Browse > Article
http://dx.doi.org/10.12989/scs.2013.15.1.103

An experimental study on fire resistance of medical modular block  

Kim, Hyung-Jun (Fire Safety Research Center, Korea Institute of Construction Technology)
Lee, Jae-Sung (Department of Architectural Engineering, Hannam University)
Kim, Heung-Youl (Fire Safety Research Center, Korea Institute of Construction Technology)
Cho, Bong-Ho (Department of Architectural Engineering, Ajou University)
Xi, Yunping (Department of Civil, Environmental, and Architectural Engineering, University of Colorado)
Kwon, Ki-Hyuck (Department of Architecture Engineering, University of Seoul)
Publication Information
Steel and Composite Structures / v.15, no.1, 2013 , pp. 103-130 More about this Journal
Abstract
Fire performance and fire safety of high-rise buildings have become major concerns after the disasters of World Trade Center in the U.S. in 2001 and Windsor tower in Spain in 2005. Performance based design (PBD) approaches have been considered as a better method for fire resistance design of structures because it is capable of incorporating test results of most recent fire resistance technologies. However, there is a difficulty to evaluate fireproof performance of large structures, which have multiple structural members such as columns, slabs, and walls. The difficulty is mainly due to the limitation in the testing equipment, such as size of furnace that can be used to carry out fire tests with existing criteria like ISO 834, BS 476, and KS F 2257. In the present research, a large scale calorie meter (10 MW) was used to conduct three full scale fire tests on medical modular blocks. Average fire load of 13.99 $kg/m^2$ was used in the first test. In the second test, the weighting coefficient of 3.5 (the fire load of 50 $kg/m^2$) was used to simulate the worst fire scenario. The flashover of the medical modular block occurred at 62 minutes in the first test and 12 minutes in the second test. The heat resistance capacity of the external wall, the temperatures and deformations of the structural members satisfied the requirements of fire resistance performance of 90 minutes burning period. The total heat loads and the heat values for each test are calculated by theoretical equations. The duration of burning was predicted. The predicted results were compared with the test results, and they agree quite well.
Keywords
full-scale fire test; modular block; fire load; fire resistance;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Park, S.Y., Kim, H.J., Kim, H.Y. and Hong, K.P. (2010), "Fire resistance of the Korean asymmetric slim floor beam depending on load ratio", J. Asian Architect. Build. Eng., 10(2), 413-420.
2 Proe, D.J. and Bennetts, I.D. (1994), "Real fire tests in 380 Collins street office enclosure", BHP Research, BHPR/PPA/R/94/SG021A, Melbourne, Australia.
3 SBBHP (1994), "Building Regulations 1994", Swedish Board of Building, Housing and Planning, Sweden.
4 SNIP 21-01-97 (1997), "Fire Safety of Buildings and Structures, Standards and Regulations", Construction Codes and Regulations.
5 Steel Construction Industry Forum (1991), "Investigation of Broadgate phase 8 fire", The Steel Construction Institute.
6 Sun, R.R., Huang, Z.H. and Burgess, I.W. (2012), "The collapse behaviour of braced steel frames exposed to fire", J. Construct. Steel Res, 72, 130-142.   DOI   ScienceOn
7 Thomas, I.R., Bennetts, I.D., Dayawansa, P., Proe, D.J. and Lewis, R.R. (1992), Fire Tests of the 140 William Street Office Building, BHP Research, BHPR/ENG/R/92 /043/SG2C, Melbourne Australia.
8 Wald, F., Simoes da Silva, L., Moore, D.B., Lennon, T., Chladna, M., Santiago, A., Benes, M. and Borges, L. (2006), "Experimental behaviour of a steel structure under natural fire", Fire Safety J., 41(7), 509-522.   DOI   ScienceOn
9 Wald, F., Sokol, Z., and Moore, D. (2009), "Horizontal forces in steel structures tested in fire", J. Construct. Steel Res., 65(8-9), 1896-1903.   DOI   ScienceOn
10 NPB 233-96 (1996), "Full Scale Fire Test Methods for Buildings", NPB Fire Safety Regulations.
11 ISO (1999), "Fire resistance tests-Elements of building construction-part 1: General requirements", ISO 834-1, International Organization for Standardization, Switzerland.
