• 제목/요약/키워드: Power Cabinet

검색결과 80건 처리시간 0.026초

Grouping effect on the seismic response of cabinet facility considering primary-secondary structure interaction

  • Salman, Kashif;Tran, Thanh-Tuan;Kim, Dookie
    • Nuclear Engineering and Technology
    • /
    • 제52권6호
    • /
    • pp.1318-1326
    • /
    • 2020
  • Structural modification in the electrical cabinet is investigated by a proposed procedure that comprises of an experimental, analytical and numerical solution. This research emphasizes the linear dynamic analysis of the cabinet that is studied under the seismic excitation to demonstrate the real behavior of the cabinets in NPP. To this end, an actual electric cabinet is experimentally tested using an impact hammer test which reveals the fundamental parameters of the cabinet. The Frequency-domain decomposition (FDD) method is used to extract the dynamic properties of the cabinet from the experiment which is then used for numerical modeling. To validate the dynamic properties of the cabinet an analytical solution is suggested. The calibrated model is analyzed under the floor response obtained from the Connecticut nuclear power plant structure excited by Tabas 1978 (Mw 7.4) earthquake. Eventually, the grouping effect of the cabinets is proposed which represents the influence on the dynamic modification. This grouping of the cabinets is described more sophisticatedly by the theoretical understating, which results in a significant change in the seismic response. Considering the grouping effects will be helpful in the assessment of the real seismic behavior, design, and performance of cabinets.

원전용 분산제어시스템을 이용한 차세대 원전 제어봉 구동장치제어시스템 원형 개발 (Development of KNGR-CEDMCS Prototype Using DCS for Nuclear Power Plant)

  • 천종민;이종무;김춘경;박민국;권순만;신종렬
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 D
    • /
    • pp.2275-2277
    • /
    • 2004
  • Korea Next Generation Reactor(KNGR) is in the midst of being developed and will exceed Korea Standard Nuclear Power Plant(KSNP) economically. Domestic Instrumentation and Control(I&C) systems shall be applied to KNGR and the development of Control Element Drive Mechanism Control System(CEDMCS) considered as an essential part in nuclear I&C system will be dealt with in this paper. The newly developed CEDMCS has the control cabinet using the nuclear Distributed Control System(DCS) made in Korea and the power cabinet produced by our research institute and interfaced with the DCS control cabinet.

  • PDF

Model Updating of an Electric Cabinet using Shaking Table Test

  • Cui, Jintao;Cho, Sung-Gook;Kim, Doo-Kie;Koo, Ki-Young;Cho, Yang-Hee
    • 한국소음진동공학회:학술대회논문집
    • /
    • 한국소음진동공학회 2008년도 춘계학술대회논문집
    • /
    • pp.59-62
    • /
    • 2008
  • This paper presents the procedure and the results of modal identification testing of a seismic monitoring system central processing unit cabinet for a nuclear power plant. This paper also provides a model updating for making effective analytical modeling of cabinet-type electrical equipment by comparing the test results with the analysis results. From the test results and their interpretation, modal properties (modal frequency, mode shape, and modal damping) of the specimen were satisfactorily identified. However, the analysis results may need to study further to find the effective and presentative model for the cabinet-type electrical equipment. This paper just presents the first stage of the research project "Development of dynamic behavior analysis technique of dynamic structure system" which is trying to build the lumped mass beam stick model even their results do not agree well with the test results.

  • PDF

원자력 발전소 캐비닛구조물의 내진보강 (Seismic Retrofitting of Cabinet Structures in Nuclear Power Plant)

  • 이계희;김재민;김상윤
    • 한국지진공학회논문집
    • /
    • 제7권4호
    • /
    • pp.31-37
    • /
    • 2003
  • 본 논문에서는 오래된 원자력발전소의 내진검증과 관련한 USI A-46 문제의 해결에 사용될 수 있는 캐비닛의 내진보강방안에 대해 연구하였다. 캐비닛 구조물의 동적거동특성을 파악하기 위하여 3종류의 모델링을 수행하였고 그 결과를 비교하였다. 또한 ICRS(In Cabinet Reponse Spectrum)의 저감을 위하여 1) 보강프레임, 2)감쇠기 설치, 3) 동조질량감쇠기 등 세 가지 내진보강방안에 대하여 구조물의 응답을 산정하였다. 해석결과, 가새보강 및 감쇠기를 설치하는 보강방법에서는 보강전의 구조물보다 큰 ICRS가 얻어지는 경우가 발생해 보강시 많은 주의가 요구된다. 동조질량감쇠기의 사용은 좋은 제진효과를 보였으나 실구조물과 정확한 진동특성을 반영한 모델의 작성이 중요한 것으로 판단되었다.

