• Title/Summary/Keyword: Power System Oscillations

Search Result 120, Processing Time 0.025 seconds

A Modified Perturb and Observe Sliding Mode Maximum Power Point Tracking Method for Photovoltaic System uUnder Partially Shaded Conditions

  • Hahm, Jehun;Kim, Euntai;Lee, Heejin;Yoon, Changyong
    • International Journal of Fuzzy Logic and Intelligent Systems
    • /
    • v.16 no.4
    • /
    • pp.281-292
    • /
    • 2016
  • The proposed scheme is based on the modified perturb and observe (P&O) algorithm combined with the sliding mode technique. A modified P&O algorithm based sliding mode controller is developed to study the effects of partial shade, temperature, and insolation on the performance of maximum power point tracking (MPPT) used in photovoltaic (PV) systems. Under partially shaded conditions and temperature, the energy conversion efficiency of a PV array is very low, leading to significant power losses. Consequently, increasing efficiency by means of MPPT is particularly important. Conventional techniques are easy to implement but produce oscillations at MPP. The proposed method is applied to a model to simulate the performance of the PV system for solar energy usage, which is compared to the conventional methods under non-uniform insolation improving the PV system utilization efficiency and allowing optimization of the system performance. The modified perturb and observe sliding mode controller successfully overcomes the issues presented by non-uniform conditions and tracks the global MPP. Compared to MPPT techniques, the proposed technique is more efficient; it produces less oscillation at MPP in the steady state, and provides more precise tracking.

Accurate Calculation of RMS Value of Grid Voltage with Synchronization of Phase Angle of Sampled Data (샘플링 시점의 위상각 동기화를 이용한 계통전압 실효값의 정확한 계산 방법)

  • Ham, Do-Hyun;Kim, Soo-Bin;Song, Seung-Ho;Lee, Hyun-Young
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.23 no.6
    • /
    • pp.381-388
    • /
    • 2018
  • A novel and simple algorithm for accurate calculation of RMS voltage is proposed in a digitally controlled grid-tie inverter system. Given that the actual frequency of grid voltage is continuously changing, the constant sampling frequency cannot be a multiple number of the fundamental frequency. Therefore, the RMS of grid voltage contains periodic oscillations due to the differences in the phase angle of sampled data during calculation. The proposed algorithm precisely calculates and updates the initial phase angle of the first sampled voltage in a half-cycle period using phase-locked loop, which is commonly utilized for phase angle detection in grid-tie inverter systems. The accuracy and dynamic performance of the proposed algorithm are compared with those of other algorithms through various simulations and experiments.

Optimization of automatic power control of pulsed reactor IBR-2M in the presence of instability

  • Pepelyshev, Yu.N.;Davaasuren, Sumkhuu
    • Nuclear Engineering and Technology
    • /
    • v.54 no.8
    • /
    • pp.2877-2882
    • /
    • 2022
  • The paper presents the main results of computational and experimental optimization of the automatic power control system (AC) of the IBR-2M pulsed reactor in the presence of a high level of oscillatory instability. Optimization of the parameters of the AC made it possible to significantly reduce the influence of random and deterministic oscillations of reactivity on the noise of the pulse energy, as well as to sharply reduce the manifestation of the oscillatory instability of the reactor. As a result, the safety and reliability of operation of the reactor has increased substantially.

MOBA based design of FOPID-SSSC for load frequency control of interconnected multi-area power systems

