigeration system. The main results were summarized as follows: In case of heat transfer, it is useful to use secondary refrigerants in low evaporating temperature region and the heat transfer coefficient of single-phase is larger than two-phase secondary refrigerants. In case of pressure drop, it is useful to use secondary refrigerants in high evaporating temperature region and the pressure drop of two-phase is smaller than single-phase secondary refrigerant. Also, $CO_2$ is the best useful because pressure drop of $CO_2$ among the secondary refrigerants is the smallest.

Experimental Study of An Indirect-Refrigeration System with Carbon Dioxide (이산화탄소를 이용한 간접 냉장시스템의 실험적 연구)

  • Kim, Yoonsup;Baik, Wonkeun;Yun, Rin
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.28 no.5
    • /
    • pp.202-207
    • /
    • 2016
  • Experimental studies for an indirect R404A-$CO_2$ refrigeration system and a direct R404A refrigeration system were conducted. The configurations of the indirect R404A-$CO_2$ refrigeration system are a R404A refrigeration system as a top cycle and a circulating $CO_2$ system as a bottom cycle. The direct R404A system was modified from indirect R404A-$CO_2$ refrigeration system by removing circuit for $CO_2$ circulation. Various tests for both systems were conducted by changing load side brine temperature from 0 to 5 and $10^{\circ}C$ with cooling brine temperatures for R404A system at 15, 20, or $25^{\circ}C$. The indirect R404A-$CO_2$ refrigeration system showed the highest COP when load side brine temperature was at $10^{\circ}C$ in the evaporator and at cooling brine temperature of $15^{\circ}C$. The COP of 3.04 under that condition was the highest. This indirect R404A-$CO_2$ refrigeration system showed 9.02% higher COP than the direct R404A system that had increased pipeline length of 15 m, which simulated actual installation in a supermarket.

Operating characteristics of 3RT heat pumps

  • Moon, Chang-Uk;Choi, Kwang-Hwan;Yoon, Jung-In;Jeon, Min-Ju;Heo, Seong-Kwan;Sung, Yo-Han;Park, Sung-Hyeon;Lee, Jin-Kook;Son, Chang-Hyo
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.41 no.2
    • /
    • pp.140-145
    • /
    • 2017
  • Newly designed vapor-injection heat pumps have been proposed and analyzed in the present study. An economizer-type vapor-injection (V-I) system has been employed as the standard system because of its reliability and simple control method. The V-I system has a re-cooler and re-heater for cooling and heating, respectively. Solar panels have been installed in the V-I heat pump as well as in the re-heater in order to enhance heating capacity and performance. R410A has been employed as a working fluid and performance analysis has been conducted under various conditions. Results are summarized as follows: (1) The V-I system with the re-cooler yielded a marginally higher coefficient of performance (COP) than the conventional V-I refrigeration system. (2) By increasing the re-cooler cooling capacity, enhanced system performance as compared to the conventional V-I system was observed. (3) The re-heater negatively affected the system performance; hence, the V-I heat pump with the re-heater yielded a lower COP than that of the conventional V-I heat pump used for heating. (4) Although the solar panels increased the system performance, this increase could not offset performance degradation by the re-heater.

A Simulation Study on the Cascade Refrigeration Cycle for the Liquefaction of the Natural Gas [2]: An Application to the Multistage Cascade Refrigeration Cycle (천연가스 액화를 위한 캐스케이드 냉동사이클의 전산모사에 대한 연구 [2]: 다단 캐스케이드 냉동 사이클에 적용)

  • Cho, Jung-Ho;Kim, Yu-Mi
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.12 no.2
    • /
    • pp.1013-1019
    • /
    • 2011
  • In this paper, simulation works for a multi-stage cascade refrigeration cycle using propane, ethylene and methane as refrigerants have been performed for the liquefaction of natural gas using Peng-Robinson equation of state built-in PRO/II with PROVISION release 8.3. The natural gas feed compositions were supplied from Korea Gas Corporation and the flow rate was assumed to be 5.0 million tons per annual. Supply temperature for propane refrigerant was fixed as $-40^{\circ}C$, that for ethylene refrigerant as $-95^{\circ}C$, and that for methane refrigerant as $-155^{\circ}C$. For the multi-stage refrigeration cycle, three-stage refrigeration was assumed for propane refrigeration cycle, two-stage refrigeration for ethylene refrigeration cycle and three-stage refrigeration for methane refrigeration cycle. Natural gas was finally cooled and liquefied to $-162^{\circ}C$ by Joule-Thomson expansion. Conclusively, 91.71% by mole of the natural gas liquefaction ratio was obtained through a cascade refrigeration cycle and Joule-Thomson expansion and 0.433 kW of compression power was consumed for the liquefaction of 1.0 kg/hr of natural gas.

