• 제목/요약/키워드: Publicly used establishments

검색결과 4건 처리시간 0.016초

Analysis of evacuation time for New publicly used establishments according to whether safety facilities, etc. are installed

  • Hong-Sang Lee;Ha-Sung, Kong
    • International Journal of Internet, Broadcasting and Communication
    • /
    • 제15권2호
    • /
    • pp.49-59
    • /
    • 2023
  • In accordance with the revision of "Special act on the safety control of publicly used establishments", this study is aim to measure the change in evacuation time due to whether safety facilities, etc. are installed of a room escape cafe business and kids cafe business(hereinafter referred to as "New publicly used establishments"), which were added as new targets of the publicly used business from June 8, 2022. In the case of new publicly used establishments or publicly used establishments whose owners are changed after the revision of the relevant laws, safety facilities, etc. are installed and maintained under the "Special act on the safety control of publicly used establishments", but in the case of existing businesses that have been operating even before the revision of the law, the business continues without safety facilities, etc. installed because the revised law is not retroactively applied. The purpose of this study is to compare and analyze the change in evacuation time by measuring the evacuation time to operating before the revision of the law to simulate evacuation at existing new publicly used establishments without safety facilities, etc. and measure the evacuation time at new publicly used establishments with safety facilities after the revision of the law

간이스프링클러 설비의 소화성능 향상에 관한 실험적 연구 (An Experimental Study on Improvement of Fire Extinguishing Performance of Basic Sprinkler System)

  • 허민녕;신창섭
    • 한국안전학회지
    • /
    • 제33권3호
    • /
    • pp.46-51
    • /
    • 2018
  • A basic sprinkler system is a fire extinguishing system that can be easily installed in a fire-vulnerable place such as a publicly used establishments. However, the publicly used establishments are not only complicated in structure, but also have a large amount of flammable interior materials, and the users are not normally in a normal state, which is a very dangerous fire-fighting object. Therefore, due to the low fire extinguishing performance of the basic sprinkler system installed in the publicly used establishments, the fire suppression control can not be performed quickly in case of fire, which may increase the life and property damage. In this study, the cases of quantitative changes of extinguishing water used in basic sprinkler system and the cases of addition of additives such as wetting agents, reinforced agents to improve extinguishing performance were compared. Experimental results showed that the extinguishing performance was improved as the quantity of extinguishing water increase and the reinforced agents showed similar performance to that of 60% increase in the amount of extinguishing water. The cooling time to $200^{\circ}C$ and oxygen concentration were improved up to 14.3% and 34.5%, respectively. In the case of using the wetting agent, the cooling time to $200^{\circ}C$ and oxygen concentration did not show any significant improvement, but showed the effect of preventing deep seated fire. In order to prevent loss of life and property, it is necessary to improve the performance of the basic sprinkler system by increasing amount of extinguishing water or using additives like reinforced agents.

Delphi/AHP를 활용한 다중이용업 신종업종의 화재위험평가지표 분석 (Analysis of Fire Risk Assessment Indicators of Publicly-Used Establishments using Delphi/AHP)

  • 김명철;김학중;박경환;윤해권;이승호
    • 한국화재소방학회논문지
    • /
    • 제33권6호
    • /
    • pp.87-94
    • /
    • 2019
  • 국민권익위원회 2018년 7월 17일 보도 자료에 의하면 방탈출카페, 실내양궁장 등 신종업종이 다중이용업에서 제외되어 지정을 검토하고 화재예방 대책을 수립하도록 소방청에 권고하였다. 본 연구는 Delphi 기법으로 다중이용업 신종업종의 화재위험평가 측정영역 및 측정지표를 계층화하고 적합도(3.00 이상) 분석결과, 적합도 평균값이 4.25로서 적합성을 확보하였다. AHP 분석결과, 화재위험평가 측정영역의 일관성 비율은 4.0%로서 CR ≤ 0.1(10%) 보다 낮게 분석되었고 하위 측정지표의 일관성 비율도 0.1%~3.6%로서 모두 일관성이 있음을 확인하였다. 통합 측정지표의 중요도와 우선순위는 영업장 내부통로의 형태 및 출구의 피난능력(0.316), 점화원관리(0.141), 고유위험(0.106), 화재감지시스템의 적절성 및 적응성(0.097), 가연물관리(0.084), 피난안내 및 피난설비(0.075), 내화구조 및 마감재료(0.060), 구획 및 비상구(0.049), 연소확대위험(0.046), 소화설비의 적절성 및 적응성(0.026)의 순으로 도출 되었다. 본 연구는 향후, 화재위험평가지표 개발 연구의 중요한 자료로 널리 활용 될 것이다.

영국 안전규제체계의 분석을 통한 국내 다중이용업소 안전관리체계의 개선방안 연구 (A Study on Improvement of Safety Management System of Publicly Used Establishments Through Analysis of the UK Regulatory Regime)

  • 박수형;윤명오
    • 한국재난정보학회 논문집
    • /
    • 제16권4호
    • /
    • pp.768-783
    • /
    • 2020
  • 연구목적: 국내 다중이용업소는 업종의 특수성 등으로 인하여 화재위험성이 높은 것으로 평가되며, 이에 따라 2006년에 다중이용업소의 안전관리에 관한 특별법이 제정되어 현재까지 운용 중이나 그간 다수의 개정에도 불구하고 개선할 점이 여전히 상존한다. 본 연구는 규제체계의 구축과 운영에 있어 모범국가인 영국의 안전규제체계를 분석함으로써 국내의 다중이용업소 안전관리체계를 근본적으로 개선할 수 있는 방안을 마련하고자 하는 취지에서 수행되었다. 연구방법:본 연구는 비교연구법을 활용하여 국내 다중이용업소의 안전관리체계와 영국의 화재안전 관리체계를 분석하였다. 연구결과: 이러한 정성적 분석의 결과, "관계인", "화재위험평가", "화재안전감사" 등 국내 다중이용업소의 안전관리체계를 개선하기 위해 주목할 만한 제도들을 선정하였고, 이에 추가로 국내의 제반여건을 고려하여 "국내 다중이용업소 소방안전관리체계(안(案))"를 고안하였다. 결론: 본 연구는 다중이용업소의 안전체계를 민간 중심으로 재편하고 특히 화재예방분야에서 정부의 개입을 최소화하는 영국의 사례를 분석함으로써 앞으로 국내의 다중이용업소 안전관리체계를 보다 합리적이고 실효성있는 체계로 개선시킬 수 있는 방안을 제안한다.