  • Falehi, Ali Darvish
    • Smart Structures and Systems
    • /
    • v.22 no.1
    • /
    • pp.81-94
    • /
    • 2018
  • Automatic Generation Control (AGC) has functionally controlled the interchange power flow in order to suppress the dynamic oscillations of frequency and tie-line power deviations as a perturbation occurs in the interconnected multi-area power system. Furthermore, Flexible AC Transmission Systems (FACTS) can effectively assist AGC to more enhance the dynamic stability of power system. So, Static Synchronous Series Compensator (SSSC), one of the well-known FACTS devices, is here applied to accurately control and regulate the load frequency of multi-area multi-source interconnected power system. The research and efforts made in this regard have caused to introduce the Fractional Order Proportional Integral Derivative (FOPID) based SSSC, to alleviate both the most significant issues in multi-area interconnected power systems i.e., frequency and tie-line power deviations. Due to multi-objective nature of aforementioned problem, suppression of the frequency and tie-line power deviations is formularized in the form of a multi-object problem. Considering the high performance of Multi Objective Bees Algorithm (MOBA) in solution of the non-linear objectives, it has been utilized to appropriately unravel the optimization problem. To verify and validate the dynamic performance of self-defined FOPID-SSSC, it has been thoroughly evaluated in three different multi-area interconnected power systems. Meanwhile, the dynamic performance of FOPID-SSSC has been accurately compared with a conventional controller based SSSC while the power systems are affected by different Step Load Perturbations (SLPs). Eventually, the simulation results of all three power systems have transparently demonstrated the dynamic performance of FOPID-SSSC to significantly suppress the frequency and tie-line power deviations as compared to conventional controller based SSSC.

A Loss-of-RHR Event under the Various Plant Configurations in Low Power or Shutdown Conditions

  • Seul, Kwang-Won;Bang, Young-Seok;Lee, Sukho;Kim, Hho-Jung
    • Proceedings of the Korean Nuclear Society Conference
    • /
    • 1997.05a
    • /
    • pp.551-556
    • /
    • 1997
  • A present study addresses a loss-of-RHR event as an initiating event under specific low power or shutdown conditions. Two typical plant configurations, cold leg opening case with water-filled steam generators and pressurizer opening case with emptied steam generators, were evaluated using the RELAP5/ MOD3.2 code. The calculation was compared with the experiment conducted at ROSA-IV/LSTF in Japan. As a result, the code was capable of simulating the system transient behavior following the event. Especially, thermal hydraulic transport processes including non-condensable gas behavior were reasonably predicted with an appropriate time step and CPU time. However, there were some code deficiencies such as too large system mass errors and severe flow oscillations in core region.

  • PDF

Development of Hardware for Power System Stabilizer(PSS) (발전기 제어계통 안정화 장치용 하드웨어 개발)

  • Kim, C.K.;Park, M.K.;Kim, J.M.;Kweon, S.M.
    • Proceedings of the KIEE Conference
    • /
    • 2001.07a
    • /
    • pp.131-133
    • /
    • 2001
  • The basic function of a Power-System Stabilizer(PSS) is to add damping to the generator rotor oscillations by controlling its excitation using auxiliary stabilizing signals. To provide damping. the stabilizer must produce a component of electrical torque in phase with the rotor speed deviations. This paper introduces the hardware specifications and various functions of microprocessor (TMS320C32)-based digital PSS to provide the damping torque.

  • PDF

Design of Fuzzy Logic Controller for Power System Stabilizer Using Adaptive Evolutionary Computation (적응진화연산을 이용한 전력계통안정화장치의 퍼지제어기의 설계)

  • Hwang, G.H.;Mun, K.J.;Kim, H.S.;Park, J.H.;Lee, H.S.;Kim, M.S.
    • Proceedings of the KIEE Conference
    • /
    • 1998.07c
    • /
    • pp.1118-1120
    • /
    • 1998
  • In this study, an adaptive evolutionary computation (AEC), which uses adaptively a genetic algorithm having global searching capability and an evolution strategy having local searching capability with different methodologies, is suggested. We applied the AEC to design of fuzzy logic controllers for a PSS (power system stabilizer). FLCs for PSS controllers are designed for damping the low frequency oscillations caused by disturbances such as tile sudden changes of loads, outages in generators, transmission line faults, etc. The membership functions of FLCs is optimally determined by AEC.

