• Title/Summary/Keyword: Parallel active power filter

Search Result 55, Processing Time 0.027 seconds

The Compensating Unbalanced Source Voltages for Unified Active Power Filter System (직.병렬 능동 전력필터 시스템을 이용한 불평형 전원전압 보상)

  • Kim, Young-Seok;Kang, Min-Hyung
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.4
    • /
    • pp.716-723
    • /
    • 2007
  • This paper suggests of a 3-phase 3-wire unified active power filter. The system is composed of a series active power filter and a parallel active power filter. The proposed series active power filter compensating unbalance source voltage and current harmonics of the parallel active power filter improves power factor. The proposed algorithm which improves for power factor and harmonic reduction are calculated by the performance function, and which compensates for the unbalanced source voltage is calculated based on the symmetrical component analysis. We composed a combined system of the series active power filter and parallel active power filter to confirm a validity of the proposed control methods. The effectiveness of the proposed algorithm is confirmed by the experiments.

A New Parallel Hybrid Filter Configuration Minimizing Active Filter Size

  • Park, Sukin;Sung, Jeong-hyoun;Nam, Kwanghee
    • Proceedings of the KIPE Conference
    • /
    • 1998.10a
    • /
    • pp.894-897
    • /
    • 1998
  • A conventional parallel hybrid active filter has an inherent problem of large current ratings of devices used in inverter. In general, this problem has been solved by adjusting turn ratio of a matching transformer. However, making the transformer with high turn ratio may be not available for high power system due to its requirement for high voltage insulation. In this paper, a new configuration is proposed for parallel hybrid active filter. In the proposed hybrid active filter, the active filter is connected to the passive filter inductor in parallel through a matching transformer for the aim of reducing the size of inverter. Through computer simulations, we have shown the outstanding performances of the proposed topology.

  • PDF

A Three-Phase Parallel Active Power Filter Operating with PCC Voltage Compensation by Controlling Reactive Power (무효전력 제어에 의한 PCC전압 보상을 갖는 삼상 병렬형 능동전력필터)

  • Lee, U-Cheol;Hyeon, Dong-Seok;Lee, Taek-Gi
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.49 no.3
    • /
    • pp.211-218
    • /
    • 2000
  • The performance and dynamic characteristics of three-phase active power filter with PCC voltage compensation is presented and analyzed in this paper. The characteristics of parallel active filter are discussed when they are applied to nonlinear loads with current source and voltage source type, the characteristics of voltage compensator and comparison of two functions are discussed. The proposed scheme in this paper employs a PWM voltage-source inverter and has two operation modes. First, it operates as a conventional active filter with reactive power compensation while PCC voltage is in a certain range. Second, is operates as a voltage compensator while PCC voltage is out of range. Finally, the validity of this scheme is investigated through analysis of simulation and experimental results for a prototype active power filter system rated at 10KVA.

  • PDF

A Study on Current Harmonics Reduction and Unbalanced Source Voltage Compensation Using Series Active Power Filter and Parallel Passive Filter (직렬 능동전력필터와 병렬 수동필터를 이용한 고조파 전류 저감 및 불평형 전원 전압 보상에 관한 연구)

  • Oh, Jae-Hoon;Ko, Su-Hyun;Han, Yoon-Seok;Kim, Young-Seok
    • Proceedings of the KIEE Conference
    • /
    • 2001.10a
    • /
    • pp.196-199
    • /
    • 2001
  • This paper deals with current harmonics and unbalanced source voltages compensation using combined filter system. Filter system consists of a series active filter and parallel passive filters. Passive filters were a traditional method to compensate current harmonics, so those were installed in power system widely. The active filter can be a substitution to improve filtering characteristics and complement drawbacks of the passive filter. The combined system of the active power filter and passive filter can has a better compensation performances and economical goods. The series type active power filter injects compensation voltage into power system by transformers. It's compensation principle is able to applicate for voltage compensation. A new control algorithm for series active filter to compensate current harmonics and unbalanced source voltages is proposed. In the proposed algorithm, a compensation voltage for harmonic reduction is calculated directly by instantaneous reactive power theory, and a compensation voltage for unbalanced source voltage is calculated in based on a synchronous reference frame. By experiments, we show validity of proposed compensation method.

