• 제목/요약/키워드: Polymer Arrester

검색결과 33건 처리시간 0.024초

고분자 피뢰기의 기밀특성에 관한 연구 (Sealing Integrity of polymeric ZnO Surge Arresters)

  • Liang, He-Jin;Han, Se-Won;Cho, Han-Goo;Kim, In-Sung
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1997년도 추계학술대회 논문집
    • /
    • pp.258-261
    • /
    • 1997
  • The sealing integrity is related to the safe operation of arrester the prime failure reason of porcelain housed arresters is moisture ingress. To be a meaningful tests a polymer arrester sealing test must be a realistic acceleration of field service. We think the test should be an accelerating course of actual temperatures, the enduring property to mechanical load and temperatures should be considered together. A union test method consisting of the thermal mechanical test and thermal cycling test is proposed to test the sealing integrity of polymeric arresters, which uses dielectric loss, leakage current 1mA DC voltage and partial discharge as the diagnostic techniques, and the test results were presented. The comparison states that the TMTCUT method is suitable fur the test of sealing integrity of polymeric arresters. .

  • PDF

전철 탑재용 피뢰기의 설계 및 성능평가 (Design and Performance Evaluation of Surge Arrester for Loading in Railway Rolling Stock)

  • 조한구;한세원;이운용;김석수;장태봉
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 춘계학술대회 논문집 유기절연재료 방전 플라즈마
    • /
    • pp.74-77
    • /
    • 2000
  • The main objective of this paper is to design and test a new type of polymer ZnO surge arrester for AC power system of railroad vehicles. Metal oxide surge arrester for most electric power system applications, electric train and must not have explosive breakage of the housing to minimize damage to other equipment when subjected to internal high short circuit current. When breakdown of ZnO elements in a surge arrester occurs due to flashover, fault short current flows through the arrester and internal pressure of the arrester rises. The pressure rise can usually be limited by fitting a pressure relief diaphragm and transferring the arc from the inside to the outside of the housing. However, there is possibility of porcelain fragmentation caused by the thermal shock. pressure rise, etc. Non-fragmenting of the housing is the most desired way to prevent damage to other equipment. The pressure change which is occurred by flashover become discharge energy. This discharge energy raises to damage arrester housing and arrester housing is dispersed as small fragment. Therefore, the pressure relief design is requested to obstruct housing dispersion. The main research works are focused on the structure design by finite element method, pressure relief of module, and studies of performance of surge arrester for electric railway vehicle.

  • PDF

열-기계적 스트레스가 폴리머 피뢰기의 전기적 특성에 미치는 영향 (Effect of Thermal Mechanical Stresses on Electrical Characteristics of Polymer Housed Surge Arresters)

  • 조한구;유대훈
    • 한국전기전자재료학회논문지
    • /
    • 제20권6호
    • /
    • pp.555-560
    • /
    • 2007
  • This paper describes the results of a study on the sealing integrity of polymer housed surge arrester based on the thermal mechanical test. The polymer housed surge arrester employs silicone insulating materials for its housing, instead of the conventional porcelain housing. The polymer housed surge arresters exhibited the highest sealing integrity because it is not air volume between the FRP(fiber reinforced plastics) module and the silicone housing. In accordance, the sealing integrity of station class surge arresters is investigated with moisture ingress test. And, the influence of sealing integrity was evaluated through such as measurement of the deflection, reference voltage, leakage current. In electrical characteristics, reference voltage decreased in the range of $16.45{\sim}16.15\;kV$ with after thermal mechanical test. In contrary, despite the continued moisture ingress, the polymer housed surge arresters exhibited almost the same leakage current value and the resistive leakage current has risen slightly. As a results, It was thought that the polymer housed surge arresters shows good stability with sealing integrity.

전철 탑재형 피뢰기의 모듈설계 및 성능평가기술 (Module Design and Performance Evaluation of Surge Arrester for Loading In Railway Rolling Stock)

  • 조한구;김석수;한세원;이운응
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 C
    • /
    • pp.2038-2040
    • /
    • 2000
  • The main objective of this paper is to design and test a new type of polymer ZnO surge arrester for AC power system of railroad vehicles. Metal oxide surge arrester for most electric power system applications, electric train and subway are now being used extensively to protect overvoltage due to lightning. Surge arresters with porcelain housing must not have explosive breakage of the housing to minimize damage to other equipment when subjected to internal high short circuit current. When breakdown of ZnO elements in a surge arrester occurs due to flashover, fault short current flows through the arrestor and internal pressure of the arrester rises. The pressure rise can usually be limited by fitting a pressure relief diaphragm and transferring the arc from the inside to the outside of the housing. However, there is possibility of porcelain fragmentation caused by the thermal shock, pressure rise. etc. Non-fragmenting of the housing is the most desired way to prevent damage to other equipment. The pressure change which is occurred by flashover become discharge energy. This discharge energy raises to damage arrester housing and arrester housing is dispersed as small fragment. Therefore, the pressure relief design is requested to obstruct housing dispersion. The main research works are focused on the structure design by finite element method, pressure relief of module, and studies of performance of surge arrester for electric railway vehicle.

