  • This paper provides an assessment of the potential economic impacts of the Vietnam-Korea free trade agreement on Vietnam, by using general equilibrium modeling. The results show that Vietnam-Korea FTA will increase aggregate welfare for both countries in the long run. The most important gains accrue from better allocation of resources consequent to trade liberalization. All the sectoral differences and changes are consistent with the trade profiles of the two countries, and the long-run results are more pronounced than those of the short-run. In comparison with other ASEAN countries, the CGE analysis suggests that Vietnam's agriculture exports to Korea would especially rise in the long run. However, there will be strong competition in this sector among ASEAN members. Thus, an earlier conclusion of a comprehensive FTA with Korea is expected to be a good strategy for Vietnam, so as to avoid the direct competition with ASEAN members in the future.

Measurement and Analysis of the Dangerous Voltage Around Grounding Electrode for Safety in Substation Ground (변전소 접지설계를 위한 접지전극 주변의 위험전압 측정과 분석)

  • Son, Seok-Geum;Kim, Jae-Chul
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.60 no.4
    • /
    • pp.214-219
    • /
    • 2011
  • The substation grounding design,"IEEE Guide for Safety in AC Substation Grounding (ANSI / IEEE Std 80)"has been widely used. Substation grounding design and substation grounding resistance of grounding network site to predict the voltage at the risk of a very important task, which is a ground fault current due to the influx of the ground network and due to rise in the Earth's potential can be applied to human dangerous Voltage within safe tolerances be configured to be the ground because the network. IEEE Std. 80 for the substation construction safety equipment on the ground securing the ground electrode and the mesh around the boundary potential distribution in terms of risk analysis by the touch voltage and the reference was to clean up the definition and the basic steps of the voltage of the voltage limits the risk of peripheral grounding electrode Suppression by the simulator through a new secure from dangerous voltage design techniques were presented.

The Optimization Grounding Analysis for Soil Resistivity (대지저항률에 따른 최적화 접지 해석)

  • Jung, Yeon-Ha;Jang, Tae-Jun;Kwak, Hee-Ro;Roh, Young-Su;Shong, Kil-Mok
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.11a
    • /
    • pp.241-245
    • /
    • 2004
  • The electric safety tends to be more important according to electric facilities's increase and its use in these days. This paper analyzes soil resistivity of two areas in the country using CDEGS(Current Distribution, Electromagnetic Interference, Grounding and Soil Structure, Canada). We designed rod and mesh grounding system and made a comparative study of ground resistance, GPR(Main Electrode Potential Rin), step voltage and touch voltage. Then we could analyz only the safety but also economical efficiency in elocution of grounding. As a result of simulation, ground resistance, GPR(Main Electrode Potential Rise), step voltage and touch voltage became higher in proportion to soil resistivity. Therefore we expect to estimate the propriety of grounding system design through accumulation and analysis of data in consideration of characteristics of soil.

  • PDF

A Protection Technique Against the Damages Caused by Lightning Surges on Information and Communication Facilities

  • Lee, Bok-Hee;Kang, Sung-Man;Ahn, Chang-Hwan
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • v.3C no.4
    • /
    • pp.117-122
    • /
    • 2003
  • The AC power lines and signal lines of info-communication networks are routed on overhead poles and are highly exposed to lightning strikes. Due to the potential difference between grounding points of AC power lines and signal lines, the electronic equipments connected to the signal lines can easily be damaged by lightning surges. In this work, in order to develop reliable methods of protecting information and communication facilities from lightning surges, the reliability and performance of SPDs (surge protective devices) were experimentally investigated in an actual-sized test circuit. The behaviors of SPDs against lightning surges from AC power lines and signal lines and the coordinated effects of SPD installation methods were evaluated. As a consequence, it was confirmed that the bypass arrester methods and common grounding system are both highly effective.

Analysis on Rail Potential on the AC Electric Railway Grounding System (교류전기철도 매설접지방식에서의 레일전위 해석)

  • Chang, Sang-Hoon;Oh, Kwang-Hae;Kim, Joo-Rak;Choi, Kyu-Hyung;Kim, Jung-Hoon
    • Proceedings of the KIEE Conference
    • /
    • 2001.04a
    • /
    • pp.446-448
    • /
    • 2001
  • Railway electrification results in Electromagnetic Interference, which affects a life and a equipment. Therefore, a plan against EMI must be considered. This study presents accurate simulation to examine a reason rail potential rise and how to design ground connection and draw up a plan of an optimal buried grounding system according to section.

