• Title/Summary/Keyword: Reactor cavity cooling system

Search Result 16, Processing Time 0.019 seconds

EVALUATION OF METHODOLOGY FOR AXISYMMETRIC SIMULATION OF RCCS IN VHTR (초고온가스로의 RCCS 해석을 위한 축대칭 모사 방법론 평가)

  • Kim, S.H.;Cho, B.H.;Tak, N.I.;Kim, M.H.
    • Journal of computational fluids engineering
    • /
    • v.15 no.1
    • /
    • pp.1-8
    • /
    • 2010
  • RCCS is a passive safety-related system that removes the decay heat of VHTR when normal decay heat removal systems are in failure. Understanding thermo-hydraulics of RCCS is important to design a safer VHTR. RCCS consists of 292 cooling panels, which are placed in the reactor cavity. The layout of RCCS gives an idea that, for CFD simulations, cooling panels can be assumed to be one annulus tube. This assumption can reduce significantly the computational time, especially for the unsteady simulation. To simulate RCCS in an axisymmetric manner, three models were suggested and compared. Each model has (1) the same outer radius, (2) the same cross-sectional area (3) the same pressure drop, respectively, as the RCCS cooling panels. The steady-state simulation was conducted with these three models and the DO radiation model. It is found that over 90% of the heat from the outer wall of the reactor pressure vessel is transported to the RCCS by radiative heat transfer. The simulation with the third model, which has the same pressure drop as the design, estimates the closest wall temperature profiles to a thermo-hydraulic code, GAMMA+, result.

EXPERIMENTAL STUDY ON MEASUREMENT OF EMISSIVITY FOR ANALYSIS OF SNU-RCCS

  • CHO YUN-JE;KIM MOON OH;PARK GOON-CHERL
    • Nuclear Engineering and Technology
    • /
    • v.38 no.1
    • /
    • pp.99-108
    • /
    • 2006
  • SNU-RCCS is a water pool type RCCS (Reactor Cavity Cooling System) developed for VHTR (Very High Temperature Reactor) application by SNU (Seoul National University). Since radiation heat transfer is the major process of passive heat removal in a RCCS, it is important to determine the precise emissivity of the reactor vessel. Review studies have used a constant emissivity in the passive heat removal analysis, even though the emissivity depends on many factors such as temperature, surface roughness, oxidation level, wavelength, direction, atmosphere conditions, etc. Therefore, information on the emissivity of a given material in a real RCCS is essential in order to properly analyze the radiation heat transfer in a VHTR. The objectives of this study are to develop a method for compensation of the factors affecting the emissivity measurement using an infrared thermometer and to estimate the true emissivity from the measured emissivity via the developed method, especially in the SNU-RCCS environment. From this viewpoint, we investigated factors such as the attenuation effect of the window, filling gas, and the effect of background radiation on the emissivity measurements. The emissivity of the vessel surface of the SNU-RCCS facility was then measured using a sight tube. The background radiation was subsequently removed from the measured emissivity by solving a simultaneous equation. Finally, the calculated emissivity was compared with the measured emissivity in a separate emissivity measurement device, yielding good agreement with the emissivity increase with vessel temperature in a range of 0.82 to 0.88.

Evaluation of Pressure History due to Steam Explosion (증기폭발에 의한 압력이력 평가)

  • Kim, Seung Hyun;Chang, Yoon-Suk;Song, Sungchu;Hwang, Taesuk
    • Transactions of the Korean Society of Mechanical Engineers A
    • /
    • v.38 no.4
    • /
    • pp.355-361
    • /
    • 2014
  • Steam explosions can be caused by fuel-coolant interactions resulting from failure of the external vessel cooling system in a new nuclear power plant. This can threaten the integrity of structures, including the nuclear reactor and the containment building. In the present study, an improved technique for analyzing the steam explosion phenomenon was proposed on the basis of previous research and was verified by simulations involving alumina experiments. Also, the improved analysis technique was applied to determine the pressure history of the reactor cavity in accordance with postulated failure locations. The results of the analysis revealed that the effects of vessel side failure are more serious than those of vessel bottom failure, with approximately 70% higher maximum pressure.

