대용량 수치발전기의 절연진단에 의한 절연상태평가 (Assessment of Insulation Condition for Hydro-generator)

  • 이광호;박종진;김기원;이은웅
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 C
    • /
    • pp.1810-1812
    • /
    • 2002
  • This test was performed to assess the insulation deterioration condition of the stator winding of Chung-Ju hydrogenerator #4 and Dae-Cheong hydrogenerator #2 which had been in service after being constructed 1980. The insulation diagnostic tests include resistance polarization index(P.I.) AC current, dissipation factor(Tan ${\delta}$) and partial discharges ($Q_{max}$). The results of diagnostic tests were compared to factory test measurements.

  • PDF

발전기 고정자 권선 절연재료의 초기특성 (Initial Characteristics of Generator Stator Insulations)

  • 이영준;김희동
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 E
    • /
    • pp.2110-2113
    • /
    • 1999
  • This paper describes the initial characteristics of turbine generators at the Taean thermal power plant #4 and Wolsong nuclear power plant #2. The turbine generators had been in service for two years. The insulation diagnostic tests included measurements of insulation resistance, polarization index, ac current, dissipation factor($tan{\delta}$) and partial discharges (PD). The values of ac current and tan a were measured by Schering bridge. PD measurements were conducted using digital PD detector. The variation of $tan{\delta}$ and PD was confirmed in two generator stator insulations.

  • PDF

인버터 전원에 의한 견인전동기 고정자 코일의 절연특성 변화 (Change of Insulation Properties of Stator Coil fed by Inverter Source on Traction Motor)

  • 장동욱;박현준;이길헌;최종선;김정수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 춘계학술대회 논문집 전기기기 및 에너지변환시스템부문
    • /
    • pp.420-422
    • /
    • 2003
  • Aging and failure of motor insulation depend on the stresses imposed on it. The insulation life time depends on the severity of the stresses. The electrical aging by transient surge is very important to traction motor in EMU(electric multiple unit). This paper Presents the insulation characteristics of stator coil by transient surge from inverter. There are several nondestructive tests available for checking the condition of motor insulation, the probable extent of aging,. and the rate of which aging is taking pace. So the insulation characteristics of stator coil were each analyzed by measurement of leakage current, dielectric loss($tan{\delta}$), capacitance, polarization index(PI) and partial discharge. The method of diagnosis is able to analyze the aging condition and Predict the life of the traction motor in EMU.

  • PDF

FABRICATION AND CHARACTERIZATION OF NONLINEAR OPTICAL GLASSES

  • Cardinal, T.;Fargin, E.;Le Flem, G.
    • 한국광학회:학술대회논문집
    • /
    • 한국광학회 2001년도 제12회 정기총회 및 01년도 동계학술발표회
    • /
    • pp.4-5
    • /
    • 2001
  • Advent of lasers offering high intensity beam has opened the glass to the nonlinear optic (NLO). The high electric field associated with such laser beams can be so large that high order components of the glass polarization can be measured. Such development is of scientific and technological interests in particular in systems involving an intensity-dependent refractive index and/or ultra-fast response (<10$\^$-12/s). From a scientific viewpoint the NLO response intensity must be understood as a function of the glass composition. On the other hand, large family of applications are presently under investigation in various fields of optical materials or systems e.g. laser glasses for fusion energy, soliton propagation for ultra-long distances, ultra-fast-switching, optical storage etc....(omitted)

  • PDF

In-line Variable Optical Attenuator Based on the Bending of the Tapered Single Mode Fiber

  • Kim, Kwang-Taek;Kang, Ji-Hoon;HwangBo, Seung;Im, Kie-Gon
    • Journal of the Optical Society of Korea
    • /
    • 제13권3호
    • /
    • pp.349-353
    • /
    • 2009
  • We propose a simple in-line variable optical attenuator (VOA) based on the bending effect of tapered single mode fibers. The influence of the taper structure and the reflective index of the external medium surrounding the taper region on the bending loss of the tapered fiber have been investigated experimentally. An attenuation range exceeding 35 dB and a very low excess loss of < 0.2 dB at 1550 nm were achieved. The measured polarization dependent loss of the present VOA at the attenuation level of 10 dB, 20 dB, and 30 dB were 0.1 dB, 0.2 dB, and 0.5 dB, respectively.

