• Title/Summary/Keyword: Prevent Smoke

Search Result 127, Processing Time 0.032 seconds

A Study On Effectiveness of Prevent Smoke Backflow in Apartment (계단식 공동주택 방연풍속 실효성에 대한 연구)

  • Lee, Kwang­Soo;Yoon, Myong­O;Lee, Jun
    • Journal of the Society of Disaster Information
    • /
    • v.17 no.1
    • /
    • pp.1-9
    • /
    • 2021
  • Purpose: The purpose of this study is to analyze the differential pressure and velocity to prevent smoke backflow of Stairways Apartment House fire, and verified the effectiveness of smoke velocity standards proposed by NFSC 501A. Method: The smoke control design of the stairways apartment house of the real model and the performance of the velocity to prevent smoke backflow according to the window opening conditions of the living room were analyzed using the CONTAM program. Result: Although the differential pressure performance of the apartment's smoke control system was satisfactory, it was found that Performance of velocity to prevent smoke backflow did not come out according to the opening condition of the living room window. Conclusion: In the case of Stairways Apartment House, it is necessary to review the method of making exceptions to the 'velocity to prevent smoke backflow' standard required by the National Fire Safety Codes(NFSC 501A)

A Numerical Study on Effective Smoke-Control System of a Rescue Station in a Tunnel Fire (터널내 열차 화재시 효과적인 구난역 제연 설비를 위한 수치 해석 연구)

  • Yang, Sung-Jin;Won, Chan-Shik;Hur, Nahm-Keon;Cha, Chul-Hyun
    • 유체기계공업학회:학술대회논문집
    • /
    • 2006.08a
    • /
    • pp.575-578
    • /
    • 2006
  • In designing smoke-control system of rescue station in train tunnel, a purpose is to prevent a disaster by proposing the jet fan operation together with smoke-control curtain in tunnel fire. This study has investigated the relationship of the Heat Release Rate(HRR) and a adequate ventilation velocity to control the fire propagation in tunnel fire, and has improved the effect of the smoke-control curtain on preventing the flow of pollutants. In this study, Computational Fluid Dynamics(CFD) simulations with ST AR-CD(ver 3.24) were carried out on predicting the fire spreading and the flow of pollutants, considering jet fan operations and effect of smoke-control curtain. Our simulation domain is the full scale model of the 'DAEGWALLYEONG' 1st tunnel. The results represent that ventilation operation can control the fire spreading and pollutants effectively to prevent a disaster.

  • PDF

The Influence on the Stack Effect with the Opening of Smoke Ventilators in High-rise Buildings (초고층 건축물에서 배연창 개방이 연돌효과에 미치는 영향)

  • Lim, Chae-Hyun;Kim, Bum-Gyue;Yeo, Yong-Ju;Park, Yong-Hwan
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2008.04a
    • /
    • pp.209-213
    • /
    • 2008
  • The effects on the performance of natural smoke exhaust ventilators installed in high-rise buildings were analyzed depending on the wind velocities and smoke temperatures using CONTAMW tool. The results showed that the smoke exhaust ventilators can maintain given performances in such conditions as low smoke temperatures and low wind velocities. However, high smoke temperatures and high wind velocities can prevent the smoke ventilators to exhaust smokes from the fire room. Significant changes in stack effects in high-rise buildings can also occur with the opening of smoke ventilators in the fire floor.

  • PDF

A Study on the Performance Improvement Plan of Inflowing Air Emission (유입 공기의 배출 성능 개선방안에 관한 연구)

  • Lee, Hye-Young
    • Journal of the Society of Disaster Information
    • /
    • v.18 no.2
    • /
    • pp.241-251
    • /
    • 2022
  • Purpose: In the event of a fire in a high-rise building, if the smoke control area is not effectively protected, smoke or flames enter the stairwell, making it difficult to evacuate. When inflowing air is discharged from a closed corridor, a negative pressure is formed in the corridor, the pressure in the smoke control area becomes excessively high, and the force required to open the door during evacuation is exceeded. Also, if the air introduced into the hallway is not exhausted, the smoke may flow back into the smoke control area. This paper tried to identify the problems caused by the inflowing air and to find out how to improve the performance. Method: Using the CONTAM program, simulations were performed with the basic conditions and the modified conditions. Result: If the inflowing air was discharged from the sealed corridor, overpressure occurred in the Smoke Control Area and exceeded the opening force, and the prevent smoke backflow was insufficient in the layer where the inflowing air was not discharged. Conclusion: "Differential pressure exhaust damper" application, simultaneous opening of two exhaust dampers, and automatic window installation between corridors and outdoors improved the exhaust performance of inflowing air.

