• 제목/요약/키워드: Refrigerant Oil

검색결과 115건 처리시간 0.026초

수평관내 초임계 영역의 Co2 냉각 열전달 특성 (Heat Transfer Characteristics During Gas Cooling Process of Carbon Dioxide in a Horizontal Tube)

  • 손창효;이동건;오후규;정시영;김영률
    • 대한기계학회논문집B
    • /
    • 제28권3호
    • /
    • pp.289-295
    • /
    • 2004
  • The heat transfer coefficient and pressure drop during gas cooling process of carbon dioxide in a horizontal tube were investigated. The experiments were conducted without oil in the refrigerant loop. The main components of the refrigerant loop are a receiver, a variable-speed pump, a mass flowmeter, an evaporator, and a gas cooler(test section). The main components of the water loop consist of a variable-speed pump, an isothermal tank, and a flowmeter. The gas cooler is a counterflow heat exchanger with refrigerant flowing in the inner tube and water flowing in the annulus. The test section consists of smooth, horizontal stainless steel tube of the outer diameter of 9.53mm and of the inner diameter of 7.75mm. The length of the test section is 6m. The refrigerant mass fluxes were 200∼300kg/(m2$.$s) and the inlet pressure of the gas cooler varied from 7.5㎫ to 8.5㎫. The main results were summarized as follows : Pressure drop of CO2 increases with increasing gas cooler pressure. The friction factors of CO2 in a horizontal tube show a relatively good agreement with the correlation by Blasius. The heat transfer coefficient of CO2 in transcritical region increases with decreasing gas cooler pressure and decreasing mass flux of CO2. Most of correlations proposed in a transcritical region showed significant deviations with experimental data except for those predicted by Gnielinski.

오블롱 셀 플레이트 열교환기에서의 R-l34a, R-407C, R-410A의 응축성능에 관한 실험적 연구 (Study on R-l34a, R-407C, and R-410A Condensation Performance in the Oblong Shell and Plate Heat Exchanger)

  • 박재홍;김영수
    • 대한기계학회논문집B
    • /
    • 제28권12호
    • /
    • pp.1535-1548
    • /
    • 2004
  • Condensation heat transfer experiments were conducted with the oblong shell and plate heat exchanger without oil in a refrigerant loop using R-l34a, R-407C and R-410A. An experimental refrigerant loop has been developed to measure the condensation heat transfer coefficient h$_{r}$ and frictional pressure drop $\Delta$p$_{f}$ of the various refrigerants in a vertical oblong shell and plate heat exchanger. The effects of the refrigerant mass flux(40∼80kg/$m^2$s), average heat flux(4∼8kW/$m^2$), refrigerant saturation temperature(30∼4$0^{\circ}C$) and vapor quality of refrigerants on the measured data were explored in detail. Similar to the case of a plate heat exchanger, even at a very low Reynolds number, the flow in the oblong shell and plate heat exchanger remains turbulent. A comparison of the performance of the various refrigerants revealed that R-410A had the highest heat transfer performance followed by R-l34a, and R-407C had the lowest performance of the refrigerants tested. The pressure drops were also reported in this paper. The pressure drops for R-410A were approximately 45% lower than those of R-l34a. R-407C had 30% lower pressure drops than R-l34a. Experimental results were compared with several correlations which predicted condensation heat transfer coefficients and frictional pressure drops. Comparison with the experimental data showed that the previously proposed correlations gave unsatisfactory results. Based on the present data, empirical correlations of the condensation heat transfer coefficient and the friction factor were proposed.tor were proposed.sed.

초임계 영역내 $CO_2$ 냉각 열전달과 압력강하 분석 (Analysis of Heat Transfer and Pressure Drop During Gas Cooling Process of Carbon Dioxide in Transcritical Region)

