• Title/Summary/Keyword: Prevention power system accident

Search Result 60, Processing Time 0.031 seconds

Calculation of Network Analysis and Fault Decision using Equality Constraint Condition with MATLAB (등호제약조건을 이용한 계통 해석 및 고장판단 계산 구현)

  • Yang, Min-Uk;Kim, Kern-Joong;Hwang, In-Jun
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.11
    • /
    • pp.2101-2106
    • /
    • 2009
  • The power system state estimation and prediction are very important for operation. Because that accidents of the Power system are the cause that many devices and etc are damaged. Currently, almost every power systems have 2nd,3rd back-upsystem for prevention of accident. But prevention of accident by miss-operation, due to operator or miss data, has not acounter plan. Because, we need to estimate the power system for correcting miss data and preventing miss operation by operator. We suggest algorithm for integrity of power system network data.

A Classification on the Causes of Wind Turbine Accidents (풍력발전기의 사고 발생요인의 분류)

  • Kim, Gui-Shik;Jeong, Ji-Hyun
    • Journal of Power System Engineering
    • /
    • v.19 no.4
    • /
    • pp.76-81
    • /
    • 2015
  • The production of electricity from wind energy is noticed as economic power generation system in the natural resource. Lately, since lots of wind turbine have installed globally, the accidents have increased gradually. In this paper, we classified domestic information for 10 years, information of new energy and industrial technology development organization(NEDO) for 4years and caithness windfarms information forum(CWIF) for 15 years according to part and cause of wind turbine accident. We found that the main causes of accidents are storm, lightening and carelessness. The results of classifying and analyzing the informations, should be used to take measures on the accident prevention of wind turbine.

Investigation of a Hydrogen Mitigation System During Large Break Loss-Of-Coolant Accident for a Two-Loop Pressurized Water Reactor

  • Dehjourian, Mehdi;Sayareh, Reza;Rahgoshay, Mohammad;Jahanfarnia, Gholamreza;Shirani, Amir Saied
    • Nuclear Engineering and Technology
    • /
    • v.48 no.5
    • /
    • pp.1174-1183
    • /
    • 2016
  • Hydrogen release during severe accidents poses a serious threat to containment integrity. Mitigating procedures are necessary to prevent global or local explosions, especially in large steel shell containments. The management of hydrogen safety and prevention of over-pressurization could be implemented through a hydrogen reduction system and spray system. During the course of the hypothetical large break loss-of-coolant accident in a nuclear power plant, hydrogen is generated by a reaction between steam and the fuel-cladding inside the reactor pressure vessel and also core concrete interaction after ejection of melt into the cavity. The MELCOR 1.8.6 was used to assess core degradation and containment behavior during the large break loss-of-coolant accident without the actuation of the safety injection system except for accumulators in Beznau nuclear power plant. Also, hydrogen distribution in containment and performance of hydrogen reduction system were investigated.

A Study on Development of Open-Phase Protector Having Leakage Current Generation and Incapable Operation Prevention at Open-Phase Accident (결상 시 누전전류 발생과 오동작 방지 기능을 갖는 결상보호기 개발에 관한 연구)

  • Kwak, Dong-Kurl
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.64 no.1
    • /
    • pp.182-187
    • /
    • 2015
  • In the three-phase power system, when any one-phase or two-phases is open-phase, the unbalanced current flows and the single-phase power supplies to three-phase loads. Specially, motor coil and transformer coil receive over-current. As a result, great damage as well as electrical fire can occur to the power system. In order to improve these problems, this paper proposes that an open-phase detection device is designed by a new algorithm using electric potential difference between the resultant voltage of neutral point and ground, and a control circuit topology of open-phase protector is composed of highly efficient semiconductor devices. It improves response speed and reliability. The control algorithm circuit also operates the cut-off of a conventional residual current protective device (RCD) which flows an enforced leakage current to ground wire at open-phase accident. Furthermore, time delay circuit is added to prevent the incapable operation of open-phase protector about instantaneous open-phase not open-phase fault. The time delay circuit improves more reliability.

Detection and Comparison of Surface Defects in Pipe Welds (배관 용접부 표면결함 검출 및 비교)

  • Jung, Yoon-Soo;Gao, Jia-Chen;Ahn, Tae-Hyoung;Kim, Jae-Yeol
    • Journal of the Korean Society of Manufacturing Process Engineers
    • /
    • v.19 no.1
    • /
    • pp.43-48
    • /
    • 2020
  • At present, 24 nuclear power plants are in operation nationwide as the main power source responsible for about 27% of Korea's electricity, and five nuclear power plants are currently under construction. Issues of nuclear safety and reliability have always existed, but after the Fukushima accident, ensuring reliability has become an even more important issue for safety. Compared to other kinds of accidents, the initial response after a nuclear accident is more important than any other accident. Prior to accidents, it is important to be able to predict and judge the accident in advance for the sake of prevention. In this research, non-destructive inspection methods for existing pipe welds include radiographic, ultrasonic, magnetic particle practice, and liquid penetration testing. For this experiment, carbon steel pipes like that of the material used in nuclear pipes were adopted, and specimen welded to the flange (Flange) were manufactured. After testing, the weld specimen were not damaged through the infrared thermography (IRT) experiment. This study attempted to improve the safety of carbon steel pipes through a comparative analysis of finite element analysis.

