• 제목/요약/키워드: Refrigerant heat exchanger

검색결과 264건 처리시간 0.024초

대체냉매 R407C 및 R410A를 이용한 슬릿휜-관 열교환기의 응축특성에 관한 연구 (An Experimental Study on Condensation Characteristics of Slit Fin-tube Heat Exchanger Using Alternative Refrigerants, R407C and R410A)

  • 전창덕;장경근;강신형;이진호
    • 설비공학논문집
    • /
    • 제14권9호
    • /
    • pp.706-716
    • /
    • 2002
  • R410A and R407C are considered to be alternative refrigerants to R22 for the air-conditioners. Experimental investigation is made to study the condensation heat transfer characteristics of slit fin-tube heat exchanger using alternative refrigerants R410A and R407C. R407C, a non-azeotropic refrigerant mixture, exhibited a quite different condensation phenomenon from those of R22 and R410A and its condensation heat transfer coefficient was much lower than that of R22 and R410A. Between the R22 and R410A, the condensation heat transfer coefficient of R410A, near-azeotropic refrigerant mixture, was a little higher than that of R22. R410A also showed the lowest condensation pressure drop across the test section. For all refrigerants, the condensation heat transfer coefficient and pressure drop increase as the mass flux increases.

평판 핀 튜브 열교환기의 공기측 강제대류 열전달계수에 대한 실험 및 수치계산 (Experimental Measurement and Numerical Computation on the Air-Side Forced Convective Heat Tranfer Coefficient in Plate Fin-Tube Exchangers)

  • 윤영환;팽진기;윤건식
    • 설비공학논문집
    • /
    • 제18권9호
    • /
    • pp.729-737
    • /
    • 2006
  • Air-side forced convective heat transfer of a plate fin-tube heat exchanger is investigated by experimental measurement and numerical computation. The heat exchanger consists of staggered arrangement of refrigerant pipes of 10.2 m diameter and the pitch of fins is 3.5 m. In the experimental study, the forced convective heat transfer is measured at Reynolds number of 1082, 1397, 1486, 1591 and 1649 based on diameter of refrigerant piping and mean velocity. Average Nusselt number for the convective heat transfer coefficient is also computed for the same Reynolds number by commercial software of STAR-CD with standard $k-{\varepsilon}$ turbulent model. It is found that the relative errors of average Nusselt numbers between experimental and numerical data are less than 6 percentage in Reynolds number of $1082{\sim}1649$. The errors between experiment and other correlations are ranged from 7% to 32.4%. But the correlation of Kim at al is closest to the experimental data within 7% of the relative error.

흡입관 열교환기를 이용한 탄화수소계 냉매용 냉동사이클의 성능 분석 (Performance Analysis of Refrigeration Cycle of Hydrocarbon Refrigerant using Suction-Line Heat Exchanger)

  • 구학근
    • 한국산학기술학회논문지
    • /
    • 제10권9호
    • /
    • pp.2195-2201
    • /
    • 2009
  • 본 논문은 R290, R600a, R1270과 같은 탄화수소계 냉매를 사용하는 냉동사이클의 효율에 대한 흡입관 열교환기의 영향을 고려하였다. 이러한 흡입관 열교환기는 냉동시스템의 성능을 향상시킬 수도 있지만, 성능을 저하시킬 수도 있다. 본 논문에서는 흡입관 열교환기를 가진 냉동사이클의 성능 특성을 파악하기 위해서 정상상태의 수학적 모델을 사용하였다. 그리고 탄화수소계 냉매유량, 흡입관 열교환기의 내관 직경, 길이, 유용도 등과 같은 운전조건의 영향을 분석하였다. 연구결과는 흡입관 열교환기의 내관 직경, 길이, 유용도, 탄화수소계 냉매의 질량유량은 냉동사이클의 상대냉동능력지수, 냉동능력, 압축일량에 영향을 미치는 것을 알 수 있었다. 따라서 이러한 영향을 상세히 파악하여, 흡입관 열교환기를 설치한 탄화수소계 냉매용 증기압축식 냉동사이클을 설계할 필요가 있다.