  • PDF

Transient Ground Impedance of Small-sized Needle-rod Electrodes due to Underground Soil Discharge (토양의 지중방전에 따른 소형 침봉전극의 과도접지임피던스)

  • Lee, Tae-Hyung;Cho, Sung-Chul;Eom, Ju-Hong;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.10a
    • /
    • pp.211-215
    • /
    • 2008
  • This paper deals with the transient ground impedance of small-sized needle-rod installed in a test field, Impulse voltage generator was used to inject lightning impulse on a ground electrode and modified fall-of potential method was proposed to measure the high ground potential rise. Transient ground impedance was analysed with impedance curve and I-V curve as respects the resistivity of soil. Soil ionization near the ground electrode is activated in high resistivity soil and have an effect on the reduction of transient ground impedance significantly.

  • PDF

Towards Resource-Generative Skyscrapers

  • Imam, Mohamed;Kolarevic, Branko
    • International Journal of High-Rise Buildings
    • /
    • v.7 no.2
    • /
    • pp.161-170
    • /
    • 2018
  • Rapid urbanization, resource depletion, and limited land are further increasing the need for skyscrapers in city centers; therefore, it is imperative to enhance tall building performance efficiency and energy-generative capability. Potential performance improvements can be explored using parametric multi-objective optimization, aided by evaluation tools, such as computational fluid dynamics and energy analysis software, to visualize and explore skyscrapers' multi-resource, multi-system generative potential. An optimization-centered, software-based design platform can potentially enable the simultaneous exploration of multiple strategies for the decreased consumption and large-scale production of multiple resources. Resource Generative Skyscrapers (RGS) are proposed as a possible solution to further explore and optimize the generative potentials of skyscrapers. RGS can be optimized with waste-energy-harvesting capabilities by capitalizing on passive features of integrated renewable systems. This paper describes various resource-generation technologies suitable for a synergetic integration within the RGS typology, and the software tools that can facilitate exploration of their optimal use.

Dynamic characteristics of hygro-magneto-thermo-electrical nanobeam with non-ideal boundary conditions

  • Ebrahimi, Farzad;Kokaba, Mohammadreza;Shaghaghi, Gholamreza;Selvamani, Rajendran
    • Advances in nano research
    • /
    • v.8 no.2
    • /
    • pp.169-182
    • /
    • 2020
  • This study presents the hygro-thermo-electromagnetic mechanical vibration attributes of elastically restrained piezoelectric nanobeam considering effects of beam surface for various elastic non-ideal boundary conditions. The nonlocal Eringen theory besides the surface effects containing surface stress, surface elasticity and surface density are employed to incorporate size-dependent effects in the whole of the model and the corresponding governing equations are derived using Hamilton principle. The natural frequencies are derived with the help of differential transformation method (DTM) as a semi-analytical-numerical method. Some validations are presented between differential transform method results and peer-reviewed literature to show the accuracy and the convergence of this method. Finally, the effects of spring constants, changing nonlocal parameter, imposed electric potential, temperature rise, magnetic potential and moisture concentration are explored. These results can be beneficial to design nanostructures in diverse environments.

Analysis of Ground Impedance of a Ground Rod Using Circuit Models (회로모델을 이용한 봉상전극 접지임피던스의 분석)

  • Lee, Bok-Hee;Lee, Tae-Hyung;Eom, Ju-Hong
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.05a
    • /
    • pp.95-99
    • /
    • 2004
  • A systematic approach of measurement, modeling and analysis of grounding system impedance in the field of lightning protection systems is presented. The measurement and analysis of ground impedance are based on a computer aided technique. The magnitude and phase of ground impedance were measured and analyzed by the modified fall-of-potential method and the proposed computer program algerian using the waveforms of the test current and potential rise. The theoretical analysis of ground impedance were performed with the equivalent circuit models, and the theoretical results were compared with the measured data.

  • PDF

Effect of Mutual Coupling Between Test Leads on Ground Impedance Measurement (측정선의 상호유도작용이 접지임피던스의 측정에 미치는 영향)

  • Lee, Bok-Hee;Eom, Ju-Hong;Cho, Sung-Chul
    • Proceedings of the KIEE Conference
    • /
    • 2003.11a
    • /
    • pp.71-74
    • /
    • 2003
  • Fall-of-potential method is used usually to measure the ground impedance of large scale grounding system exactly. Because the interlinked magnetic flux between closed loops to inject test current and to measure potential rise is existed in E-P-C straight line arrangement, mutual(or inductive) coupling influences greatly on the measurement correctness. Measurement errors produced from inductive coupling could be reduced by the arrangement methods of auxiliary electrodes. Right angle or P-E-C order arrangement methods were effective to reduce the inductive coupling and the decrease degree of measurement error was analysed as quantitative through an experiment.

  • PDF