  • 손창효;이동건;정시영;김영률;오후규
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제28권1호
    • /
    • pp.65-74
    • /
    • 2004
  • The heat transfer coefficient and pressure drop of $CO_2$(R-744) during gas cooling Process of carbon dioxide in a horizontal tube were investigated experimentally and theoretically. The experiments were conducted without oil in the refrigerant loop. The main components of the refrigerant loop consist of a receiver. a variable-speed pump. a mass flowmeter, an evaporator. and a gas cooler(test section). The main components of the water loop consist of a variable-speed Pump. an constant temperature bath. and a flowmeter. The gas cooler is a counterflow heat exchanger with refrigerant flowing in the inner tube and water flowing in the annulus The test section consists of smooth, horizontal stainless steel tube of 9.53 mm outer diameter and 7.75 mm inner diameter. The length of test section is 6 m. The refrigerant mass fluxes were 200 ~ 300 kg/($m^2{\cdot}s$) and the inlet pressure of the gas cooler varied from 7.5 MPa to 8.5 MPa. The main results were summarized as follows : The predicted correlation can evaluated the R-744 exit temperature from the gas cooler within ${\pm}10%$ for most of the experimental data, given only the inlet conditions. The predicted gas cooley capacity using log mean temperature difference showed relatively food agreement with gas cooler capacity within ${\pm}5%$. The pressure drop predicted by Blasius estimated the pressure drop on the $CO_2$ side within ${\pm}4.3%$. The predicted heat transfer coefficients using Gnielinski's correlation evaluated the heat transfer coefficients on the $CO_2$ side well within the range of experimental error. The predicted heat transfer coefficients using Gao and Honda's correlation estimated the heat transfer coefficients on the coolant side well within ${\pm}10\;%$. Therefore. The predicted equation's usefulness is demonstrated by analyzing data obtained in experiments.

Temperature Control of an Oil Cooler System For Machine Tools Using a Fuzzy- Logic-Based Algorithm

  • Kim, Sun-Chul;Hong, Dae-Sun;Lee, Choon-Man;Kim, Gyu-Tak
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 제어로봇시스템학회 2004년도 ICCAS
    • /
    • pp.1006-1011
    • /
    • 2004
  • Recently, technical trend in machine tools is focused on enhancing of speed, accuracy and reliability. Such high speed usually results in thermal displacement and structural deformation. To minimize such thermal effect, most precision machine tools adopt high precision cooling system. This study proposes a temperature control for an oil cooler system using PI control with fuzzy logic. In a cooler system, the refrigerant flow rate is controlled by rotational speed of the compressor, where the outlet oil temperature is selected as the control variable. The fuzzy control rules iteratively correct PID parameters to minimize the error, difference between the outlet temperature and the reference one. Here, the ambient temperature is used as the reference one. To show the effectiveness of the proposed method, a series of experiments are conducted for an oil cooler system of machine tools, and the results are compared with the ones of a conventional PID control. The experimental results show that the proposed method has advantages of smaller overshoot and smaller steady state error.

  • PDF

마이크로핀관 내 $CO_2$의 증발 열전달과 오일 영향에 관한 실험적 연구 (Experimental Study on Evaporation Heat Transfer and Oil Effect in Micro-fin Tube Using $CO_2$)

  • 이상재;최준영;이재헌;권영철
    • 설비공학논문집
    • /
    • 제20권2호
    • /
    • pp.106-112
    • /
    • 2008
  • In this paper, the experimental results on evaporation heat transfer characteristics were reported for a micro-fin tube using $CO_2$. An experimental refrigerant loop had been established to measure the evaporation heat transfer coefficient and pressure drop of $CO_2$. Experiments were conducted for mass fluxes, heat fluxes, saturation temperatures and PAG oil concentrations. With increasing the heat flux and the saturation temperature, the evaporation heat transfer coefficient increased. At the higher mass flux, however, the exit vapor quality of the micro-fin tube was to be lower. The peak of the heat transfer coefficient was shifted toward low quality region. The evaporation pressure drop increased as the mass flux increased and the saturation temperature decreased. As PAG oil concentration increased, the evaporation heat transfer coefficient decreased and the dryout was delayed by oil addition.

$CO_2$/오일 시스템에서 P-$\upsilon$-T-$\chi$ 관계의 측정 및 예비 해석 (Measurement and preliminary analysis of P-$\upsilon$-T-$\chi$ relation for $CO_2$/oil systems)

  • 유한연;박경근;강병하
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2007년도 동계학술발표대회 논문집
    • /
    • pp.652-657
    • /
    • 2007
  • This paper is an interim report on the investigation of thermodynamic properties of $CO_2$/oil mixture refrigerant. First, liquid density of POE (poly-ol ester) and PAG (poly alkylene glycol) were measured and expressed as a function of temperature. Then, a solubility equation was developed which enables us to calculate the weight fraction of $CO_2$ for the mixture in a liquid state. An experimental apparatus with a cell was constructed to measure P-$\upsilon$-T-$\chi$ data for $CO_2$/oil mixture. The volume of the cell was determined using a certain formula considering change in volume as a function of temperature and pressure. Then, experimental data were obtained over the temperatures $40^{\circ}C$, $50^{\circ}C$, $60^{\circ}C$, $70^{\circ}C$ and $80^{\circ}C$ with various mole fractions. Finally, assuming a primitive model of ideal gas, the volume of $CO_2$/oil mixture was predicted with a relatively larger error of 5.05% for $CO_2$/PAG and 8.81% for $CO_2$/POE. The volume of $CO_2$/oil mixtures would be better predicted using an appropriate equation of state, of which results will be reported soon.