Early Estimation of Compressive Strength of Concrete Using Mineral Admixture by Refrigeration Curing Method (냉동양생에 의한 광물질 혼합 콘크리트의 압축강도 추정)

  • Sung , Chan-Yong;Cho , Il-Ho
    • Journal of The Korean Society of Agricultural Engineers
    • /
    • v.46 no.5
    • /
    • pp.55-60
    • /
    • 2004
  • This study was performed to evaluate the early estimation of compressive strength of concrete using mineral admixture by refrigeration curing method. It was a method of early decision for the property of concrete after the curing age 28days through the refrigeration curing at $-18{\pm}3^{\circ}$ for five hours. The test result was fixed connection between the curing age 28days and 31hours by the compressive strength test through the standard curing and refrigeration curing. Accordingly, it can be reduced the mistake of construction work by forecasting the property of concrete through the refrigeration curing.

The Effect of R-134a and R-430a on the Performance of Refrigeration Equipment for R-134a (R-134a용 냉동장치의 성능에 미치는 R-134a와 R-430a의 영향)

  • Byun, Chul-Kju;Kang, Hyung-Suk
    • Journal of Industrial Technology
    • /
    • v.34
    • /
    • pp.21-26
    • /
    • 2014
  • The effect of refrigerant R-134a and R-430a on the performance of refrigeration equipment for R-134a is investigated. Refrigeration effect, compression work and coefficient of performance of refrigeration equpment for both R-134a and R-430a are obtained by experimentation. These performances comparison between R-134a and R-430a is made in case of the maximum load. Refrigeration effect for R-134a and that for R-430a is almost equal while compression work for R-134a is less than that for R-430a. Consequently it shows that coefficient of performance for R-134a is relatively 11% higher than that for R-430a.

  • PDF

The Characteristic of Propane(R290)-Ethane(R170) as Refrigerant in the Cascade Refrigeration System (캐스캐이드 냉동시스템에서 냉매로서의 프로판-에탄 냉매의 성능 분석)

  • Kim, P.H.;Lee, B.H.;Jeong, H.M.;Chung, H.S.;Kim, C.S.
    • Journal of Power System Engineering
    • /
    • v.11 no.4
    • /
    • pp.50-55
    • /
    • 2007
  • Nowadays, demands on super low temperature condition for industrial and commercial uses are thriving. Considering of its wide application in the present and the future, study of the super-low temperature refrigeration system should be actively carried out. This study is aimed to investigate refrigeration capacity and coefficient of performance(COP) of the cascade refrigeration system, as well as to get the system which can reach evaporator temperature of $-70^{\circ}C$. For this purpose, R290 and R170 are charged in high stage and low stage respectively. Finally the characteristics of system using R290 and R170 will be proposed. Additionally, In this experiment, the flow rate of air flowing through the LS evaporator and the compressor inlet pressure were varied to investigate the refrigeration capacity and coefficient of performance characteristics.

  • PDF

Performance Characteristics of Propane/isobutane Mixtures in a Small Refrigeration System (프로판-이소부탄 혼합냉매를 적용한 소형 냉동시스템의 성능 특성에 관한 연구)

  • 윤원재;김용찬
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.1
    • /
    • pp.73-82
    • /
    • 2002
  • A small refrigeration system used in a water purifier was tested by employing propane/isobutane (R-290/R-6OOa) mixtures as an alternative refrigerant of R-12. The drop-in tests were performed by varying mass fraction of propane at 0.25, 0.5 and 0.75 with a change of both refrigerant charge amount and capillary tube length in order to find an optimum composition in aspect of performance and reliability of the system. As a result, the mixture of 50% propane-50% isobutane showed the best performance and reliability among them in a small refrigeration system. During steady state operations, both the COP and refrigeration capacity increased by 4% and 9%, respectively, as compared to the baseline R-12 system. In addition, the propane/isobutane (50/50) mixture system yielded advantages in the minimization of modification and redesigning of system components due to very similar saturation tempera- ture and pressure characteristics with R-12.