• 제목/요약/키워드: Refrigerant heat exchanger

검색결과 264건 처리시간 0.025초

R-22를 사용한 용접형 판형 열교환기의 응축열전달 및 압력강하 특성에 관한 연구 (Study on Condensation Heat Transfer and Pressure Drop Characteristics of R-22 in Brazed Plate Heat Exchanger)

  • 전창덕;권오갑;이진호
    • 대한기계학회논문집B
    • /
    • 제25권2호
    • /
    • pp.171-179
    • /
    • 2001
  • Experimental study has been carried out on the characteristics of pressure drop and heat transfer of brazed plate heat exchangers using R-22. Data are presented for the following range of variables: the mass flux (40∼90kg/$m^2$s), chevron angle ($20^{\circ}$, $35^{\circ}$, $45^{\circ}$) and inlet pressure of the refrigerant (1.4 and 1.6MPa). For both subcooled and two-phase flow, as chevron angle increases, pressure drop and heat transfer coefficient decrease. Condensation heat transfer coefficient and pressure drop were compared with the previously proposed correlations. Among therm, Traviss correlation agreed with experimental results within -40%∼-84% for heat transfer coefficient and -59%∼62% for pressure drop.

수평원관내 $CO_2$의 증발열전달 (Evaporation Heat Transfer of Carbon Dioxide in a horizontal Round Tube)

  • 경남수;장승일;최선묵;손창효;오후규
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2005년도 동계학술발표대회 논문집
    • /
    • pp.262-267
    • /
    • 2005
  • The evaporation heat transfer coefficient of $CO_2$ in a horizontal round tube was investigated experimentally. The experiments were conducted without oil in a closed refrigerant loop which was driven by a magnetic gear pump. The main components of the refrigerant loop are a receiver, a variable-speed pump, a mass flow meter, a pre-heater and evaporator(test section). The test section was made of a horizontal stainless steel tube with the inner diameter of 7.75 mm, and length of 5 m. The experiments were conducted at mass flux of 200 to 500 $kg/m^2s$, saturation temperature of $-5^{\circ}C$ to $5^{\circ}C$, and heat flux of 10 to 40 $kW/m^2$. The test results showed the evaporation heat transfer of $CO_2$ has great effect on more nucleate boiling than convective boiling. The evaporation heat transfer coefficients of $CO_2$ are highly dependent on the vapor quality, heat flux and saturation temperature. In comparison with teat results and existing correlations, correlations failed to predict the evaporation heat transfer coefficient of $CO_2$, therefore, it is necessary to develop reliable and accurate predictions determining the evaporation heat transfer coefficient of $CO_2$ in a horizontal tube.

  • PDF

고효율 수퍼히트펌프에 관한 전산 해석 (Computer Simulation of a Super-Heat Pump System)

  • 김학준;정동수;김종보;하경용
    • 설비공학논문집
    • /
    • 제7권2호
    • /
    • pp.234-248
    • /
    • 1995
  • A super-heat pump system composed of a suction line heat exchanger, low and high stage economizers, and a screw compressor is simulated to examine the energy performance and design options. CFC12, HCFC22, HFC134a, HCFC22/HCFC142b, HFC32/HFC134a, and HFC125/HFC134a are used as working fluids for comparison. The results indicate that the proposed system charged with appropriate mixtures is up to 33.4% more energy efficient than the normal system with CFC12. The performance of the super-heat pump system charged with mixtures was influenced by such factors as the temperature matching, heat source temperature difference, low stage economizer, and high stage economizer. The fluids with a larger liquid specific heat such as HFC134a would have more benefits when a suction line heat exchanger is installed. 40%HCFC22/60%HCFC142b mixture seems to be a good candidate to replace CFC12. On the other hand, 25%HFC32/75% HFC134a would be a good long term candidate to replace HCFC22.

