• Title/Summary/Keyword: Predicted Fire

Search Result 260, Processing Time 0.03 seconds

A Study on the Fire Suppression Characteristics Using a Water Mist (물분무에 의한 화재제어 특성에 관한 연구)

  • 김성찬;유홍선
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.4
    • /
    • pp.261-267
    • /
    • 2003
  • The present study investigates the fire suppression characteristics using a water mist fire suppression system. Numerical simulations of fire suppression with water mist are performed with considering the interaction of fire plume and water droplet, droplet evaporation, and combustion of pool fire. The predicted temperature fields of smoke layer are compared with that of measured data. Numerical results agree with the experimental results within 5$^{\circ}C$ in the case without water mist In the case of fire suppression with water mist, numerical results dose not predict well lot temperature field in the gradual cooling region after water mist injection. But the predicted results of initial fire suppression are in good agreement with that of measured data. The reason of the discrepancy between predicted and measured data is due to the variation of turning rate during the injection of water mist. The effect of burning rate on the fire suppression is left as future study.

The Effects of Water Mist on the Compartment Fire

  • Ryou, Hong-Sun;Kim, Sung-Chan
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.12 no.1
    • /
    • pp.30-36
    • /
    • 2004
  • The present study investigates the fire suppression characteristics using a water mist fire suppression system. Numerical simulations of fire suppression with water mist are performed with considering the interaction of fire plume and water spray. The predicted temperature fields of smoke layer are compared with those of measured data. Numerical results agree with the experimental results within $10^{\circ}C$ in the case without water mist. In the case of fire suppression with water mist, numerical results do not predict well for temperature field in the gradual cooling region after water mist injection. But the predicted results of initial fire suppression are in good agreement with those of measured data. The reason for the discrepancy between predicted and measured data is due to the poor combustion modeling during the injection of water mist. More elaborate models for numerical simulation are required for better predictions of the fire suppression characteristics using water mist.

A Numerical Study on Temperature Prediction Bias using FDS in Simulated Thermal Environments of Fire (모사된 화재의 열적환경에서 FDS를 이용한 온도 예측오차에 관한 수치해석 연구)

  • Han, Ho-Sik;Kim, Bong-Jun;Hwang, Cheol-Hong
    • Journal of the Korean Society of Safety
    • /
    • v.32 no.2
    • /
    • pp.14-20
    • /
    • 2017
  • A numerical study was conducted to identify the predictive performance for the bare-bead thermocouple (TC) using FDS (Fire Dynamics Simulator) in simulated thermal environments of fire. A relative prediction bias of TC temperature calculated from reverse-radiation correction by FDS was evaluated with the comparison of previous experimental data. As a result, it was identified that the TC temperatures predicted by FDS were lower than the temperatures measured by bare-bead TC for the ranges of heat flux and gas temperature considered. The relative prediction bias of TC temperature by FDS was gradually increased with the increase in radiative heat flux and also significantly increased with the decrease in the gas temperature. Quantitatively, at the gas temperature of $20^{\circ}C$, the TC temperature predicted by FDS had the relative bias of approximately -20% with the radiative heat flux of $20kW/m^2$ corresponding to thermal radiation level of the flashover. It is predicted from the present study that more accurate validation of fire modeling will be possible with the quantitative prediction bias occurred in the process of reverse-radiation correction of temperature predicted by FDS.

A Validation Study of Temperature Field Predicted by Computational Fire Model for Spray Fire in a Multi-Compartment (다중구획공간내 분무화재시 화재해석모델의 온도장 검증연구)

  • Kim, Sugn-Chan
    • Fire Science and Engineering
    • /
    • v.28 no.5
    • /
    • pp.23-29
    • /
    • 2014
  • The present study has been conducted to investigate the validity of the computational fire model and the results predicted by BRANZFIRE zone model and FDS field model are compared with a real scale fire test with spray fire in a multi-compartment. The liquid spray fires fueled with toluene and methanol are used as the fire source and the quantitative measurement of heat release rate is performed in an isolated ISO-9705 compartment with a standard door opening. The temperature field predicted by FDS model showed good agreement with the measurement in the fire room and the corridor, and BRANZFIRE model also gave acceptable result in spite of its simplicity and roughness. The mean temperature predicted by FDS model corresponds with measurement within maximum discrepancy range of 25% and the overall mean value of FDS model matched well with experimental data less than 10%. This study can contribute to establish the limitation and application scope of computational fire model and provide reference data for applying to reliable fire risk assessment.

