• Title/Summary/Keyword: Quench characteristics

Search Result 220, Processing Time 0.028 seconds

Simultaneous Quench Analysis of a Three-Phase 6.6 kV Resistive SFCL Based on YBCO Thin Films (YBCO 박막을 이용한 3상 6.6kV 항형 초전도 한류기의 동시Quench 분석)

  • Sim J;Kim H. R;Hyun O. B
    • Progress in Superconductivity
    • /
    • v.6 no.1
    • /
    • pp.46-51
    • /
    • 2004
  • We fabricated a resistive type superconducting fault current limiter (SFCL) of 3-phase $6.6 kV_{rms}$ / rating, based on YBCO thin films grown on sapphire substrates with a diameter off inch. Each element of the SFCL was designed to have the rated voltage of $600 V_{rms}$ $/35A_{rms}$. The elements produced a single phase with 8${\times}$6 components connected in series and parallel. In addition, a NiCr shunt resistor of 23 $\Omega$ was connected in parallel to each of them for simultaneous quenches between the elements. Prior to investigating the performance of the 3 phase SFCL, we examined the quench characteristics for 8 elements connected in series. For all elements, simultaneous quenches and equal voltage distribution within 10% deviation from the average were obtained. Based on these results, performance of the SFCL for single line-to-ground faults was investigated. The SFCL successfully limited the fault current of $10 kA_{ rms}$ below 816 $A_{peak}$ within 0.12 msec right after the fault occurred. During the quench process, average temperature of all components did not exceed 250 K, and the SFCL was totally safe during the whole operation.

  • PDF

Stability and Quench Charcteristics of the SC Conductor for a $\mu$SMES Magnet ($\mu$SMES마그네트용 초전도도체의 안정성 및 퀀치 특성)

  • 김해종;성기철;조전욱;권영길;류강식;최병주;류경우
    • Progress in Superconductivity and Cryogenics
    • /
    • v.2 no.1
    • /
    • pp.19-23
    • /
    • 2000
  • We are developing a small-sized superconducting magnetic energy storge ($\mu$SMES) magnet with the storage capacity of a few megajoules, which provides electric power with high quality to sensitive electric loads. A kA class superconductor with a high coppe $r^erconductor ratio was selected as a candidate conductor. The superconductor was tested in two points of view, which are basic and important in development of the $\mu$SMES magnet. First, stabilities of the superconductor against localized disturbances such as wire motions were estimated by using a wire heater. Second, the quench current characteristics for different charge rates were also tested. The stability data showed that the short heat pulses made the conductor more unstable. The superconductor had relatively high recovery currents ranging between 40% and 50% of its critical currents. The quench tests indicated that the quench currents of the conductor were independent of current ramp rates up to 3000 A/s and nearly equal to its cuitical current data.ta.

  • PDF

A study on the Detection of Premature Quench Generated in the Process of Current Pumping in a Superconducting Power Supply (초전도 Power Supply의 전류펌핑 과정에서 발생하는 조기 퀜치발생 진단)

  • Kim, Ho-Min;Bae, Joon-Han;Noh, Jeong-Sub;Sim, Ki-Deok;Jang, Won-Kap;Ko, Tae-Kuk
    • Proceedings of the KIEE Conference
    • /
    • 1997.07a
    • /
    • pp.244-246
    • /
    • 1997
  • This paper is to analyze the Premature Quench characteristics of a rotating magnet type superconducting fluxpump and consider the method of detecting and protecting this premature quench. Practically, there is contact resistance between the fluxpump and the load, namely the S.C. magnet. The thermal increase due to the contact resistance cause the premature quench before the charging current amounts to the critical current of S.C magnet. Therefore, this paper is devoted to solving the heat equation on contact region using cylindrical coordinates and to calculating the rate of thermal increase during the current is pumped up. Doing so, the predictive value of the maximum pumping current is obtained. It has been verified that the results of simulation are coincident with those of experiment. It must be considered essentially to minimize the contact resistance in designing the S.C fluxpump system in order to protect the premature quench and improve the maximum pumping current.

