• 제목/요약/키워드: Plate Fin-Tube Heat Exchanger

검색결과 36건 처리시간 0.027초

Plate fin-oval tube 열교환기에서 와류발생체에 의한 fin 표면에서의 국소 열전달 특성 (Local Heat Transfer Characteristics on Fin Surface of Plate Fin - Oval Tube with Delta Wing Vortex Generators)

  • 신석원;정인기;김수연
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2007년도 춘계학술대회B
    • /
    • pp.2390-2395
    • /
    • 2007
  • The present research was experimentally performed to analyze the effect of delta-wing vortex generators(DWVG) on the heat transfer of fin surface of the plate fin-oval tube. The local heat transfer coefficient of the fin surface for four kinds of DWVG's arrangement was measured by the naphthalene sublimation technique for Reynolds numbers ranging from 2000 to 3200. The results showed that the heat transfer of the plate fin-oval tube can be significantly enhanced by DWVG for relatively low Reynolds numbers.

  • PDF

휜-관 열교환기의 착상 성능 해석 (Analysis of Frosting Performance of a Fin-Tube Heat Exchanger)

  • 양동근;이관수
    • 설비공학논문집
    • /
    • 제17권11호
    • /
    • pp.965-973
    • /
    • 2005
  • This paper proposes a mathematical model for predicting the frosting performance on a fin-tube heat exchanger. The model consists of empirical correlations of average heat transfer coefficients for the plate and tube surfaces and a diffusion equation inside the frost layer. The numerical results are compared with experimental data for the frost thickness, the frosting rate and the heat transfer rate to validate the proposed model. The results are in good agreement with the experimental data, and show that this model can be applied to predict frosting performance of common fin-tube heat exchanger.

평판관-루버핀 열교환기의 공기측 열전달 및 압력강하 특성에 관한 실험적 연구 (An Experimental Study on Heat Transfer and Pressure Drop of Air Side in a Plate-Louvered Fin Heat Exchanger)

  • 강병하;김석현;장혁재;박병규
    • 설비공학논문집
    • /
    • 제14권6호
    • /
    • pp.485-492
    • /
    • 2002
  • Heat transfer and pressure drop on the air side of a plate-louvered fin heat exchanger with new shape of louver fin have been investigated experimentally. Water is employed inside the flat tube to transfer heat with air for convenience. This problem is of particular interest in the design of a plate-louvered heat exchanger. The effect of air flow rate, water flow rate and water temperature on pressure drop as well as heat transfer in air side are studied in detail. The present results showed a good agreement qualitatively with the previous results in general. Based on the experimental data, f-factor and j -factor correlations of the present louvered-fin are suggested. It is also found that heat transfer could be enhanced with new shape of louver fin, compared with the conventional louvered-fin, while the f-factor remains unchanged.

단일(單一) 긴 수직평판(垂直平板)핀을 가진 수평전도관(水平傳導管)으로 부터의 자연대류(自然對流) (Conjugate Heat Transfer by Natural Convection from a Horizontal Heat Exchanger Tube with a Long Vertical Longitudinal Plate Fin)

  • 배대석;권순석
    • 설비공학논문집
    • /
    • 제1권1호
    • /
    • pp.64-72
    • /
    • 1989
  • Laminar natural convection heat transfer from a horizontal heat exchanger tube with one infinitely long vertical plate fin has been studied by a finite-difference numerical procedure. In predicting convective heat transfer from a circular tube, the thermal boundary condition at solid fluid interface is usually assumed to be isothermal. However, in reality, the thermal boundary condition is not isothermal, and the tube has the thickness and the conductivity. So the temperature at the interface is not known a priori to the calculation. This problem has the conjugate phenomena which occur between the tube conduction and external natural convection, and between the fin conduction and external natural convection. Numerical results are obtained to determine the effects of the conductivity of solid wall and the thickness of tube wall on heat transfer. It is found that the conduction causes significant influence on the natural convection heat transfer at low K and high ${\delta}$.

  • PDF

독립 핀-튜브 열교환기의 열전달 성능특성에 관한 연구 (Study on Heat Transfer Characteristics of Discrete Fin-and-tube Heat Exchangers)

  • 이호성;김용한;최종민;김용찬
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2005년도 동계학술발표대회 논문집
    • /
    • pp.274-280
    • /
    • 2005
  • The objective of this study Is to investigate the heat transfer performance of plate discrete fin-and-tube heat exchangers with large fin pitch. In this study, twenty-two heat exchangers were tested with a variation of fin pitch, number of tube row, longitudinal tube pitch and fin alignment. Discrete fin type exchangers improved heat transfer performance more than 10% compared to tile continuous fin type heat exchangers. The air-side heat transfer coefficient decreased with a reduction of the fin pitch and an increase of the number of tube row, The staggered fin alignment improved heat transfer performance more than 6% compared to the inline fin alignment. The effect of longitudinal tube pitch was insignificant on the j-factor and experiments found opposite effects on the j-factor with respect to fin alignment. Heat transfer correlations were developed from the measured data for flat plate discrete fin-and-tube heat exchangers with large fin pitch. The correlations yielded good predictions of the measured data with mean deviations of 1,4% and 0.3% for tire inline and staggered tube alignment, respectively.