An Instrumentation System Design for Electrical Accident Prevention of 3-Phase Electrical Control Panel (3상 전기제어반 전기사고 예방을 위한 계측시스템 설계)

  • Kwak, D.K.;Choi, J.K.;Kim, J.J.;Kwon, Y.J.;Song, G.
    • Proceedings of the KIPE Conference
    • /
    • 2016.07a
    • /
    • pp.36-37
    • /
    • 2016
  • The main cause of electrical fires are caused due to short circuit and open circuit. This is generates an instantaneous electric arc or spark accompanied with such electric faults. These arcs generate a pressed wire, contact badness, and a weakness in the wire coating etc.. This research proposes a protection circuit to prevent open-phase accident due to contact failure of electromagnetic contactor, tracking arc fault, open-phase within the three-phase electrical control panel which is the most commonly applied in the industry. The proposed circuit also alarms and cuts off of power system when electrical faults occurs. In addition, the proposed circuit is validated by various electric accident simulator.

  • PDF

A Study on Micom Algorithm Design for Prevention of Serial Parallel Arc Accident (직병렬아크사고 예방을 위한 마이컴 알고리즘 설계에 관한 연구)

  • Choi, Jung-Kyu;Kwak, Dong-Kurl;Choi, Shin-Hyeong;Jung, Do-Young;Kim, Dae-Hwan
    • Proceedings of the KIPE Conference
    • /
    • 2018.11a
    • /
    • pp.9-11
    • /
    • 2018
  • This paper studies on the development of an electric fire prevention system with the detection and alarm in case of parallel arc fault occurrence in low voltage distribution lines. The proposed detector has the characteristics of high speed operation responsibility and superior system reliability from composition using a large number of semiconductor devices. The line voltage is always feedback, and when an arc or a spark occurs, these are detected by the microcomputer. In addition, we design and develop algorithms using high speed and high precision microcomputer. A new conceptual control technique is adopted that RCD cuts-off by forming a forced short circuit between the phase voltage and ground in the event of an electrical accident. Some experimental tests of the proposed system also confirm practicality and the validity of the analytical results.

  • PDF

EXPERT SYSTEM FOR A NUCLEAR POWER PLANT ACCIDENT DIAGNOSIS USING A FUZZY INFERENCE METHOD

  • Lee, Mal-Rey;Oh, Jong-Chul
    • Journal of applied mathematics & informatics
    • /
    • v.8 no.2
    • /
    • pp.505-518
    • /
    • 2001
  • The huge and complicated plants such as nuclear power stations are likely to cause the operators to make mistakes due to a variety of inexplicable reasons and symptoms in case of emergency. That’s why the prevention system assisting the operators is being developed for. First of all. I suggest an improved fuzzy diagnosis. Secondly, I want to demonstrate that a classification system of nuclear plant’s accident investigating the causes of accidents foresees possible problems, and maintains the reliability of the diagnostic reports in spite of improper working in part. In the event of emergency in a nuclear plant, a lot of operational steps enable the operators to find out what caused the problems based on an emergent operating plan. Our system is able to classify their types within twenty to thirty seconds. As so, we expect the system to put down the accidents right after the rapid detection of the damage control-method concerned.

Effect of Spray System on Fission Product Distribution in Containment During a Severe Accident in a Two-Loop Pressurized Water Reactor

  • Dehjourian, Mehdi;Rahgoshay, Mohammad;Sayareh, Reza;Jahanfarnia, Gholamreza;Shirani, Amir Saied
    • Nuclear Engineering and Technology
    • /
    • v.48 no.4
    • /
    • pp.975-981
    • /
    • 2016
  • The containment response during the first 24 hours of a low-pressure severe accident scenario in a nuclear power plant with a two-loop Westinghouse-type pressurized water reactor was simulated with the CONTAIN 2.0 computer code. The accident considered in this study is a large-break loss-of-coolant accident, which is not successfully mitigated by the action of safety systems. The analysis includes pressure and temperature responses, as well as investigation into the influence of spray on the retention of fission products and the prevention of hydrogen combustion in the containment.

Fuzzy-AHP Estimation Technique for Korea High Speed Railway Safety Management (F-AHP 평가수법을 적용한 고속전철 안전성의 평가)

  • Park Tae-Keun;Park Choon-Soo;Seo Sung-Il
    • Proceedings of the KSR Conference
    • /
    • 2004.06a
    • /
    • pp.328-333
    • /
    • 2004
  • Railway is huge traffic system which is operated organically combining all the elements; vehicle, track, electric power, signal/communication, operation, etc. Safety level has ben improved steadily by learning lessons from past accident. But with rapid progress in high-speed, massive, high-frequency transit fresh idea of accident prevention is now in order. In quest of effective and efficient countermeasure, we aim to establish an adequate safety evaluation/management method. Our proposals are basic concept relating to safety analysis of fatal accidents, AHP of Saaty, Fuzzy AHP.

  • PDF