고효율 혼합 냉매 천연 가스 액화 공정에 대한 고찰 (Analysis of high efficiency natural gas liquefaction cycle with mixed refrigerant)

  • 백승환;황규완;정상권
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 동계학술발표대회 논문집
    • /
    • pp.181-185
    • /
    • 2008
  • The new concept for liquefaction of natural gas has been designed and simulated in this paper. Conventional liquefaction cycles are usually composed with Joule-Thomson valves at lower temperature refrigerant cycle. The new concept of natural gas liquefaction is discussed. The main difference with conventional liquefaction process is the presence of the turbine at low temperature of MR (mixed refrigerant) cycle. The turbine acts as expander but also as an energy generator. This generated energy is provided to the compressor which consumes energy to pressurize refrigerants. The composition of the mixed refrigerant is investigated in this study. Components of the refrigerant are methane, propane and nitrogen. Composition for new process is traced with Aspen HYSYS software. LNG heat exchangers are analyzed for the new process. Heating and cooling curves in heat exchangers were also analyzed.

  • PDF

Advances In Air-Cooled Heat Exchanger Technology for Residential Air-Conditioning

  • Webb Ralph L.;Kim Nae-Hyun
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제13권4호
    • /
    • pp.184-195
    • /
    • 2005
  • This paper describes the recent work on advanced technology concepts applied to air cooled heat exchangers for residential air-conditioning. The concepts include vortex generators for the air-side, micro-fin or flat tubes for the refrigerant-side. Advances in understanding of heat transfer mechanisms, predictive models are discussed.

내부열교환기 및 전자팽창장치를 적용한 가변속 이산화탄소 사이클의 냉방성능에 관한 실험적 연구 (Experimental Study on the Cooling Performance of a Variable Speed $CO_2$ Cycle with Internal Heat Exchanger and Electronic Expansion Valve)

  • 조홍현;류창기;김용찬
    • 설비공학논문집
    • /
    • 제17권3호
    • /
    • pp.209-215
    • /
    • 2005
  • Since a transcritical $CO_2$ cycle shows lower performance than conventional air conditioners in the cooling mode operation, it is required to enhance the performance of the $CO_2$ cycle by applying advanced technologies and optimizing components. In this study, the cooling performance of a $CO_2$ system measured by varying refrigerant charge amount, compressor frequency, EEV opening and length of internal heat exchanger. As a result, the cooling COP of the basic system without internal heat exchanger was 2.1. The cooling performance of the modified cycle applying internal heat exchanger improved by $4-9\%$ over the basic cycle.

고속 회전축 냉각용 루우프 히트파이프 열교환기의 응축열전달 특성에 관한 연구 (A Study on the Condensation Heat Transfer Characteristics of a Loop Heat Pipe Heat Exchanger for High Speed Rotary Shaft Cooling)

  • 조동현;이종선
    • 한국기계가공학회지
    • /
    • 제16권4호
    • /
    • pp.147-152
    • /
    • 2017
  • In the present study, we used a loop thermosyphon heat exchanger consisting of condensers with internal fins and external plate fins which are 480 mm wide, 68 mm long, and 1,000 mm high. The heat transfer pipes in the heat exchanger were 15 mm in diameter and 1,000 mm in length, and 98 heat transfer pipes were installed in the heat exchanger. According to the experimental results, as the spaces between the internal discontinuous pins decreased, the frequency of pressure drops increased and changes in temperature at the outlet of the condenser were shown to be a little smaller. Therefore, we can see that as the spaces between internal discontinuous pins decreased, the heat transfer performance increased. For the loop heat pipe heat exchanger consisting of a condenser with internal and plate fins, as the temperature of the air flowing into the condenser increased, the condensation heat transfer rate also increased, and as the condenser refrigerant inflow temperature increased, the condensation heat transfer rate increased as well.