An Experimental and Numerical Study on Fire Suppression Using a Mid-low Pressure Water Mist in a Carriage Fire (중저압 물분무를 이용한 객차내 화재진압에 관한 실험 및 수치해석적 연구)

  • Roh Jae-Seong;Yang Seung-Shin;Kim Dong-Hyun;Jung Woo-Sung;Jang Yong-Jun;Ryou Hong-Sun
    • Journal of the Korean Society for Railway
    • /
    • v.9 no.3 s.34
    • /
    • pp.291-297
    • /
    • 2006
  • The present study investigated the effect of fire suppression using a mid-low pressure water mist in a carriage fire. The fire extinguishing time and temperature distributions below ceiling in the enclosed compartment of $2.9m{\times}2.8m{\times}5.0m$ were measured by stopwatch and k-type thermocouples for various fire positions. The numerical simulations were extensively performed using. Fire Dynamics Simulator(FDS, Ver. 4.0) code and the predictions were compared with experimental data. The prediction results showed good agreement with the measured maximum temperature in the all cases. Whereas the predicted temperature was about $40^{\circ}C$ higher than the measured one after operating of water mist. The predicted fire extinguishing times were compared with those of measured data. Fires are extinguished within 200 seconds at the experiment in Case 2 and Case 3. But in Case 1 fire was not extinguished in the numerical simulation. The reason of the discrepancy between predicted and measured data was that a simple suppression algorithm has been implemented in FDS. Also, various databases of fire properties for combustible materials and more elaborate model considering the water mist were required fur better predictions of the cooling and suffocation effect.

A Numerical Analysis for Fire Spread Mechanism of Residential Building Fire (주거용 건축물의 화염전파 현상에 대한 수치해석적 검토)

  • Ahn, Chan-Sol;Kim, Heung-Youl;You, Yong-Ho;Kim, Hyung-Jun
    • Fire Science and Engineering
    • /
    • v.26 no.1
    • /
    • pp.31-37
    • /
    • 2012
  • This study is intended to present a computational thermal model for a residential building. As the Performance Based Design is more popular, fire-intensity and fire-load have turned out to be very important factors for building design and can be predicted through some computational work. To predict and estimate the fire properties of a residential fire, we made some numerical models of combustibles and residential building. In a bid to validate the estimate values, computational analysis results from numerical models were compared with real fire tests. For computational analysis, the Fire Dynamics Simulator (FDS) was used with Large Eddy Simulation (LES) model for turbulence. Consequently, fire-intensity was well predicted and flash-over of rooms were successfully estimated.

The study of a fire fighting characteristic by a Single Evaporating Droplet in the case of a fire of military enclosure space (군사용 밀폐공간내의 화재시 단일 증발액적에 의한 방재특성 연구)

  • 이진호;방창훈;김정수
    • Journal of the Korea Institute of Military Science and Technology
    • /
    • v.3 no.1
    • /
    • pp.207-217
    • /
    • 2000
  • A fire fighting characteristic by a single evaporating droplet in the case of a fire of military enclosure space was studied experimentally. Transient cooling of solid surface by water droplet evaporation has been investigated through controlled experiments using a heated brass cylinder. Quantitative predictions of droplet evaporation time and in-depth transient temperature distribution in solid have been made. The particular interest was in the removal of thermal energy from the heated cylinder by evaporative cooling. A $10{\mu}1$ single droplet is deposited on a horizontal brass surface with initial temperatures in the range of $90^{\circ}C{\sim}130^{\circ}C.$ The results can be summarized as follows; Evaporating droplet was divided into three different configuration. Evaporation time was predicted as a function of initial surface temperature ($t_c=492.62-6.89T_{s0}+0.0248T_{s0}^2).$ The contact temperature was predicted as a function of initial surface temperature( $T_{i}$=0.94 $T_{s0}$+1.4), The parameter ${\beta}_o$ was predicted as a function of initial surface temperature( ${\beta}_0$ : 0.O0312 $T_{s0}+0.932$)>)>)

