• Title/Summary/Keyword: Radiate electromagnetic wave

Search Result 5, Processing Time 0.019 seconds

A Study of the Characteristics of a Partial Discharge of SF6 Following a Fault

  • Yoon, Dea-Hee;Song, Hyun-Jig;Lee, Kwang-Sik
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.9
    • /
    • pp.18-24
    • /
    • 2007
  • When faults occur in the power equipment that is used a great deal in industrial sites, it may lead to fatal accidents that cause losses both economically and in manpower. In this paper, the effect of particle impact on the partial discharge of $SF_6$ gas was measured by simulating a partial discharge following the type of fault found in the GIS using $SF_6$ insulating gas as the insulating material. A spectrum analysis was performed on the radiate electromagnetic waves emitted upon partial discharge by using the UHF insulation diagnosis method. This subject of this study is insulation diagnosis by the measurement of radiate electromagnetic waves when particles exist in the GIS and power equipment insulated with $SF_6$ gas.

A Study on Optimizing Energy Transfer of Capacitive Switching Antenna (Capacitive Switching Antenna의 최적 에너지 전달에 관한 연구)

  • Kim, Jin-Man;Bang, Jeong-Ju;Huh, Chang-Su
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.62 no.2
    • /
    • pp.232-238
    • /
    • 2013
  • In this paper we describe the maximum energy transfer of CSA(Capacitive Switching Antenna). CSA which is radiated antenna system contain energy storage and switch, antenna needs to high voltage source for electrical field radiation experiment. In this experiment we employed Marx generator as a charging source. CSA can radiate electrical field more efficiently by varying antenna capacitance. The electromagnetic generation system which was using CSA has some advantages which are more simple and more effective compared to exist system. We evaluated the performance of electromagnetic wave generating system using CSA. As a result UWB gain of system is 0.47, It is higher level than exist system is 0.3. Radiated electrical field strength at 1m is 70kV/m. It is measured by D-dot sensor and gap distance is 20mm. Center frequency of CSA is approximately 25MHz. When vary the antenna gap distance from 50mm to 20mm, we can find the radiation field strength is decrease and antenna center frequency is increased. We also simulated the energy transfer efficiency to compare with experiment result. Consequentially, CSA needs to appropriate capacitance which is similar value from marx generator for maximum energy transfer, and gap is less than 1mm to increase the CSA capacitance.

Circuit Design of Ultraviolet Flame-Sensor for Fire-Fighting Appliances (자외선 센서를 이용한 화재감지기 응용 회로 설계)

  • Kim, Yeong-Min;Kim, Jong-Man
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2008.04c
    • /
    • pp.1-5
    • /
    • 2008
  • In this paper, we proposed that when combustible burn with ultraviolet radiation, introduce fire detector with sensor of private-use detectable light energy as ultraviolet in energy of electromagnetic-wave type radiate from flame. This research using ultraviolet flame sensor is pyro-electric ultraviolet sensor based black body radiation theory. To have high sensibility and to gain proper output voltage, it has high responsive performance. This research introduced UV flame detector and proposed method of false alarm reduced to resemble fire. the result proposed the prevention and extinction of fire technique degree, certificated operation of detector.

  • PDF

Driving Method of Ultraviolet Sensor for Fire alarms using Pulse Width Modulation (PWM을 이용한 화재 감지를 위한 자외선 센서의 구동 방법)

  • Lim, Byung-Hyun;Ko, Nak-Yong;Hwang, Jong-Sun;Kim, Yeong-Min
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.05c
    • /
    • pp.31-35
    • /
    • 2004
  • We propose driving method of Ultraviolet sensor for fire alarms using pulse width modulation that used to fire detector with sensor of private-use detectable light energy as ultraviolet in energy of electromagnetic-wave type radiate from flame, when combustible burn with contain carbon,. Ultraviolet sensor is UV Tron using gas multiplication effect to current discharge and photoelectric effect of metal. To have high sensibility and to gain proper output voltage, it has high responsive performance. This research designed driving circuit with UV sensors and proposed method of false alarm reduced to resemble fire. the result propers the prevention and extinction of fire technique degree, certificated operation of detector.

  • PDF

Introduction of Ultraviolet/Infrared Flame Detector and Method for False Detection Prevention (자외선/적외선 불꽃감지기 소개 및 오동작 방지를 위한 연구)

  • Lim, Byung-Hyun;Ko, Nak-Yong;Hwang, Jong-Sun;Kim, Yeong-Min;Kim, Jong-Man
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.05b
    • /
    • pp.8-11
    • /
    • 2003
  • We propose that when combustible burn with contain carbon, introduce fire detector with sensor of private-use detectable light energy as infrared and ultraviolet in energy of electromagnetic-wave type radiate from flame, method for correct discrimination to resemble fire produce false alarm of detector such as sun light, hot object radiation, are welding. This research using infrared sensor is pyroelectric infrared sensor based black body radiation theory. Ultraviolet sensor is uv Tron using gas multiplication effect to current discharge and photoelectric effect of metal. To have high sensibility and to gain proper output voltage, it has high responsive performance. This research introduced UV/IR compound type flame detector and proposed method of false alarm reduced to resemble fire. The result propres the prevention and extinction of fire technique degree, certificated operation of detector.

  • PDF