  • PDF

Analysis on Fault Current Limiting Operation of Three-Phase Transformer Type SFCL Using Double Quench (이중퀜치를 이용한 삼상변압기형 한류기의 고장전류제한 동작 분석)

  • Han, Tae-Hee;Ko, Seok-Cheol;Lim, Sung-Hun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.35 no.2
    • /
    • pp.184-189
    • /
    • 2022
  • In this paper, the fault current limiting operations of three-phase transformer type superconducting fault current limiter (SFCL) using double quench, which consisted of E-I iron core with three legs wound by primary and secondary windings and two superconducting modules (SCMs), were analyzed according to three-phase ground fault types. To verify the effective operation of the three-phase transformer type SFCL using double quench, the test circuit for three-phase ground faults was constructed, and the fault current tests were carried out. Through analysis on the fault current test results, the different fault current limiting characteristics of three-phase transformer type SFCL using double quench from three-phase transformer type SFCL using three SCMs were discussed.

Analysis of Fault Current limiting Characteristics According to Fault Type in Integrated Three-Phase Flux-Lock Type Superconducting Fault Current limiting (사고종류에 따른 삼상 일체화된 자속구속형 SFCL의 사고전류제한특성 분석)

  • Park, Chung-Ryul;Lim, Sung-Hun;Park, Hyoung-Min;Cho, Yong-Sun;Choi, Hyo-Sang;Han, Byoung-Sung
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.07a
    • /
    • pp.54-56
    • /
    • 2005
  • In this paper, we investigated the quench characteristics of HTSC elements in the integrated three-phase flux-lock type SFCL according to fault types such as the single-line-to-ground fault, the double-line-to-ground fault, the line-to-line fault and the three-line-to-ground fault. The integrated three-phase flux-lock type SFCL was the upgrade version of the single-phase flux-lock type SFCL. The structure of the integrated three-phase flux-lock type SFCL consisted of three-phase flux-lock reactor wound on an iron core with the ratio of the same turn between coil 1 and coil 2 in each phase. When the SFCL is operated under the normal condition, the flux generated in the iron core is zero because the flux generated between two coils of each single phase is canceled out. Therefore, the SFCL's impedance is zero, and the SFCL has negligible influence on the power system. However, if a fault occurs in any single-phase among three phases, the flux generated in the iron core is not zero any more. The flux makes HTSC elements of all phases quench irrespective of the fault type, which reduces the current of fault phase as well as the current of sound phase. It was observed that the fault current limiting characteristics of the suggested SFCL were dependent on the quench characteristics of HTSC elements in all three phases.

  • PDF

Quench Characteristics of HTSC Elements according to fault types in Integrated Three-Phase (삼상일체화된 자속구속형 SFCL의 사고종류에 따른 소자들의 퀜치 특성)

  • Park, Chung-Ryul;Lee, Jong-Hwa;Park, Sig;Du, Ho-Ik;Lim, Sung-Hun;Choi, Hyo-Sang;Han, Byoung-Sung
    • Proceedings of the KIEE Conference
    • /
    • 2005.07b
    • /
    • pp.960-962
    • /
    • 2005
  • In this paper, we investigated the quench characteristics of high-Tc superconducting(HTSC) elements in the integrated three-phase flux-lock type superconducting fault current limiter(SFCL) according to fault types such as the single-line-to-ground fault, the double-line-to-ground fault, the line-to-line fault and the triple-line-to-ground fault. The integrated three-phase flux-lock type SFCL is an upgrade version of single-phase flux-lock type SFCL. The structure of the integrated three-phase flux-lock type SFCL consisted of a three-phase flux-lock reactor wound on an iron core with the ratio of the same turn between coil 1 and coil 2 in each phase. When the SFCL is under the normal condition, the flux generated in the iron core is zero because the flux generated between two coils of each single phase is canceled out. Therefore, the SFCL's impedance is zero, and the SFCL has negligible influence on the power system. However, if a fault occurs in any single one of three phases, the flux generated in the iron core is not zero any more. The flux makes HTSC elements of all phases to quench irrespective of the fault type, which reduces the current in fault phase as well as the current of sound phase. It was obtained that the fault current limiting characteristics of the suggested SFCL were dependent on the quench characteristics of HTSC elements in all three phases.