유전자알고리즘을 이용한 캐비닛 구조의 최적감쇠보강 (The optimum damper retrofit of cabinet structures by genetic)

  • 이계희;최익창;하동호
    • 한국전산구조공학회:학술대회논문집
    • /
    • 한국전산구조공학회 2004년도 가을 학술발표회 논문집
    • /
    • pp.379-386
    • /
    • 2004
  • The optimal seismic retrofitting of NPP(Nuclear Power Plant) cabinet structures that contained class 1 relays were studies in this paper. During earthquake event, the failure modes of relays are not appeared in form of structural failure, but are appeared in form of contact chatter of relay. Therefore, the retrofitting of cabinet has to be aimed to the reducing of the structural response, such as acceleration. In this study, the optimal characteristic values of dampers were searched by μ-GA (micro-Genetic Algorithm) scheme for several installation patterns. To keep accuracy and efficiency of analysis, the structural models of cabinet were considered as a frame structure. The responses of structure were obtained in form of acceleration response spectra derived from the results of nonlinear time history analysis including damping nonlinearity. The fitness function of the optimum procedure was constructed based on the ratio of maximum spectral value and target GERS (General Equipment Ruggedness Spectra). The results show the good improvements of fitness fur adequate retrofitting pattern. Especially, the improvements of fitness were remarkable when the damping exponents are proper.

  • PDF

납-고무베어링을 적용한 제어장비의 동적 특성평가 (Dynamic Property Evaluation of Control Equipment using Lead Rubber Bearing)

  • 이경진;김갑순;서용표
    • 한국지진공학회:학술대회논문집
    • /
    • 한국지진공학회 2002년도 추계 학술발표회 논문집
    • /
    • pp.341-348
    • /
    • 2002
  • In these days, The base isolation system is often used to improve the seismic capacity of the structures instead of conventional techniques of strengthening the structural members. The purpose of this study is to evaluate dynamic property evaluation of control equipment using lead Lead Rubber Bearing. In this study, a base isolation test of seismic monitoring control cabinet with LRB(lead rubber bearing) was performed. The cabinet will be installed on access floor in MCR(main control room) of nuclear power plant. Details and dynamic characteristics of the access floor were considered in the construction of testing specimen. N-S component of El Centre earthquake was used as seismic input motion. Acceleration response spectrums in the top of cabinets showed that the first mode frequency of cabinet with LRB(lead rubber bearing) was shifted to 7.5 Hz in compared with 18Hz of cabinet without LRB and the maximum peak acceleration was reduced in a degree of22 percent from 2.35 g to 1.84 g

  • PDF

원자로 제어봉 구동장치 제어시스템용 전력제어기 개발 (Development of Power Controller for Control Rod Drive Mechanism in Reactor)

  • 김춘경;천종민;이종무;권순만
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 학술회의 논문집 정보 및 제어부문 B
    • /
    • pp.575-579
    • /
    • 2003
  • In this paper, we describe a Duplex Power Controller for Control Rod Control System(CRCS). A Duplex Power Controller has the various functions for the reliable operations of Control Rod Drive Mechanism(CRDM). Also we have implemented the diverse functions by utilizing the developed Duplex Power Controller. Due to the developed Duplex Power Controller, we are assured that the commercial operation by this system be made before long.

  • PDF

열유동 해석을 이용한 컴퓨터 구조의 소형화 설계 (Optimal Miniaturization of Desk-Top Computer by Thermal Design)

  • 박성관
    • 한국CDE학회논문집
    • /
    • 제4권4호
    • /
    • pp.318-326
    • /
    • 1999
  • Recently, electronic systems including computers have been rapidly shrinking in size while at the same time the complexity and the capability of these systems continue to grow/sup [1]/. Thus, system volumes have decreased as system power has increased, resulting in dramatic increases in system heat density. The high temperature of the computer system is considered as the major reason for low performance and shortening life of the product. It is necessary to solve this problem due to the heat density increased and to develop the design skill of the computer cabinet according to miniaturization. M4500 desk-top computer was selected for analyzing the thermal management inside cabinet. The cabinet volume, the configuration of the heating devices, the size and location of air ventilation, and the fan selection have been investigated as the important parameters to find out an optimal cabinet design. The objectives of this project were to analyze which design parameters would affect cooling performance by thermal strategy, to design an optimal model, and to measure the temperatures of the main parts to confirm the effect of the thermal design. The temperatures of each part of the optimal model were compared with those of the existing model. As a result. the volume of this miniaturized model was about 16% smaller than that of M4500 without any change in operating performance.

  • PDF

Variation of reliability-based seismic analysis of an electrical cabinet in different NPP location for Korean Peninsula

  • Nahar, Tahmina Tasnim;Rahman, Md Motiur;Kim, Dookie
    • Nuclear Engineering and Technology
    • /
    • 제54권3호
    • /
    • pp.926-939
    • /
    • 2022
  • The area of this study will cover the location-wise seismic response variation of an electrical cabinet in nuclear power point (NPP) based on classical reliability analysis. The location-based seismic ground motion (GM) selection is carried out with the help of probabilistic seismic hazard analysis using PSHRisktool, where the variation of reliability analysis can be understood from the relation between the reliability index and intensity measure. Two different approaches such as the first-order second moment method (FOSM) and Monte Carlo Simulation (MCS) are helped to evaluate and compare the reliability assessment of the cabinet. The cabinet is modeled with material uncertainty utilizing Steel01 as the material model and the fiber section modeling approach is considered to characterize the section's nonlinear reaction behavior. To verify the modal frequency, this study compares the FEM result with recorded data using Least-Squares Complex Exponential (LSCE) method from the impact hammer test. In spite of a few investigations, the main novelty of this study is to introduce the reader to check and compare the seismic reliability assessment variation in different seismic locations and for different earthquake levels. Alongside, the betterment can be found by comparing the result between two considered reliability estimation methods.