• 제목/요약/키워드: Phasor angle difference

검색결과 5건 처리시간 0.022초

동기위상 측정장치를 이용한 전력계통 위상각 측정 (Measurement of Phasor Angles of Power System using Synchronized Phasor Measurement System)

  • 이경극;이재욱;왕재명;추진부
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 추계학술대회 논문집 학회본부 A
    • /
    • pp.55-57
    • /
    • 2000
  • This paper presents the measurement of phasor angle of power system using Synchronized Phasor Measurement System(SPMS). SPMS includes the GPS receiver, so it can add the exact time information to the data acquired from the power system by SPMS. Using that data, we can compare the difference of phasor angles of voltages currents acquired at the exactly same time, and monitor the RMS values of voltage and current. In this paper, we present the difference of voltage angles between 345kV Sinjechon S/S and 345kV Asan S/S, where two SPMS were installed separately, and prove their performance by comparing to simulation result of PSS/E.

  • PDF

디지털 신호처리기법을 이용한 전력계통 주파수 추정 기법에 관한 연구 (A study on the Estimation Technique of Frequency in the Power System using Digital Signal Processing)

  • 남시복;박철원;신명철
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 하계학술대회 논문집 A
    • /
    • pp.175-177
    • /
    • 2001
  • Frequency and phasor are the most important quantities in power system operation. Frequency reflects the dynamic energy balance between load and generating power. To estimate of power system frequency, an accurate digital tracking algorithm by using phasor angle difference is presented. For an evaluation of the proposed technique, simulations by EMTP have been performed. Test results were showed the algorithm's accuracy under the effect of noise and changes in frequency and amplitude on the input signal.

  • PDF

페이저 상차각 연산에 의한 전력계통 주파수 추정 알고리즘 (A Frequency Estimation Algorithm using Phase Angle Difference Calculation in Power System)

  • 남시복;박철원;신명철
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 A
    • /
    • pp.313-315
    • /
    • 2002
  • Frequency and phasor are the most important quantities in power system operation because they can reflect the whole power system situation. This paper proposes a design and implementation using phase angle difference calculation for frequency measuring in power system. The process is considered to be complicated as compared to the present proposed method. Performance test results, using signals from Excel program, indicate that the proposed technique can provide accurate estimates within 16ms.

  • PDF

적응기법을 이용한 전력계통의 주파수 측정 (An Adaptive Scheme for Frequency Measurement in Power System)

  • 박철원;남시복;신명철
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제51권3호
    • /
    • pp.143-152
    • /
    • 2002
  • Frequency is regarded as one of most important indices for the operating power systems. Several digital techniques for measuring frequency have been presented in the last decades. This paper proposes a design and implementation an adaptive scheme using phase angle difference calculation fort frequency measuring in power system. The advantages of the proposed technique are demonstrated by fault signals from EMTP simulation and user defined arbitrary signals by Excel program. The proposed technique is compared with the conventional methods. Performance teat results indicate that the proposed technique provides accurate measures in pretence of noise and harmonics and in case faults and is suitable for measurement near-nominal, nominal. and off-nominal frequencies. We can see that It will be useful in microprocessor based relays and digital metiers that need to measure power system frequency.

상분리 모선의 자계 및 와전류 특성 해석 (Analysis of the Magnetic Field and Eddy Current Characteristics in Isolated Phase Bus System)

  • 김진수;하덕용;최승길;강형부
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제50권10호
    • /
    • pp.509-516
    • /
    • 2001
  • Isolated phase bus(IPS) has a special structure for carrying large current generated by a generator to a main transformer. In the analysis of IPB, the understanding of the magnetic field distribution generated by large current is important. Especially, while the bus conductor current is flowing, almost same amount of current as bus conductor current is induced in the enclosures under the influence of time varying magnetic field, and therefore the large electric loss and the deterioration of insulating capability might occur due to Joule heating effect. Hence for the optimal design of IPB satisfying the condition to minimize the loss, the accurate analysis of magnetic field distribution and the eddy current characteristics of three phase isolated phase bus have been investigated. In the analysis of time varying magnetic field, instead of finite difference method(FDM) which is generally used, finite element method with phasor concept is investigated under the assumption that the bus current is purely sinusoidal. The characteristics is studied along the phase angle by comparing the effect of eddy current on the magnetic field distribution with the case that eddy current is not considered, and also the effect of material, thickness and radius of enclosure on the eddy current distribution is discussed.