12 Kim, H.J., Kim, H.Y., Lee, J.S. and Cho, B.H. (2009a), "An analytical study on optimal shape condition of modular beam using fireproof board", J. Architect. Inst. Korea (Struct. & Construct.), 25(7), 3-12.   과학기술학회마을
13 Kim, H.Y., Lee, J.S., Yoo, Y.H., Cho, B.H. and Kim, H.J. (2009b), "A study on the fire experiment of medical modular block for the structure behavior and deformation under fire load condition", J. Architect. Inst. Korea (Struct. & Construct.), 25(12), 21-30.   과학기술학회마을
14 Korean agency for technology and Standards (2005), KS F 2257-1, "Methods of fire resistance test for elements of building construction-General requirements", Korean Standards Association.
15 Korea Institute of Construction Technology (2004), Development of Fireproof Design Technology for the Architectural Buildings, Vol. 1, Ministry of Land, Transport, and Maritime Affairs, 97-99.
16 Kwon, I.K. (2002), "State of the Art on the Fire Resistance of Steel Structures and Experimental Study on Section Factors in Korea", SFPE, 4th International Conference on Performance-Based Codes and Fire Safety Design Methods, Melbourne, Australia, March.
17 Kwon, I.K. (2005), "Evaluation of fire resistance performance of load-bearing elements made up of light gauge steels", 8th International Conference on Steel, Space and Composition Structures, Malaysia.
18 British Standard (1987), "Fire tests on building materials and structures-part22", BS 476-22, British Standard Institution, London, UK.
19 Lawson, R.M., Mullett, D.L. and Rackham, J.W. (1997), "Design of asymmetric 'Slimflor' beams using deep composite decking", The Steel Construction Institute, Berkshire, UK 175.
20 Lee, J.S., Kim, H.Y., Cho, B.H., Kim, H.J. and Kim, G.D. (2008), "Fire resistance system of MCO beam using fireproof board", J. Architect. Inst. Korea (Struct. & Construct.), 24(11), 93-100.   과학기술학회마을
21 BSI (2002), Eurocode 1: "Actions on structures. Part 1-2: General actions - Actions on structures exposed to fire", BS EN 1991-1-2, European Standard, London, UK.
22 Buchanan, A.H. (2001a), Fire Engineering Design Guide.
23 Buchanan, A.H. (2001b), Structural design for fire safety, John Willy & Sons.
24 Carden, L.P. and Itani, A.M. (2007), "Performance of an unprotected steel structure subjected to repeated fire at a firefighter training facility", Fire Safety J., 42(2), 81-90.   DOI   ScienceOn
25 CNISK, MNTKS, BNIIPO (1996), "Elements of building constructions, fire - Resistance test methods (General Requirement)", GOST-30247-94, IPK.
26 Department of Building Housing (2011), "Compliance Document for New Zealand Building Coode Clauses C1,C2,C3,C4 Fire Safety", New Zealand Government, 39-41.
27 Dwaikat, M.M.S. and Kodur, V.K.R. (2011), "A performance based methodology for fire design of restrained steel beams", J. Construct. Steel Res., 67(3), 510-524.   DOI   ScienceOn
28 GOST 30247.0 (1994), "Elements of building constructions, Fire-resistance test methods: General requirements", Interstate Scientific and Technical Commission on Standardization.
29 HMSO (1985), "The Building Regulations 1985", London, UK.
30 GOST 30247.1 (1994), "Elements of building constructions, Fire-resistance test methods: Loadbearing and separating elements", Interstate Scientific and Technical Commission on Standardization.
31 IFCI (2000), "International Building Code", International Fire Code Institute, USA.
32 Iqbal, S. and Harichandran, R.S. (2011), "Capacity reduction and fire load factors for LRFD of steel columns exposed to fire", Fire Safety J., 46(6), 234-242.   DOI   ScienceOn
33 BIA (1992), New Zealand Building Code Handbook and Approved Documents, Building Industry Authority, Wellington, New Zealand.
34 ABCB (1996), "Building Code of Australian", Australian Building Codes Board, Australia.