Effect of inlet throttling on thermohydraulic instability in a large scale water-based RCCS: A system-level analysis with RELAP5-3D

  • Zhiee Jhia Ooi;Qiuping Lv;Rui Hu;Matthew Jasica;Darius Lisowski
    • Nuclear Engineering and Technology
    • /
    • v.56 no.5
    • /
    • pp.1902-1912
    • /
    • 2024
  • This paper presents results from system-level modeling of a water-based reactor cavity cooling system using RELAP5-3D. The computational model is benchmarked with experimental data from a half-scale RCCS test facility at Argonne National Laboratory. The model prediction is first compared with a two-phase oscillatory baseline experimental case where mixed accuracy is obtained. The model shows reasonable prediction of mass flow rate, pressure, and temperature but significant overprediction of void fraction. The model prediction is then compared with a fault case where the inlet of the risers is gradually reduced using a throttling valve. As the valve is closed, the model is able to predict some major flow phenomena observed in the experiment such as the dampening of oscillations, the reintroduction of oscillations, as well as boiling, flashing, and geysering in the risers. However, the timeline of these events are not well captured by the model. The model is also used to investigate the evolution of flow regime in the chimney. This work highlights that the semi-empirical constitutive relations used in RELAP-3D could have a strong influence on the accuracy of the model in two-phase oscillatory flows.

Development of an on-demand flooding safety system achieving long-term inexhaustible cooling of small modular reactors employing metal containment vessel

  • Jae Hyung Park;Jihun Im;Hyo Jun An;Yonghee Kim;Jeong Ik Lee;Sung Joong Kim
    • Nuclear Engineering and Technology
    • /
    • v.56 no.7
    • /
    • pp.2534-2544
    • /
    • 2024
  • This paper proposes a flooding safety system (FSS) and its operation strategy that can provide long-term safety and effective maintenance for modules of small modular reactor (SMR) and metal containment maintained at dried environment during normal operation. During hypothesized accidents, the FSS re-collects the evaporated steam into the common pool by the condenser installed above the common water pool and provides an emergency coolant for the cavities and auxiliary pools. This study suggested that the condensate re-collection strategy using the FSS can effectively delay the depletion of available water in response to the accidents. Without recollection, the achievable grace periods ranged from 44 to 1507 days for six-module and one-module accidents, respectively. However, with a full re-collection (ratio = 1.0), the time to total depletion of emergency coolant was estimated indefinite. Even with a partial re-collection ratio of 0.3, a grace period of 83.5 days could be ensured for a six-module transient. This study reported the effectiveness of condensate re-collection and the FSS as an innovative safety management strategy and system. Employing a condensate re-collection strategy with a high re-collection ratio can enhance the long-term safety and effective convenience of SMR operations and maintenance.

Effect of inlet throttling on thermohydraulic instability in a large scale water-based RCCS: An experimental study

  • Qiuping Lv;Matthew Jasica;Darius Lisowski;Zhiee Jhia Ooi;Rui Hu;Mitch Farmer
    • Nuclear Engineering and Technology
    • /
    • v.56 no.2
    • /
    • pp.655-665
    • /
    • 2024
  • The objective of the present experimental study is to investigate the effect of inlet throttling on the thermohydraulic stability of a large scale water-based Reactor Cavity Cooling System (RCCS). The test was performed using the water-based Natural convection Shutdown heat removal Test Facility (NSTF) at Argonne, which represented a ½ axial scale and 12.5° sector slice of the full scale Framatome 625 MWt SC-HTGR RCCS concept. A two-phase steady state was first established through direct condensate refill, followed by increased inlet throttling over 10 stages, corresponding to a loss coefficient K over the range of 0.05-653. With the inlet throttling gradually increased, the system experienced a unique transition process between stabilization and destabilization. Through a stability analysis, three instability mechanisms were identified in the present test, including a compound mechanism due to both natural circulation oscillations (NCOs) and density wave oscillations (DWOs), Type-II DWOs, and geysering.