  • PDF

Analysis of Quench Generation in Fault Types According to Inductance Variation in Integrated Three-Phase Flux-Lock Type Superconducting Fault Current Limiting (삼상일체화된 자속구속형 고온초전도 전류제한기의 인덕턴스 변화에 따른 사고유형별 퀜치발생 분석)

  • Park, Chung-Ryul;Lim, Sung-Hun;Park, Hyoung-Min;Cho, Yong-Sun;Choi, Hyo-Sang;Han, Byoung-Sung
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.165-166
    • /
    • 2005
  • In this paper, we investigated the quench generation of HTSC elements in fault types according to inductance variation in the integrated three-phase flux-lock type SFCL. The integrated three-phase flux-lock type SFCL was the upgrade version of the single-phase flux-lock type SFCL. The structure of the integrated three-phase flux-lock type SFCL consisted of three-phase flux-lock reactor wound on an iron core with the ratio of the same turn between coil 1 and coil 2 in each phase. When the SFCL is operated under the normal condition, the flux generated in the iron core is zero because the flux generated between two coils of each single phase is canceled out. Therefore, the SFCL's impedance is zero, and the SFCL has negligible influence on the power system. However, if a fault occurs in any single-phase among three phases, the flux generated in the iron core is not zero any more. The flux makes HTSC elements of all phases quench irrespective of the fault type, which reduces the current of fault phase as well as the current of sound phase. It was observed that the fault current limiting characteristics of the suggested SFCL were dependent on the quench characteristics of HTSC elements in all three phases.

  • PDF

Preliminary study on the quench protection of Bi-22231 Ag tape using superconducting fault current limiter (초전도 한류기를 이용한 Bi-2223/Ag 선재의 퀜치 보호를 위한 기초 연구)

  • Du, Ho-Ik;Yim, Seong-Woo;Hyun, Ok-Bae;Hwang, Si-Dole;Cho, Chul-Yong;Park, Chung-Ryul;Han, Byoung-Sung
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2006.06a
    • /
    • pp.243-244
    • /
    • 2006
  • As an preliminary study for the quench protection of high temperature superconducting (HTS) cable using superconducting fault current limiter (SFCL), experimental research was carried out. The test circuit was composed of Bi-2223/Ag HTS tape and a SFCL made of YBCO thin films. In the normal state, the applied current of 56 A, which was critical current of HTS tape, could be flown through the circuit without resistive loss. Increasing the currents, the quench development of both materials was investigated from the voltage signal acquired from the resistance of the quenched superconductor. Up to around 10 times of the critical current was applied to the HTS tape and the current limiting characteristics of SFCL were investigated. In addition, for the finding out the optimal operating condition of SFCL such as the numbers of elements, a shunt resistor was applied to the SFCL and quench characteristics were analyzed as well.

  • PDF

Analysis on operation characteristics and power burdens of the double quench trigger type SFCLs

  • Lim, Seung-Taek;Lim, Sung-Hun;Han, Tae-Hee
    • Progress in Superconductivity and Cryogenics
    • /
    • v.19 no.2
    • /
    • pp.33-37
    • /
    • 2017
  • To protect the power systems from fault current, the rated protective equipment should be installed. However growth of power system scale and concentration of loads caused the large fault current in power transmission system and distribution system. The capacities of installed protective equipment have been exceeded the due to increase of fault current. This increase is not temporary phenomenon but will be steadily as long as the industry develops. The power system operator need a counter-measurement for safety, so superconducting fault current limiter (SFCL) has been received attention as effective solutions to reduce the fault current. For the above reasons various type SFCLs have been studied recently. In this paper, operation characteristics and power burden of trigger type SFCL is studied. The trigger type SFCL has been used for real system research in many countries. Another trigger type SFCL (double quench trigger type SFCL) is also studied. For this paper, short circuit test is performed.

Quench Characteristics of Flux-lock type Superconducting Fault Current Limiter using Open-loop Iron Core (개루프 철심을 이용한 자속구속형 초전도한류기의 퀜치특성)

  • Nam, Gueng-Hyun;Choi, Hyo-Sang;Park, Hyoung-Min;Cho, Yong-Sun;Lee, Na-Young;Lim, Sung-Hun;Park, Chung-Ryul
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.159-160
    • /
    • 2005
  • The superconducting fault current limiter(SFCLs) provides the effect such as enhancement in the power system reliability due to limiting fault current in a few miliseconds. The Flux-lock type SFCL using the YBCO film among various type SFCLs consists of the primary and the secondary copper coils that are wound in parallel each other through the iron core. The operation can be controlled by adjusting the inductances and the winging directions of each the coil. We compared the current limiting performance on the additive and the subtractive polarity winding directions in case of an open-loop iron core. To analyze quench characteristics, we experimented various phase angle.

  • PDF