  • PDF

습표면 조건에서 슬릿 핀-튜브 열교환기의 열전달 및 압력강하 특성 (Heat Transfer and Friction Characteristics of Slit Fin and Tube Heat Exchangers in Wet Conditions)

  • 장근선
    • 설비공학논문집
    • /
    • 제19권1호
    • /
    • pp.1-9
    • /
    • 2007
  • Water condensate accumulated on the surface of a fin-and-tube heat exchanger significantly affects its thermal and hydraulic performance. The purpose of this study is to investigate the effect of condensate retention on the air-side heat transfer performance and flow friction. Total 12 samples of slit and plate fin-and-tube heat exchangers with varying fin spacing and number of tube rows are tested under dry and wet conditions. The thermal fluid measurements are made using a psychometric calorimeter. Frontal air velocity varies in the range from 0.7 m/s to 1.5 m/s. Using the experimental data, presented are the heat transfer coefficients in terms of Colburn j-factor and friction factor.

An Experimental Study of the Airside Performance of Slit Fin-and-Tube Heat Exchangers under Dry and Wet Conditions

  • Chang, Keun-Sun;Long, Phan-Than
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제17권1호
    • /
    • pp.7-14
    • /
    • 2009
  • Water condensate accumulated on the surface of a fin-and-tube heat exchanger significantly affects its thermal and hydraulic performances. The purpose of this study is to investigate the effects of condensate retention on the air-side heat transfer performance and flow friction for various flow and geometric conditions. Total of twelve samples of slit and plate fin-and-tube heat exchangers are tested under dry and wet conditions. The thermal fluid measurements are made using a psychrometric calorimeter. Frontal air velocity varies in the range from 0.7 m/s to 1.5 m/s. Using the experimental data, presented are heat transfer coefficients in terms of Colburn j-factors and friction factors, and these data are compared with the existing correlations.

평판 핀 튜브 열교환기의 공기측 강제대류 열전달계수에 대한 실험 및 수치계산 (Experimental Measurement and Numerical Computation on the Air-Side Forced Convective Heat Tranfer Coefficient in Plate Fin-Tube Exchangers)

  • 윤영환;팽진기;윤건식
    • 설비공학논문집
    • /
    • 제18권9호
    • /
    • pp.729-737
    • /
    • 2006
  • Air-side forced convective heat transfer of a plate fin-tube heat exchanger is investigated by experimental measurement and numerical computation. The heat exchanger consists of staggered arrangement of refrigerant pipes of 10.2 m diameter and the pitch of fins is 3.5 m. In the experimental study, the forced convective heat transfer is measured at Reynolds number of 1082, 1397, 1486, 1591 and 1649 based on diameter of refrigerant piping and mean velocity. Average Nusselt number for the convective heat transfer coefficient is also computed for the same Reynolds number by commercial software of STAR-CD with standard $k-{\varepsilon}$ turbulent model. It is found that the relative errors of average Nusselt numbers between experimental and numerical data are less than 6 percentage in Reynolds number of $1082{\sim}1649$. The errors between experiment and other correlations are ranged from 7% to 32.4%. But the correlation of Kim at al is closest to the experimental data within 7% of the relative error.

Performance Analysis of an Indoor Heat Exchanger with R-410A for GHP Application

  • Lee, Jong-Ho;Kim, Sung-Soo;Cha, Woo-Ho;Kang, Yong-Tae
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제17권4호
    • /
    • pp.129-134
    • /
    • 2009
  • The objectives of this paper are to study the effects of thermal and geometric conditions on the performance of indoor heat exchangers with R-410A for Gas Engine Driven Heat Pump (GHP) application and to find the optimum design conditions of indoor heat exchangers by parametric analysis for the key parameters. The key parameters are number of tube row, number of tube pipe, fin pitch and transverse tube pitch. In the air side, moisture out of the humid air condenses on the fin surface while the refrigerant (R-410A) boils inside the smooth tube. Therefore this study uses Log Mean Enthalpy Difference (LMHD) method to analyze the heat transfer from the humid air to the refrigerant. This study determines the heat exchanger size, air side/refrigerant side pressure drop and overall heat transfer coefficient. Optimum design conditions for the key parameters are also determined by the parametric analysis. The results show that number of rows and pipes, fin pitch have significant effect on the heat exchanger size. It is also found that the tube length of the louver fin is $17{\sim}30%$ shorter than that of the plate fin.

판형 핀을 가진 원통-다관형 열교환기의 열전달 특성에 관한 연구 (Study on Heat Transfer Characteristic of Shell-and-Tube Heat Exchanger with Plate Fin)

  • 임태우;조동현
    • 한국산학기술학회논문지
    • /
    • 제10권1호
    • /
    • pp.46-51
    • /
    • 2009
  • 본 논문은 세 개의 서로 다른 관수(9, 13 그리고 19)를 가지는 원통-판형 핀 관의 원통 측에서의 열전달 성능을 실험적 방법으로 평가하였다 관외를 흐르는 오일은 관내를 흐르는 냉각수에 의해 냉각된다. 오일 쿨러의 원통-다관형 열교환기는 단일 셀 통로와 두 개의 관 통로로 구성되며, 관 내경은 8.82mm, 관 길이는 575mm이다. 오일의 질량 유량은 $1.2{\sim}6.0m^3/h$이며, 냉각수의 질량 유량은 $0.6{\sim}3.0m^3/h$이다. 실험결과 9개의 관수를 가지는 열교환기의 총합 열전달계수는 13개와 19개의 관수의 열전달계수보다 각각 약 1.8배와 2.3배 높게 나타났다.