Abstract
Experimental studies for an indirect R404A-$CO_2$ refrigeration system and a direct R404A refrigeration system were conducted. The configurations of the indirect R404A-$CO_2$ refrigeration system are a R404A refrigeration system as a top cycle and a circulating $CO_2$ system as a bottom cycle. The direct R404A system was modified from indirect R404A-$CO_2$ refrigeration system by removing circuit for $CO_2$ circulation. Various tests for both systems were conducted by changing load side brine temperature from 0 to 5 and $10^{\circ}C$ with cooling brine temperatures for R404A system at 15, 20, or $25^{\circ}C$. The indirect R404A-$CO_2$ refrigeration system showed the highest COP when load side brine temperature was at $10^{\circ}C$ in the evaporator and at cooling brine temperature of $15^{\circ}C$. The COP of 3.04 under that condition was the highest. This indirect R404A-$CO_2$ refrigeration system showed 9.02% higher COP than the direct R404A system that had increased pipeline length of 15 m, which simulated actual installation in a supermarket.