  • PDF

Deadbeat control of Hybrid Active Power filter using Distrubance-observer (외란관측기를 사용한 복합형능동전력필터의 Deadbeat 제어에 관한 연구)

  • 조광승
    • Proceedings of the KIPE Conference
    • /
    • 2000.07a
    • /
    • pp.123-126
    • /
    • 2000
  • When LC filter is connected parallel to the Active Power Filter a problem of the resonance between the Active Power Filter(AF) and LC filte often arises. in this paper Deadbeat control of Hybrid Active Power Filter using Disturbance-observer is introduced to solve this problem. By the estimation of the harmonics disturbance using proposed disturbance observer the compensation characteristics of the AF is improved and the resonant current is suppressed. The validity of proposed disturbance observer is verified from simulation results using PSIM

  • PDF

A Novel Control Method of Combined System consists of Series Active Power Filter and Parallel Passive Power Filter to Compensate Current Harmonics and Unbalanced Source Voltages (전류 고조파와 불평형 전원 전압을 보상하는 직렬형 능동전력 필터와 병렬형 수동전력필터 병용시스템의 새로운 제어법)

  • O, Jae-Hun;Han, Yun-Seok;Kim, Yeong-Seok;Won, Chung-Yeon;Choe, Se-Wan
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.50 no.12
    • /
    • pp.615-623
    • /
    • 2001
  • In this paper, we study a series active power filter to compensate current harmonics and unbalanced source voltages. Conventional control methods for compensating unbalanced source voltages use source voltages to calculate compensation voltages, and in addition use load voltages to regulate load voltages. But the proposed control method uses load voltage to compensate unbalanced source voltages and regulate load voltages. And we propose a control method to reduce current harmonics which can calculate compensation voltages directly from source currents and load voltages. By well-matched operation of two control methods, the series active power filter can compensate current harmonics, unbalanced source voltages, and regulate load voltages. We compose a combined system of the series active power filter and parallel passive filters to confirm a validity of proposed control methods. The results from experiments are presented to demonstrate effectiveness of the proposed method.

  • PDF

Performance Analysis of a Three-Phase Parallel Active Power Filter which Compensates PCC Voltage and the Unbalanced Loads

  • Lee, Woo-Cheol;Lee, Taeck-Kie;Hyun, Dong-Seok
    • Journal of Power Electronics
    • /
    • v.1 no.1
    • /
    • pp.9-18
    • /
    • 2001
  • The performance analysis of a three-phase parallel active power filter that compensates PCC voltage and the unbalanced loads is presented in this paper. The proposed scheme in this paper employs a PWM voltage-source inverter and has two operation modes. Firstly, it operates as a conventional active filter with reactive power compensation when PCC voltage is within the 15% voltage drop range. Secondly, it operates as a voltage compensator when PCC voltage is not within the 15% voltage drop range. And both APF and voltage compensator compensate asymmetries caused by nonlinear loads. Finally, two methods of detecting the negative sequence are reviewed, and the validity of this scheme is investigated through analysis of simulation and experimental results for a prototype active power filter system rate at 10KVA.

  • PDF

Hybrid Active Filter System for High Power Non-linear Loads (비선형 부하를 위한 복합전력필터)

  • Kang Min-Su;Rho Youn-Sung;Kim Soo-Gon;Jeon Hee-Jong
    • Proceedings of the KIPE Conference
    • /
    • 2003.07a
    • /
    • pp.182-185
    • /
    • 2003
  • Proposed Hybrid System is composed of phase leading capacitor banks, LC passive filters and active power filter. The passive power filter in parallel connection eliminate the 5th and 7th harmonics. The Variable capacitor banks correct the most of power factor, and the active power filter takes charge of remainder,

  • PDF

Three-Phase Hybrid Shunt Filters for Power Quality Improvement

  • Bhuvaneswari, G.;G.Nair, Manjula
    • Journal of Power Electronics
    • /
    • v.7 no.3
    • /
    • pp.257-264
    • /
    • 2007
  • Active power filters can be cost-effective for use in practical systems with the insertion of a few passive elements in shunt or series configuration. The resulting hybrid filters can be designed to provide dominant lower order harmonic elimination and reactive power support by the passive elements so that the burden on the active filter counterpart is reduced. In this paper, the rate reduction in the shunt active filter is estimated when it is connected in parallel with suitable passive tuned harmonic filters. The active filtering system is based on an appropriate control scheme. The simulation and the experimental results of the shunt active filter, along with the estimated value of reduction in rating, show that the hybrid shunt filtering system is quite effective in compensating for the harmonics and reactive power, in addition to being cost-effective.