  • PDF

재냉기를 이용한 고성능 VI(Vapor Injection)사이클 열펌프의 냉방 성능특성에 관한 연구 (Cooling Performance Characteristics of High-Performance Heat Pump with VI Cycle Using Re-Cooler)

  • 이진국;최광환
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제39권6호
    • /
    • pp.592-598
    • /
    • 2015
  • 본 연구에서는 공랭식 VI(Vapour-Injection) 사이클을 적용한 R410A용 고성능 하절기 냉방 열펌프의 성능 특성을 실험적으로 규명하였다. 실험에 사용한 장치는 VI 압축기, 응축기, 유분리기, 판형열교환기, 에코노마이져(economizer), 증발기, 그리고 재냉기(re-cooler)로 구성하였다. 냉방 성능 실험 조건은 다음과 같이 3가지 사이클로 VI 사이클을 적용하고 증발기 출구 냉매와 VI사이클 흡입 냉매가 재냉기에서 서로 열교환 하지 않는 사이클(사이클 A)과 열교환을 하는 사이클(사이클 B), 그리고 VI 사이클도 적용하지 않고 증발기 출구 냉매와 VI 사이클 흡입 냉매와의 열교환도 없는 사이클(사이클 C)로 구분하였다. 분석 결과, 냉방 성능은 증발기 출구 냉매와 VI사이클 흡입 냉매가 서로 열교환하는 VI사이클(사이클 B)이 가장 높았으며 VI사이클을 적용하지 않은 사이클 C가 가장 낮음을 알 수 있었으며, 사이클B의 냉방성능계수($COP_C$)가 평균 3.5로 사이클A보다 8.6%, 사이클C보다 33% 높은 값을 나타내었다.

CO2용 실외열교환기의 오일 영향에 따른 성능변화에 대한 실험적 연구 (An Experimental Study on Oil Effect of CO2 in Heat Pump Outdoor Heat Exchanger)

  • 이진관;장영수;김서영;김용찬
    • 설비공학논문집
    • /
    • 제23권4호
    • /
    • pp.243-250
    • /
    • 2011
  • In order to investigate the effects of PAG oil concentration on heat transfer performance and pressure drop during gas cooling process of $CO_2$, the experiments on fin-tube heat exchanger of $CO_2$ heat pump were performed. The experimental apparatus consists of a gas cooler, a heater, a chiller, a mass flow meter, a pump and measurement system. Experiments were conducted in various experimental conditions, which were inlet temperature($110^{\circ}C$), mass flow rates (50, 55, 60, 65, 70 g/s) and PAG oil concentration(0 to 2.6 wt%). Heat transfer rate decreased with the increase of the oil concentration and the decrease of inlet pressure. And pressure drop increased with the increase of the oil concentration and mass flow rate of refrigerant. The COP reduction by deterioration of gas cooler performance with oil concentration was analyzed. When inlet pressure of gas cooler is 100 bar, the COP reduction was estimated by 6% under 1 wt% of oil concentration.

Dynamic Analysis of the Piston Slap Motion in Reciprocating Compressors

  • Kim, Tae-Jong
    • 한국윤활학회:학술대회논문집
    • /
    • 한국윤활학회 2002년도 proceedings of the second asia international conference on tribology
    • /
    • pp.411-412
    • /
    • 2002
  • Piston-cylinder system are widely used in power engineering applications. In reciprocating refrigeration compressors, where extremely low friction losses are required, ringless pistons are being used to diminish the friction between piston rings and cylinder wall. Since the ringless piston has the freedom of lateral motion there is a potential danger that it will occasionally hit the cylinder wall while moving up and down along it's axis. A good design must therefore provide a smooth and stable reciprocating motion of the piston and ensure that the fluid film separating the piston from the cylinder wall is maintained all times. And the compromise between refrigerant gas leakage through the piston-cylinder clearance and the friction losses is required utilizing a dynamic analysis of the secondary motion for the high efficiency compressor. To this end, the computer program is developed for calculating the entire piston trajectory and the lubrication characteristics as functions of crank angle under compressor running conditions. The results explored the effects of some design parameters and operating conditions on the stability of the piston, the oil leakage, and friction losses.

  • PDF