  • PDF

폴리머 피뢰기 단락회로내력시험에 대한 고찰 (A study for short-circuit tests of polymer arrester depends on standards)

  • 최익순;김석수;김건중
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 C
    • /
    • pp.1527-1528
    • /
    • 2006
  • This paper presents short-circuit tests for polymer-housed distribution arrestors depends on standards. The compared standards are IEC 60694(2004) and IEEE C62.11 (2005). Major differences depends on standards are prefaulted(pre-failure) method by means of a fuse wire and test procedure.

  • PDF

고분자 절연재료의 트랙킹 열화에 미치는 오손액의 영향 (The Effect of Contaminants on Tracking Aging in Polymer Insulating Materials)

  • 조한구;박용관
    • E2M - 전기 전자와 첨단 소재
    • /
    • 제10권8호
    • /
    • pp.770-777
    • /
    • 1997
  • Some polymer materials including epoxy resin are being instead of porcelain for outdoor insulating materials such as insulators bushings cable terminators and surge arrester housing. And the largest problem to be overcomed is the tracking and erosion of the outdoor polymer material brought about by dry band arcing during prolonged exposure to contaminations. In this paper the effect of surface tension wettability flow rate of contaminants with varying surfactant content and frequency of applied voltage on the tracking breakdown of epoxy insulating materials were investigated. As the flow rate of contaminant is increased the surface resistivity is decreased and the leakage current is increased the time to tracking breakdown is decreased. It is found that time to tracking breakdown depends on the surface tension of contaminant that is difference of wettability. And as the frequency of applied voltage is increased time to tracking breakdown decreased.

  • PDF

복합가속열화시험에 의한 폴리머 피뢰기의 경년특성 (Aging Characteristics of Polymer Lighting Arrester by Multi-Stress Accelerated Aging Test)

  • 송현석;이재봉;장상옥;한용희;오재형
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2004년도 춘계학술대회 논문집
    • /
    • pp.86-89
    • /
    • 2004
  • Recently polymer arresters are being used widely but we don't have appropriate long term characteristics test methods. Therefore we need to develop special test facility to evaluate long term reliability of polymer arresters. It's polymeric housing can be degraded by environmental stress and the interface between housing and inner module can be affected by moisture absorption. This moisture absorption can cause leakage current and tracking in the interface. We developed multi stress accelerated ageing test facility to simulate field conditions including UV, temperature, humidity, voltage, salt fog and rain. In addition, we carried out field exposure test at the outdoor test yard and characteristics analysis of field operated specimens to evaluate accelerating factor of this accelerated aging test.

  • PDF

직류 전차선로용 공극형 피뢰기의 특성 분석 (Characteristic Analysis of Gapped Surge Arresters for D.C. Railway Line)

  • 조한구;한세원;윤한수;천종욱
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 하계학술대회 논문집
    • /
    • pp.485-488
    • /
    • 2001
  • This paper provides the result of analysis of the structure and I-V characteristics of D.C. 1500 V surge arresters which were installed in railway line currently. As Porcelain housed surge arresters have unstable elements such as exploding and dispersion, so it is thought that the system is protected more stably with replacement of polymer housing. The adoption of gap mitigates the voltage stress which is degradation factor of surge arresters and the research is needed to enhance the life characteristic in additive and manufacturing process. Therefore, it is thought that the research should be continued to develop homemade the surge arresters for D.C. railway line as well as transmission line.

  • PDF

가속열화시험을 이용한 배전용 폴리머피뢰기의 장기신뢰성 평가기법 개발 (Development of Longtime Reliability Assessment Method of Polymer Housed Distribution Surge Arresters using Accelerated Aging Test)

  • 김주용;송일근;문재덕
    • 조명전기설비학회논문지
    • /
    • 제20권10호
    • /
    • pp.141-150
    • /
    • 2006
  • 본 논문에서는 폴리머피뢰기의 현장 열화인자를 인가할 수 있는 가속열화 시험장치를 제작하고 국내 환경조건을 모의할 수 있는 시험주기를 개발하여 폴리머피뢰기 완제품에 대한 장기신뢰성 평가법을 제안하였다. 그리고 가속열화시험 및 현장설치에 의한 전기적, 화학적 특성변화를 분석하여 폴리머피뢰기의 열화정도를 평가함으로써 본 연구에서 제안한 평가기법의 실효성을 검증하고 국산 폴리머피뢰기의 유지보수에 필요한 특성 데이터를 제시하였다.

침수시험에 의한 비전용 폴리머피뢰기의 특성연구 (A Study on the Submergence Test of the Distribution Polymer Surge Arrester)

  • 김주용;권태호;송일근;이재봉;김동명;정영호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.104-106
    • /
    • 2003
  • 본 논문은 이상전압으로부터 배전선로 및 전력기기를 보호하기 위해 사용되는 폴리머피뢰기에 대해 침수 시험을 실시하여 침수 전후 폴리머피뢰기의 특성변화를 평가하였다. 침수 시험은 수온 95[$^{\circ}C$]에서 20일 동안 실시하였다. 침수 시험 전후 폴리머피뢰기의 특성분석은 푸리에변환 적외선분광기(FTR : fourier transform infrared spectrophotometer), 유전열분석(DETA : dielectric thermal analyzer), 발수성 측정, 절연저항 측정, 누설전류 측정, 동작개시전압 측정 둥으로 연구 하였다. 이를 통해 침수시험의 열화 효과에 대해 검토하였다.

  • PDF