  • PDF

세관내 R-22와 R-410A의 응축 압력강하 (The Condensation Pressure Drop of R-22 and R-410A in Small Diameter Tube)

  • 손창효
    • 한국수소및신에너지학회논문집
    • /
    • 제19권2호
    • /
    • pp.156-162
    • /
    • 2008
  • The condensation pressure drop for R-22 and R-410A flowing in a small diameter tube was investigated. The test section is a counterflow heat exchanger with refrigerant flowing in the inner tube and coolant flowing in the annulus. The test section consists of 1220 mm length with horizontal copper tube of 3.38 mm outer diameter and 1.77 mm inner diameter. The refrigerant mass fluxes ranged from 450 to $1050\;kg/m^2{\cdot}s$ and the average inlet and outlet qualities were 0.05 and 0.95, respectively. The main experimental results were summarized as follows : In the case of two-phase flow, the pressure drop increases with increasing mass flux and decreasing quality. The pressure drop of R-22 is slightly higher than that of R-410A for the same mass flux. Most of correlations proposed in the large diameter tube showed enormous deviations with experimental data.

선박용 해수 열교환방식 A/C 응축기의 부식원인 (Study on the corrosion of A/C condenser in the ship)

  • 백상민;양정현;김기준;문경만;이명훈
    • 한국마린엔지니어링학회:학술대회논문집
    • /
    • 한국마린엔지니어링학회 2006년도 전기학술대회논문집
    • /
    • pp.283-284
    • /
    • 2006
  • The ship performs heat exchange using seawater to keep main engine and auxiliary machinery at optimum temperature. In heat exchanger, refrigerant located outside of copper tube is cooled by seawater flowing through inside of copper tube. On the other hand, seawater erosion and corrosion nay occasionally cause the corrosion of the copper tube in A/C(Air Conditioner) condenser. This corrosion of copper tube makes seawater and refrigerant mixed, seriously damaging A/C system. In this study, accordingly, the exact ive mechanism of the corrosion on the condenser entailing serious problems occasional is investigated through the electrochemical polarization experiments on the condenser's component materials. According to the experiments, the corrosive procedures on the copper tube was verified by the fact that passive film of the copper tube surface which is destroyed by the pressure of sucked seawater, is damaged by the corrosive ingredients in the seawater.

  • PDF

냉매의 불균일한 분배가 증발기의 성능에 미치는 영향 (Effects on Refrigerant Maldistribution on the Performance of Evaporator)

  • 김창덕;이진호
    • 설비공학논문집
    • /
    • 제16권3호
    • /
    • pp.230-240
    • /
    • 2004
  • An experimental investigation was conducted to study two-phase flow distribution in a T-type distributor of slit fin-and-tube heat exchanger using R22. A comparison was made between the predictions by previously proposed tube-by-tube method and experimental data for the heat transfer rate of evaporator. Experiments were carried out under the conditions of saturation temperature of 5$^{\circ}C$ and mass flow rate varying from 0.6 to 1.2kg/min. The inlet air has dry bulb temperature of 27$^{\circ}C$, relative humidity of 50% and air velocity varying from 0.63 to 1.71㎧. Experiment show that air velocity increased by 85.2% is need for T-type distributor with four outlet branches than that of two outlet branches under the superheat of 5$^{\circ}C$, which resulted in air-side pressure drop increase of 130% for T-type distributor with four outlet branches as compared to two outlet branches.

학교 건물에 설치된 지열원 열펌프 시스템의 실사용을 통한 냉난방성능 연구 (Cooling and Heating Performance Under the Actual Operating Condition of a Ground Source Heat Pump System in a School Building)

  • 김의영;정영만;송재도;이재근;김인규;이동혁
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.586-589
    • /
    • 2009
  • This paper presents the performance of a water-to-refrigerant type ground source heat pump (GSHP) system installed in a school building in Korea. For analyzing the performance of the GSHP system, we monitored various operating conditions, including the outdoor temperature, the ground temperature, and the input power of the GSHP system. The average cooling coefficient of performance (COP) of the heat pump was found to be 8.5 at 60% partial load condition, while the overall system COP was found to be 5.9. The average heating COP of the heat pump was found to be 6.5 at 45% partial load condition, while the overall system COP was found to be 5.0.