Algorithm for Detection of Fire Smoke in a Video Based on Wavelet Energy Slope Fitting

  • Zhang, Yi;Wang, Haifeng;Fan, Xin
    • Journal of Information Processing Systems
    • /
    • v.16 no.3
    • /
    • pp.557-571
    • /
    • 2020
  • The existing methods for detection of fire smoke in a video easily lead to misjudgment of cloud, fog and moving distractors, such as a moving person, a moving vehicle and other non-smoke moving objects. Therefore, an algorithm for detection of fire smoke in a video based on wavelet energy slope fitting is proposed in this paper. The change in wavelet energy of the moving target foreground is used as the basis, and a time window of 40 continuous frames is set to fit the wavelet energy slope of the suspected area in every 20 frames, thus establishing a wavelet-energy-based smoke judgment criterion. The experimental data show that the algorithm described in this paper not only can detect smoke more quickly and more accurately, but also can effectively avoid the distraction of cloud, fog and moving object and prevent false alarm.

An Experimental Study on the Pressure Differentials during the Pressurized Air Supply to the Elevator Lobby (부속실 급기가압제연시 차압변화에 관한 실험적 연구)

  • Kim, Bum-Kyu;Park, Yong-Hwan;Kim, Hong-Sik
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2009.04a
    • /
    • pp.110-119
    • /
    • 2009
  • A fire should be accompanied by the heat and smoke. However, smoke is considered main cause of heavy casualties. Smoke easily spreads away from the fire area to remote space and cause mortal wound for the resident. A technical way effectively protecting the life and property from the smoke is the smoke control system of the building. Pressurized air supply system can be considered to prevent the refuge area from the smoke infiltration that evacuate residents via evacuation route for life safety. This paper is related with performance estimation and the effectiveness of the pressurized air supply system through experiments.

  • PDF

A Study of Smokeproof in Underground Culvert (지하공동구의 연소방지설비에 관한 연구)

  • 홍경표;이영재;김선정
    • Fire Science and Engineering
    • /
    • v.15 no.4
    • /
    • pp.57-63
    • /
    • 2001
  • Due to frequent fire incidents in underground culverts, many live are lost and the function of city is paralyzed, and consequently they bring tremendous damages to fortunes and live of people. It brings my attention that there are many problems presented when the current standard of smoke prevention facility is applied to prevent fire. Among many methods to prevent smoke in underground culverts this study concentrates on water-mist method witch is not currently applied in Korea and introduces installation method.

  • PDF

A Study on the Protection of Smoke Control Performance in Building Enclosure to Prevent the Expansion of Smoke in Fire (화재시 연기확대 방지를 위한 건축물 구획공간에서의 방연성능 확보에 관한 조사 연구)

  • Jin, Seung-Hyeon;Kim, Hye-Won;Lee, Byeong-Heun;Kwon, Young-Jin
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2019.05a
    • /
    • pp.91-92
    • /
    • 2019
  • In case of fire in a compartmentalized building area, a number of casualties are caused by smoke production. Accordingly, openings, penetrations and joints in compartmentalized spaces should be secured not only for fire resistance but also for smoke-proofing. However, domestic test regulations stipulate test methods for refractory performance of penetrations and joints, but do not specify separate deferral performance. In the case of openings, the test for the smoke performance exists at room temperature, but the smoke performance at high temperature is not secured, so countermeasures are needed.

  • PDF

A Study on the Improvement of Domestic Smoke Control Standards through Analysis the Standards about Air Leakage Rate of Domestic and Abroad (국내·외 누설률에 관한 기준 분석을 통한 국내 연기제어 기준 개선에 관한 연구)

  • Kim, Hye-Won;Han, Ji-Woo;Lee, Byeong-Heun;Jin, Seung-Hyeon;Kwon, Young-Jin
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2018.11a
    • /
    • pp.61-62
    • /
    • 2018
  • On this Study, it conducts the Standards investigation about air leakage of Buildings for performance improvement of Smoke control in Fire. In domestic standards, it is incomplete the Criteria standards of air leakage. Therefore it is considered that won't limit the smoke spread due to stack effect. But in the case of the United States, it conducts the Hot smoke air-Leakage test and it consider that can prevent the Smoke Spread in Compartment.

  • PDF

A Study of Evacuation in Elderly Care Facilities Fire (요양시설 화재 시 피난에 관한 연구)

  • Cha, Jong-Ho
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.18 no.11
    • /
    • pp.602-607
    • /
    • 2017
  • The development of science and technology has increased the average life expectancy and resulted in a significant increase in the elderly population. Due to the preponderance of the nuclear family in modern society and the weakening of the spirit of filial piety and respect for the elderly caused by the influence of Western civilization, elderly people are usually not living with their family, but have become dependent on elderly care facilities and, consequently, the number of elderly care facilities has increased significantly. On May 28, 2014, a fire occurred in the elderly care facilities in Jangseong, South Jeolla Province, and despite the rapid extinction of the fire by firefighters, 21 of the 28 casualties died due to smoke inhalation. This study was conducted for the purpose of providing measures to prevent smoke from entering into the rooms from which elderly people have difficulty evacuating in the case of fire. The use of the air curtain method to prevent smoke inflow was proposed and an experiment was conducted in which smoke was generated with a smoke generator. As a result of the experiment, it was confirmed that more than 90% of the smoke inflow was blocked if the door was closed in the room where the air curtain was installed.