• Title/Summary/Keyword: Power Transformer Fault

Search Result 260, Processing Time 0.035 seconds

Development of Artificial Diagnosis Algorithm for Dissolved Gas Analysis of Power Transformer (전력용 변압기의 유중가스 해석을 위한 지능형 진단 알고리즘 개발)

  • Lim, Jae-Yoon;Lee, Dae-Jong;Lee, Jong-Pil;Ji, Pyeong-Shik
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.7
    • /
    • pp.75-83
    • /
    • 2007
  • IEC code based decision nile have been widely applied to detect incipient faults in power transformers. However, this method has a drawback to achieve the diagnosis with accuracy without experienced experts. In order to resolve this problem, we propose an artificial diagnosis algorithm to detect faults of power transformers using Self-Organizing Feature Map(SOM). The proposed method has two stages such as model construction and diagnostic procedure. First, faulty model is constructed by feature maps obtained by unsupervised learning for training data. And then, diagnosis is performed by compare feature map with it obtained for test data. Also the proposed method usぉms the possibility and degree of aging as well as the fault occurred in transformer by clustering and distance measure schemes. To demonstrate the validity of proposed method, various experiments are unformed and their results are presented.

A Study on Development of Open-Phase Protector Having Leakage Current Generation and Incapable Operation Prevention at Open-Phase Accident (결상 시 누전전류 발생과 오동작 방지 기능을 갖는 결상보호기 개발에 관한 연구)

  • Kwak, Dong-Kurl
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.64 no.1
    • /
    • pp.182-187
    • /
    • 2015
  • In the three-phase power system, when any one-phase or two-phases is open-phase, the unbalanced current flows and the single-phase power supplies to three-phase loads. Specially, motor coil and transformer coil receive over-current. As a result, great damage as well as electrical fire can occur to the power system. In order to improve these problems, this paper proposes that an open-phase detection device is designed by a new algorithm using electric potential difference between the resultant voltage of neutral point and ground, and a control circuit topology of open-phase protector is composed of highly efficient semiconductor devices. It improves response speed and reliability. The control algorithm circuit also operates the cut-off of a conventional residual current protective device (RCD) which flows an enforced leakage current to ground wire at open-phase accident. Furthermore, time delay circuit is added to prevent the incapable operation of open-phase protector about instantaneous open-phase not open-phase fault. The time delay circuit improves more reliability.

Impulse Tests for a Composite Solid Insulator for High Voltage Superconducting Power Applications (복합고체절연물의 극저온 절연성능 평가를 위한 임펄스 내전압시험)

  • Kim, W.S.;Ryu, S.D.;Hyun, O.B.;Kim, H.R.;Yim, S.W.;Yang, S.E.;Kim, H.S.
    • Progress in Superconductivity
    • /
    • v.13 no.1
    • /
    • pp.24-27
    • /
    • 2011
  • High voltage insulation in cryogenic environment is one of big issues for development of superconducting power application, such as superconducting fault current limiter, transformer, transmission cable, and so on. We had proposed a composite solid insulator composed of plastics and polymer insulation sheets for a use of high voltage superconducting power applications. It is well known that the G10 FRP keeps its mechanical strength at very low temperature and the PPLP is very good insulator adopted as insulations for superconducting transmission cables. The composition of these two materials will show very good electrical and mechanical properties adequate for the insulation components of superconducting power applications, such as bushing, insulation barrier, and even for a cryostat. Dielectric strengths of prepared samples were measured at the temperature of boiling point of liquid nitrogen at atmospheric pressure, which will be presented in this paper to show a usefulness of this technique.