  • PDF

Applying TID-PSS to Enhance Dynamic Stability of Multi-Machine Power Systems

  • Mohammadi, Ramin Shir;Mehdizadeh, Ali;Kalantari, Navid Taghizadegan
    • Transactions on Electrical and Electronic Materials
    • /
    • v.18 no.5
    • /
    • pp.287-297
    • /
    • 2017
  • Novel power system stabilizers (PSSs) have been proposed to effectively dampen low frequency oscillations (LFOs) in multi-machine power systems and have attracted increasing research interest in recent years. Due to this attention, recently, fractional order controllers (FOCs) have found new applications in power system stability issues. Here, a tilt-integral-derivative power system stabilizer (TID-PSS) is proposed to enhance the dynamic stability of a multi-machine power system by providing additional damping to the LFOs. The TID is an extended version of the classical proportional-integral-derivative (PID) applying fractional calculus. The design of the proposed three-parameter tunable TID-PSS is systematized as a nonlinear time domain optimization problem in which the tunable parameters are adjusted concurrently using a modified group search optimization (MGSO) algorithm. An integral of the time multiplied squared error (ITSE) performance index is considered as the objective function. The proposed stabilizer is simulated in the MATLAB/SIMULINK environment using the FOMCON toolbox and the dynamic performance is evaluated on a 3-machine 6-bus power system. The TID-PSS is compared with both classical PID-PSS (PID-PSS) and conventional PSS (CPSS) using eigenvalue analysis and time domain simulations. Sensitivity analyses are performed to assess the robustness of the proposed controller against large changes in system loading conditions and parameters. The results indicate that the proposed TID-PSS provides the better dynamic performance and robustness compared with the PID-PSS and CPSS.

Robust Internal Model Control of Three-Phase Active Power Filter for Stable Operation in Electric Power Equipment (전력설비의 안정한 운용을 위한 3상 능동전력필터의 강인한 내부모델제어)

  • Park, Ji-Ho;Kim, Dong-Wan
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.62 no.10
    • /
    • pp.1487-1493
    • /
    • 2013
  • A new simple control method for active power filter, which can realize the complete compensation of harmonics is proposed. In the proposed scheme, a model-based digital current control strategy is presented. The proposed control system is designed and implemented in a form referred to as internal model control structure. This method provides a convenient way for parameterizing the controller in term of the nominal system model, including time-delays. As a result, the resulting controller parameters are directly set based on the power circuit parameters, which make tuning of the controllers straightforward task. In the proposed control algorithm, overshoots and oscillations due to the computation time delay is prevented by explicit incorporating of the delay in the controller transfer function. In addition, a new compensating current reference generator employing resonance model implemented by a DSP(Digital Signal Processor) is introduced. Resonance model has an infinite gain at resonant frequency, and it exhibits a band-pass filter. Consequently, the difference between the instantaneous load current and the output of this model is the current reference signal for the harmonic compensation.

Robust Control of Induction motor using Fuzzy Sliding Adaptive Controller with Sliding Mode Torque Observer

  • Yoon, Byung-Do;Rhew, Hong-Woo;Lim, Ick-Hun;Kim, Chan-Ki
    • Proceedings of the KIEE Conference
    • /
    • 1996.07a
    • /
    • pp.420-425
    • /
    • 1996
  • In this paper a robust speed controller for an induction motor is proposed. The speed controller consists or a fuzzy sliding adaptive controller(FSAC) and a sliding mode torque observer(SMTO). FSAC removes the problem or oscillations caused by discontinuous inputs of the sliding mode controller. The controller also provides robust characteristics against parameter and sampling time variations. Although, however, the performance of FSAC is better than PI controller and fuzzy controller in robustness, it generates the problem of slow response time. To alleviate this problem, a compensator, which performs feedforward control using torque signals produced by SMTO, is added. The simulation and hardware implementation results show that the proposed system is robust to the load disturbance, parameter variations, and measurement noises.

  • PDF