Browse > Article
http://dx.doi.org/10.4313/JKEM.2007.20.6.555

Effect of Thermal Mechanical Stresses on Electrical Characteristics of Polymer Housed Surge Arresters  

Cho, Han-Goo (한국전기연구원 재료응용연구단)
You, Dae-Hoon (한국전기연구원 재료응용연구단)
Publication Information
Journal of the Korean Institute of Electrical and Electronic Material Engineers / v.20, no.6, 2007 , pp. 555-560 More about this Journal
Abstract
This paper describes the results of a study on the sealing integrity of polymer housed surge arrester based on the thermal mechanical test. The polymer housed surge arrester employs silicone insulating materials for its housing, instead of the conventional porcelain housing. The polymer housed surge arresters exhibited the highest sealing integrity because it is not air volume between the FRP(fiber reinforced plastics) module and the silicone housing. In accordance, the sealing integrity of station class surge arresters is investigated with moisture ingress test. And, the influence of sealing integrity was evaluated through such as measurement of the deflection, reference voltage, leakage current. In electrical characteristics, reference voltage decreased in the range of $16.45{\sim}16.15\;kV$ with after thermal mechanical test. In contrary, despite the continued moisture ingress, the polymer housed surge arresters exhibited almost the same leakage current value and the resistive leakage current has risen slightly. As a results, It was thought that the polymer housed surge arresters shows good stability with sealing integrity.
Keywords
Surge arresters; Polymer housing; Seating integrity; Deflection; Leakage current; Airtight;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 L. M. Levinson and H. R. Philipp, 'Zinc oxide varistors review', Am. Ceram. Soc. Bull., Vol. 65, p. 639, 1986
2 T. K. Gupta, 'Application of zinc oxide varistors', J. Am. Ceram. Soc., Vol. 73, p. 1817, 1990   DOI
3 V. Chaudhry, R. S. Gorur, R. S. Dyer, and R. Thallam, 'Electrical performance of polymer housed zinc oxide arresters under contaminated conditions', IEEE Trans. Power Delivery, Vol. 6, No.2, p. 696, 1995   DOI   ScienceOn
4 J. A. Bennett, J. P. Mackevich, and R. J. Mosso, 'Innovation in polymer arrester moisture sealing testing', IEEE Trans. Power Delivery, Vol. 10, No.1, p. 237, 2004   DOI   ScienceOn
5 E. A. Cherney, B. Biglar, and S. Iayaram, 'Salt fog testing of polymer housed surge arresters', IEEE Trans. Power Delivery, Vol. 16, No.2, p. 252, 2001   DOI   ScienceOn
6 K. Lahti, K. Kannus, and K. Nousiainen, 'Diagnostic methods in revealing internal moisture in polymer housed metal oxide surge arresters', IEEE Trans. Power Delivery, Vol. 17, No.4, p. 951, 2002   DOI   ScienceOn
7 IEC 60099-4, 'Metal-oxide surge arresters without gaps for a.c. systems', 2004. 5
8 K. Steinfeld, B. Kruska, and W. Welsch, 'Manufacturing and application of cage design voltage metal oxide surge arresters', international symposium on high voltage engineering, 2003
9 길경석, 한주섭, 송재용, 조한구, '누설전류의 파고분석에 의한 피뢰기 진단기술 및 장치' 대한전기학회논문지,52C권, 12호, p. 46, 2003
10 조한구, 유대훈, 이운용, 김하나, '폴리머 피뢰 기의 구조에 따른 온도와 누설전류 특성' 전기전자재료학회논문지, 20권,3호, p. 273, 2007   과학기술학회마을   DOI