A study on the SMES component modeling using PSCAD/EMTDC (PSCAD/EMTDC를 이용한 SMES Component modeling에 관한 연구)

  • Kim, Jin-Gun;Kim, Jae-Ho;Jung, Hee-Yeol;Park, Min-Won;Yu, In-Keun
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.1998-1999
    • /
    • 2007
  • Before applying the HTS(High Temperature Superconductor) power devices to a real utility network, system analysis should be carried out by some simulation tools. PSCAD/EMTDC simulation tool is one of the most popularized useful analysis tools for electrical power system. Unfortunately the model component for HTS coil is not provided in PSCAD/EMTDC simulation tool. In this paper, EMTDC model component for HTS coil has been developed considering real characteristics of HTS coil like critical current, temperature and magnetic field. The developed model component of HTS coil could be used for power system application. Using the developed model component for HTS coil, we can easily do the simulation of HTS power devices application test in utility with the various inductance, quench current, inner magnetic field, and temperature values, for instances; SMES(Superconducting Magnetic Energy Storage) system, superconducting motor, transformer, and FCL(Fault Current Limiter)

  • PDF

A Study on the Application of the DVR in AC Electric Traction System (전기철도계통에 순간전압강하 보상장치 적용에 관한 연구)

  • 최준호;김태수;김재철;문승일;남해곤;정일엽;박성우
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.6
    • /
    • pp.95-104
    • /
    • 2003
  • The electric traction systems are quite differ from general power systems which is single-phase and heavy load. Therefore, there are inevitably power quality problems such as steady state or transient voltage drop, voltage imbalance and harmonic distortion. Among these problems, since steady-state volatge drop is the one of most important factor in electric power quality, many researches about on the compensation of volatge drop by using SVC(Static Var Compensator) and/or STACOM(Static Compensator) have been studied and proposed Also, it is expected that transient voltage drop(voltage sag) could affect the control and safety of high speed traction load. In this paper, voltage sag compensation of AT(Auto Transformer) feeding system are studied The detailed transient models of utility source, scott transformer, AT, and traction load are estabilished. The application of DVR(Dynamic Voltage Restorer) in electric traction system is proposed to compensate the voltage sag of traction network which is occured by the fault of utility source. It can be shown that application of the DVR in electric traction system is very useful to compensate the volatge sag from the result of related simulation works.

Brief review of the field test and application of a superconducting fault current limiter

  • Hyun, Ok-Bae
    • Progress in Superconductivity and Cryogenics
    • /
    • v.19 no.4
    • /
    • pp.1-11
    • /
    • 2017
  • This article reviews the recent activities of field testing and application of superconducting fault current limiters (SFCL) based on high-temperature superconductors (HTS). The review particularly focuses on the trends in the field tests in terms of the technical aspects and commercial activities of the SFCLs. Stimulated by the discovery of HTS, numerous research and development activities have been conducted worldwide for SFCLs operating from distribution voltages to transmission voltages. Different types of SFCLs have been developed and field-tested. Consequently, more than 20 field tests and applications have been performed on real grids worldwide while supplying electric power to the customers. These field tests have not only provided the track records of the operation experiences including the problems and maintenance during operation, but also proved their current limiting capabilities against real faults, rendering this new technology highly viable. Through these activities, the following trends in the status of field testing and application are observed. Resistive-type SFCLs with HTS-coated conductors were dominantly used in the most recent field tests. This implies that the resistive type is technically more mature than the other types. Bus-bar coupling and transformer feeders were the major application locations. It is of importance that most of the field applications were conducted as R&D projects. A relevant change from the R&D stage to the application stage is shown as recently deployed SFCLs are expected to be under long-term operation and commercial service. Here, we review the installation of these SFCLs by substation. This review also discusses the recent activities for their commercial applications.

Analysis on Fault Current limiting and Recovery Characteristics of Flux-Lock Type Superconducting Fault Current Limiter According to Increase of Applied Voltage (전압증가에 따른 자속구속형 초전도 한류기의 전류제한 및 회복특성 분석)

  • Oh, Kum-Gon;Han, Tae-Hee;Cho, Yong-Sun;Cho, Hyo-Sang;Choi, Myoung-Ho;Han, Young-Hee;Sung, Tae-Hyun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.8
    • /
    • pp.107-112
    • /
    • 2007
  • The flux-lock type SFCL consists of transformer with primary and secondary windings connected to a superconducting element in serial. It can be divided into the subtractive and the additive polarity windings according to the winding direction. It could change the fault current limiting characteristics according to the inductance ratio between the coil 1 and coil 2. We investigated the voltage-current characteristics of the flux-lock type SFCL according to the increment of applied voltage. When the applied voltage of the SFCL with the subtractive and the additive polarity windings was increased a initial limiting current ($I_{ini}$) and the quench time of the superconducting element were increased. The recovery time of the superconducting element was increased by increment of applied voltage. Therefore, it was confirmed that recovery characteristics in the flux-lock type SFCL were largely dependent on the consumed energy of a superconducting element because of increment of the consumption power into the superconducting element.