냉매 과냉각 시스템을 이용한 열펌프의 성능향상에 관한 연구 (Performance Enhancement of the Heat Pump Using the Refrigerant Subcooling System)

  • 손창효;윤찬일;박승준;이동건;오후규
    • 한국마린엔지니어링학회:학술대회논문집
    • /
    • 한국마린엔지니어링학회 2001년도 춘계학술대회 논문집
    • /
    • pp.106-111
    • /
    • 2001
  • The performance characteristics of heat pump system using the new refrigerant subcooling system were investigated. The new heat pump system has the ice storage tank to accumulate the latent heat of the refrigerant during the night-time. The heat is released to subcool the saturated refrigerant liquid at the outlet of a condenser in the daytime. The experimental apparatus is a well-instrumented heat pump which consisted of a refrigerant loop and a coolant loop. The test sections(condenser and evaporator) were made of tube-in-tube heat exchanger with the horizontal copper tube of 12.7[mm] outer diameter and 9.5[mm] inner diameter. The evaporating temperatures ranged from $-5[^{\circ}C]$ to $0[^{\circ}C]$ and the subcooling degrees of the refrigerant varied from $15[^{\circ}C]$ to $25[^{\circ}C]$. The test of the ice storage was carried out at evaporating temperature of $-10[^{\circ}C]$ and the ice storage mode is an ice-on-coil type. The main results were summarized as follows ; The refrigerant mass flow rate and compressor shaft power of the heat pump system were independent of the subcooling degrees. The cooling capacity o the heat pump system increases as the evaporating temperature and subcooling degree increases. The cooling capacity of the heat pump system is about 25 to 30% higher than that of normal heat pump system. The COP of the heat pump system which subcooled the refrigerant liquid at the outlet of the condenser is about 28% higher than that of the normal heat pump system.

  • PDF

저온측과 고온측 냉매간 열교환이 열펌프의 성능특성에 미치는 영향 (Effect of the Heat Exchange between Low and High Temperature Refrigerant on the Heat Pump Performance)

  • 이건중;송현갑
    • Journal of Biosystems Engineering
    • /
    • 제24권4호
    • /
    • pp.343-350
    • /
    • 1999
  • The ambient air is commonly used as low-temperature heat source for heat pump operation. However, the coefficient of performance(COP) of the air to water heat pump is decreased with the ambient air temperature drop. In this study to solve this problem, the AVACTHE(Automatic Variable Area Capillary Type Heat Exchanger) with 3 levels of heat exchange area(0, 1,495.4, 1,794.5$\textrm{cm}^2$)was installed in the refrigerant circuit of the heat pump. The AVACTHE effect on the performance of heat pump was tested with the ambient air temperature variation. The COP improvement of the heat pump could be achieved by the AVACTHE installation when below -5$^{\circ}C$ of the ambient air temperature.

  • PDF

극저온 Joule-Thomson 냉동기용 혼합냉매 결정에 관한 연구 (A Study on the Determination of Mixed Refrigerant for the Joule-Thomson Cryocooler)

  • 이경수;장기태;정상권
    • 설비공학논문집
    • /
    • 제12권10호
    • /
    • pp.901-907
    • /
    • 2000
  • The conceptual determination of mixed-refrigerant (MR) for a closed Joule-Thomson cryocooler is described in this paper. The thermodynamic cycle design was mainly considered to develop a cryocooler by using a compressor of domestic air-conditioning unit. The target cooling performance of the designed cryocooler is 10 W around 70 K with less than 5 kJ/kg enthalpy rise. The systematic approach of choosing a proper refrigerant among 20 different kinds of mixture for such cryogenic temperature was introduced in detail. The main components of the cryocooler are compressor, evaporator, oil separator, after-cooler, counterflow heat exchanger, and J-T expansion device. Due to the limitation of the compressor operation range, the temperature after the compression was limited below $117^{\circ}C$ (390 K) and the temperature before compression was restricted above $5^{\circ}C$ (278 K). 20 atm of discharging pressure (high pressure) and less than 3 atm suction pressure (low pressure) were the design conditions. The inlet temperature of a counterflow heat exchanger in the high Pressure side was about 300 K. The proper composition of the mixed refrigerant for the designed J-T cryocooler is 15% mol of$ N_2, 30% mol of $CH_4,\; 30% mol\; of C^2H^ 6,\; 10%\; mol\; of\; C_3H_8\; and \;15%\; mol\; of\; i-C_4H_10$.

  • PDF