  • PDF

Numerical Study on the Change in Fire Characteristic as Operating Water-mist in Under-ventilated Compartments (워터미스트 작동에 의한 산소저공급 실내화재 특성 변화에 대한 수치해석 연구)

  • Ko, G.H.;Lee, S.H.;Ryou, H.S.
    • Journal of ILASS-Korea
    • /
    • v.13 no.3
    • /
    • pp.156-161
    • /
    • 2008
  • The present article reports a numerical study on the fire characteristic change by water-mist in under-ventilated compartments. The natural gas and heptane pool fires are used as fire sources, which are located in the bottom center of the 2/5 reduced-scaled model of the ISO 9705 standard room. The fire modeling using the FDS (Fire Dynamics Simulator) is validated by comparison with previously published experimental results. For temperature and combustion gas concentrations at two positions located in the upper layer of compartment, the predicted results with and without water-mist are compared each other. The results show that under the water-mist operation, the predicted temperature and carbon monoxide concentration reduce as $300{\sim}400^{\circ}C$ and about 20%, respectively, compared to those without water-mist.

  • PDF

An experimental study on fire resistance of medical modular block

  • Kim, Hyung-Jun;Lee, Jae-Sung;Kim, Heung-Youl;Cho, Bong-Ho;Xi, Yunping;Kwon, Ki-Hyuck
    • Steel and Composite Structures
    • /
    • v.15 no.1
    • /
    • pp.103-130
    • /
    • 2013
  • Fire performance and fire safety of high-rise buildings have become major concerns after the disasters of World Trade Center in the U.S. in 2001 and Windsor tower in Spain in 2005. Performance based design (PBD) approaches have been considered as a better method for fire resistance design of structures because it is capable of incorporating test results of most recent fire resistance technologies. However, there is a difficulty to evaluate fireproof performance of large structures, which have multiple structural members such as columns, slabs, and walls. The difficulty is mainly due to the limitation in the testing equipment, such as size of furnace that can be used to carry out fire tests with existing criteria like ISO 834, BS 476, and KS F 2257. In the present research, a large scale calorie meter (10 MW) was used to conduct three full scale fire tests on medical modular blocks. Average fire load of 13.99 $kg/m^2$ was used in the first test. In the second test, the weighting coefficient of 3.5 (the fire load of 50 $kg/m^2$) was used to simulate the worst fire scenario. The flashover of the medical modular block occurred at 62 minutes in the first test and 12 minutes in the second test. The heat resistance capacity of the external wall, the temperatures and deformations of the structural members satisfied the requirements of fire resistance performance of 90 minutes burning period. The total heat loads and the heat values for each test are calculated by theoretical equations. The duration of burning was predicted. The predicted results were compared with the test results, and they agree quite well.

A Simplified Steel Beam-To-Column Connection Modelling Approach and Influence of Connection Ductility on Frame Behaviour in Fire

  • Shi, Ruoxi;Huang, Shan-Shan;Davison, Buick
    • International Journal of High-Rise Buildings
    • /
    • v.7 no.4
    • /
    • pp.343-362
    • /
    • 2018
  • A simplified spring connection modelling approach for steel flush endplate beam-to-column connections in fire has been developed to enable realistic behaviour of connections to be incorporated into full-scale frame analyses at elevated temperature. Due to its simplicity and reliability, the proposed approach permits full-scale high-temperature frame analysis to be conducted without high computational cost. The proposed simplified spring connection modelling approach has been used to investigate the influence of connection ductility (both axial and rotational) on frame behaviour in fire. 2D steel and 3D composite frames with a range of beam spans were modelled to aid the understanding of the differences in frame response in fire where the beam-to-column connections have different axial and rotational ductility assumptions. The modelling results highlight that adopting the conventional rigid or pinned connection assumptions does not permit the axial forces acting on the connections to be accurately predicted, since the axial ductility of the connection is completely neglected when the rotational ductility is either fully restrained or free. By accounting for realistic axial and rotational ductilities of beam-to-column connections, the frame response in fire can be predicted more accurately, which is advantageous in performance-based structural fire engineering design.