Characteristics of Hybrid-Type SFCL according to the Parallel Connection of Secondary Windings (2차권선의 병렬연결에 따른 하이브리드형 초전도 한류기의 특성)

  • Hwang, Jong-Sun;Cho, Yong-Sun;Choi, Hyo-Sang
    • Proceedings of the KIEE Conference
    • /
    • 2006.10b
    • /
    • pp.208-211
    • /
    • 2006
  • We have analyzed operating characteristics of hybrid-type superconducting fault current limiter (SFCL) according to the parallel connection of secondary windings with $YBa_{2}Cu_{3}O_{7}$ (YBCO) films. The turn ratio between the primary and secondary windings of each reactor was 63:21. Hybrid-type SFCL using a transformer with parallel reactors could reduce the unbalanced quench caused by differences of the critical current density between YBCO films. We found that hybrid-type SFCL having parallel connection induced simultaneous quench between the superconducting elements. The quench-starting point at this time was almost same. When the applied voltage was 200V, the limiting current in the hybrid-type SFCL with a serial connection was lowered to 34 percent than that in the SFCL with a parallel connection. In the meantime, when the voltage generated in the superconducting elements was the same, the current value in the parallel connection was 60 percent less than in the serial connection. The voltage generated in the primary winding also showed the similar behavior. In conclusion, we found that the fault current was limited more effectively in the SFCL with the serial connection but the power burden of the superconducting elements was reduced in the parallel connection.

  • PDF

Operating Characteristics of Capacity Increase in a Flux-Lock Type Superconducting Fault Current Limiter (자속구속형 초전도 전류제한기의 용량증대를 위한 동작특성)

  • Nam, Gueng-Hyun;Choi, Hyo-Sang;Park, Hyoung-Min;Cho, Yong-Sun;Lee, Na-Young;Han, Tae-Hee
    • Proceedings of the KIEE Conference
    • /
    • 2006.04b
    • /
    • pp.200-202
    • /
    • 2006
  • We investigated the operating characteristics of a flux-lock type superconducting fault current limiters according to the number of the serial connection each the superconducting element at the additive polarity winding of a transformer. This SFCL consists of two coils wound in parallel on the same iron core, and the secondary coil is connected to the elements in series. Operating characteristics can be controlled by adjusting the inductances and the winding directions of the coils. It turns ratio between the primary and the secondary coils is 63:21. The analysis of voltage, current, and resistance in serial connection each element was performed to increase the applied voltage of flux-lock type SFCL. When the applied voltage was 200/$\sqrt{3}[V_{rms}]$ with three elements connected in seres, the peak value of the line current increased up to 26,24[A]. On the other hands, resistive SFCL increased up to 36.35[A], under the same conditions. This enabled the flux-lock type SFCL to be easy to increase the capacity of power system.

  • PDF

Development of Diagnostic Algorithm and Expert System to diagnose Power Transformers by the methods of Gas Analysis (가스분석기법을 이용한 전력용 변압기 내부 이상진단을 위한 진단 알고리즘 및 전문가시스템 개발)

  • 최인혁;정길조;권동진;신명철
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.15 no.5
    • /
    • pp.68-74
    • /
    • 2001
  • This paper describes the new algorithm method for detecting abnormal causes within power transformers. Generally, the gas analysis has been proved the most confident method of many transformer diagnostics. The proposed algorithm is adapted to the international codes of IEC, Dornenburg, Gas Pattern including the DEPCO´s gas analysis method for the improvement of diagnostic efficiency. Specially, this algorithm is programmed by the tool of Element Expert developed Neuron DATA Inc. in USA. Also, it was confirmed that the developed algorithm is proved the confidence by the use of real data in fault power transformers.

  • PDF