Widely Tunable Wavelength-Selective Reflector Using Polymer Waveguide Double-Ring-Resonator Add/Drop Filter and Loop-back Mirror

  • Lee, Ho;Kim, Gun-Woo;Park, Jun-Oh;Kim, Su-Hyun;Chung, Young-Chul
    • Journal of the Optical Society of Korea
    • /
    • 제12권3호
    • /
    • pp.157-161
    • /
    • 2008
  • A wavelength-selective reflector, composed of a double-ring-resonator add/drop filter and a loop-back mirror at the drop port to be used for a hybrid-integrated tunable laser is designed and fabricated. High-index-contrast polymer waveguide is used to realize a compact device as small as $2mm{\times}0.4mm$. The radii of the rings are slightly different from each other to obtain a wide wavelength tuning via a vernier effect. Peak reflectivity is measured to be 52% for TE mode and polarization-dependent wavelength shift is 0.95 nm. The tuning range is measured to be about 42 nm for applied current as small as 46 mA.

견인전동기 고정자 코일의 전기적 열화특성 (Properties of Electrical Performance on Stator Coil of Traction Motor by Accelerated Test)

  • 박현준;장동욱;김길동
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2003년도 추계학술대회 논문집(III)
    • /
    • pp.623-627
    • /
    • 2003
  • Aging and failure of motor insulation depend on the stresses imposed on it. The insulation life time depends on the severity of the stresses. The electrical aging by transient surge is very important to traction motor in EMU(electric multiple unit). This paper presents the insulation characteristics of stator coil by transient surge from inverter. There are several nondestructive tests available for checking the condition of motor insulation, the probable extent of aging, and the rate of which aging is taking place. So the insulation characteristics of stator coil were each analyzed by measurement of leakage current, dielectric loss($tan{\delta}$), capacitance, polarization index(PI) and partial discharge. The method of diagnosis is able to analyze the aging condition and predict the life of the traction motor in EMU.

  • PDF

전기철도용 견인전동기의 복합가속열화 상태진단에 관한 연구 (A Study on the Complex Accelerating Degradation and Condition Diagnosis of Traction Motor for Electric Railway)

  • 왕종배
    • 한국전기전자재료학회논문지
    • /
    • 제15권1호
    • /
    • pp.93-101
    • /
    • 2002
  • In this study, the stator form-winding sample coils based on silicone resin and polyimide were made for fault prediction and reliability estimation on the C-Class(200$\^{C}$ ) insulation system of traction motors. The complex accelerative degradation was periodically performed during 10 cycles, which was composed of thermal stress, fast rising surge voltage, vibration, water immersion and overvoltage applying. After aging of 10 cycles, the condition diagnosis test such as insulation resistance '||'&'||' polarization index, capacitance '||'&'||' dielectric loss and partial discharge properties were investigated in the temperature range of 20 ∼ 160$\^{C}$. Relationship among condition diagnosis tests was analyzed to find a dominative degradation factor and an insulation state at end-life point.

수력발전기의 절연보강 전${\cdot}$후 절연상태 비교평가 (Assessment of Insulation Condition between Diagnosis and Impregnation for Hydro-Generator)

  • 변일환;이은웅
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 B
    • /
    • pp.1124-1126
    • /
    • 2004
  • The measurements were performed to assess the insulation deterioration condition of the stator winding of Dae-Cheong hydro-generator ${\sharp}2$ which had been in service after being constructed 1980. After repair of the stator winding insulation. we conducted insulation diagnostic tests which include resistance, polarization index(P. I). AC current, dissipation factor($Tan{\delta}$) and partial discharges ($Q_{max}$). The results of diagnostic tests were compared to the previous records. On the basis of these test results. this paper tried to present the importance of insulation repair for the generator stator winding.

  • PDF

대형발전기 고정자권선 절연재료의 열 사이클에 의한 열화에 관한 연구 (A study on the heat cycle aging of insulation materials in large generator stator windings)

  • 김희곤;박영관
    • 대한전기학회논문지
    • /
    • 제45권4호
    • /
    • pp.553-557
    • /
    • 1996
  • Heat cycle aging of insulating materials in large generator stator winding has been investigated using both on-line and off-line test methods. On this study, principally, off-line test against actual generator in service was carried out to acquire information about polarization index(PI) and dissipation factor, dissipation factor tip-up, maximum partial discharge for the purpose of remnant breakdown voltage and life assessment. It was found from the tests that both dissipation factor and maximum partial discharge decreased with the increase of operating hours and starting numbers. It was found from off-line tests that the remnant breakdown voltage had a strong relationship with both dissipation factor and maximum partial discharge the remnant breakdown voltage as a results of both operating hours and starting number and the nondestructive tests were proposed as parameters which can predict the remnant lifetime of insulating materials in large generator stator windings. (author). 8 refs., 8 figs., 2 tabs.

  • PDF