  • PDF

마이크로핀관에서 프로판과 이소부탄의 증발 열전달 특성에 관한 연구 (Evaporation Heat Transfer Characteristics of Propane and Iso-butane in Micro-fin Tubes)

  • 손창효;노건상
    • 한국가스학회지
    • /
    • 제11권4호
    • /
    • pp.35-40
    • /
    • 2007
  • 본 연구는 마이크로핀관에서 이소부탄과 프로판의 증발 열전달 특성에 대해 실험적으로 조사하였다. 시험부는 외경 12.70 mm이고, 높이가 0.25 mm인 75개 핀이 원주방향으로 삽입되어 있다. 실험결과, 탄화수소계 냉매의 평균 열전달계수는 프레온계 냉매인 HCFC22보다 높을 것으로 나타났고, 높은 질랑유속에서는 이소부탄 > 프로판 순으로 나타났다. 마이크로핀관에서 증발 열전달 계수는 평활관에 비해 약 $80{\sim}100%$ 정도가 향상되었다. 이러한 본 연구 결과로부터 탄화수소계 냉매를 냉동 공조 시스템의 냉매로 사용하여 열교환장치를 설계할 경우에는 유리하리라 생각된다.

  • PDF

R22 대체냉매의 성능 평가 (Performance evaluation of R22 alternative refrigerants)

  • 송용재;박봉진;정동수;김종보
    • 설비공학논문집
    • /
    • 제10권3호
    • /
    • pp.292-302
    • /
    • 1998
  • In this study, 14 refrigerant mixtures composed of R32, R125, R134a, R143a, R152a, and R1270(Propylene) were tested in a breadboard heat pump in an attempt to replace R22 used in most of the residential air conditioners and heat pumps. The heat pump was of 1 ton capacity and water was employed as the secondary heat transfer fluids. All tests were conducted under ARI test A condition. Ternary mixtures composed of R32, R125, and R134a were shown to have 4∼5% higher COP and capacity than R22 and hence they seem to be very promising candidates to replace R22. On the other hand, ternary mixtures containing R125, R134a, and R152a have lower COP and capacity than R22. R32/R134a binary mixtures show a 7% increase in COP and have the similar capacity to that of R22 and hence they are also good candidates to replace R22. Special care must be exercised when a suction line heat exchanger is used with these mixtures in air conditioners. Finally, the compressor discharge temperatures of all mixtures tested were lower than those of R22 by 15.g∼34.7t, which indicates that these mixtures would offer better system reliability and longer life time than R22.

  • PDF

함정용 패키지 에어콘 응축기 핀튜브(Cu-Ni 70/30) 누설파괴 원인 분석 (Failure Analysis of Condenser Fin Tubes of Package Type Air Conditioner for Navy Vessel)

  • 박형훈;황양진;이규환
    • 한국표면공학회지
    • /
    • 제49권5호
    • /
    • pp.439-446
    • /
    • 2016
  • In 2015, a fin tube (Cu-Ni 70/30 alloy) of package type heat exchanger for navy vessel was perforated through the wall which led to refrigerant leakage. This failure occurred after only one year since its installation. In this study, cause of the failure was determined based on available documents, metallographic studies and computational fluid dynamics simulation conducted on this fin tube. The results showed that dimensional gap between inserted plastic tube and inside wall of fin tube is the cause of the swirling turbulent stream of sea water. As a result of combination of swirling turbulence and continuing collision of hard solid particles in sea water, erosion corrosion has begun at the end of inserted plastic tube area. Crevice corrosion followed later in the crevice between the outer wall of plastic tube and inner wall of fin tube. It was found that other remaining tubes also showed the same corrosion phenomena. Thorough inspection and prompt replacement will have to be accomplished for the fin tubes of the same model heat exchanger.