• 제목/요약/키워드: PD signal

검색결과 381건 처리시간 0.028초

지중배전케이블의 PD 검출용 필터 시험 연구 (Filter Test for Partial Discharge Detection of Underground Distribution Cables)

  • 이용성;김정윤;이관우;최용성;박대희
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2005년도 하계학술대회 논문집 Vol.6
    • /
    • pp.215-216
    • /
    • 2005
  • To decrease and remove of much noises that is detected in PD (partial discharge) measuring test. we forced on detection of those. We made W-LC filter for measuring PD. which adapted that to field test. We tested after design laboratory circumstances like field line. and then the phase change properties of detected signal in UHF sensor were measured by Lemke Probe and oscilloscope (TDS-3054. Tektronix). Eventually we checked decrement of noises from experimental result. Also from experimental result at the joint box of 22.9[kV] distribution line. we obtained reasonable data which enable noises to decrease. Hereafter those results will be adapted at ultra-high voltage for trouble prevention and on-line cable watch. diagnosis of those.

  • PDF

AE Sensor를 적용한 C-GIS내의 PD 특성 (PD Characteristics in C-GIS Using AE Sensor)

  • 이용희;신양섭;장수형;서정민;이용희;임기조
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 C
    • /
    • pp.1652-1654
    • /
    • 2002
  • The defects making partial discharge(PD) in a C-GIS(Cubicle Insulated Switchgear) initiate acoustic wave which can be detected using acoustic emission sensor placed outside or inside the C-GIS enclosure. In this paper, partial discharge property for 2 locations for AE sensor and 3 locations for defects in C-GIS are presented and PD waveforms were analyzed by PRPDA(Partial Resolved Partial Discharge Analysis). As a result, using post amplifier having gain of 10,000 and band pass filter having $20kHz{\sim}300kHz$, resolution of waveforms AE sensor signal by detected was good. Noise level was about 80 mV.

  • PDF

Studies on control mechanism and performance of a novel pneumatic-driven active dynamic vibration absorber

  • Kunjie Rong;Xinghua Li;Zheng Lu;Siyuan Wu
    • Structural Engineering and Mechanics
    • /
    • 제87권2호
    • /
    • pp.117-127
    • /
    • 2023
  • To efficiently attenuate seismic responses of a structure, a novel pneumatic-driven active dynamic vibration absorber (PD-ADVA) is proposed in this study. PD-ADVA aims to realize closed-loop control using a simple and intuitive control algorithm, which takes the structure velocity response as the input signal and then outputs an inverse control force to primary structure. The corresponding active control theory and phase control mechanism of the system are studied by numerical and theoretical methods, the system's control performance and amplitude-frequency characteristics under seismic excitations are explored. The capability of the proposed active control system to cope with frequency-varying random excitation is evaluated by comparing with the optimum tuning TMD. The analysis results show that the control algorithm of PD-ADVA ensures the control force always output to the structure in the opposite direction of the velocity response, indicating that the presented system does not produce a negative effect. The phase difference between the response of uncontrolled and controlled structures is zero, while the phase difference between the control force and the harmonic excitation is π, the theoretical and numerical results demonstrate that PD-ADVA always generates beneficial control effects. The PD-ADVA can effectively mitigate the structural seismic responses, and its control performance is insensitive to amplitude. Compared with the optimum tuning TMD, PD-ADVA has better control performance and higher system stability, and will not have negative effects under seismic wave excitations.

장시간 절연체 열화실험을 위한 부분방전측정기술 연구 (A Study on the Technology Measuring Partial Discharge for Long Term Aging Experiments of Insulation Materials)

  • 선종호;김광화;박정후;조정수
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제49권12호
    • /
    • pp.665-672
    • /
    • 2000
  • This paper described the measurement technology to analyze the partial discharge characteristics for long term aging of insulations. This system was consisted of high voltage generation and measurement part, PD detection part, digital conversion and signal processing part. We used the VXI system for digital conversion and signal processing part. In the digital conversion part, we studied the error of partial discharge magnitude and memory capacity for reading digital signal with the sampling rate. In the signal processing part, we showed the program algorithm to count pulses and read peak values of partial discharge. The allowable minimum sampling rate of digizer was decided to 250kS/s through analyzing test. We confirmed that this system was very useful in the study of $\phi-q-n$ characteristics of long term PD experiments with specimens being consisted of internal void defects and CIGRE II electrodes.

  • PDF

수중음향 분석을 통한 충격신관 지연기능 시험평가 (Test and Evaluation for Time Delay Function of Point Detonating Fuze by Underwater Sound Analysis)

  • 나태흠;장요한;정지훈;김관주
    • 한국군사과학기술학회지
    • /
    • 제20권2호
    • /
    • pp.217-224
    • /
    • 2017
  • This study proposes an evaluation method for time delay function(TDF) of Point Detonation(PD) fuse using underwater explosion and water entry phenomena. Until now, nothing but the naked eyes of an observer or video images have been used to determine whether the TDF of PD fuze is operated or not. The observer has verified the performance of TDF by analysing the shape of the plume formed by underwater explosion. However, it is very difficult to evaluate the TDF of PD fuse by these conventional methods. In order to overcome this issue, we propose a method using underwater sound signal emitted from the underwater explosion of high explosive charge. The result shows that the measured sound signal is in accord with the physical phenomena of water entry of warhead as well as underwater explosion. Also, from the hypothesis test of bubble period, difference on underwater sound analysis between dud event and delay one is proved.

UWB 안테나를 이용한 MV급 전력케이블의 부분방전 측정 연구 (PD measuring on MV XLPE Calble by Using UWB Antenna)

  • 양상현;임광진;이용성;박노준;박대희
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2008년도 하계학술대회 논문집 Vol.9
    • /
    • pp.267-268
    • /
    • 2008
  • This paper presents compact low frequency ultra-wide band(UWB) sensor design and studying of the partial discharge diagnosis by sensing electromagnetic pulse emitted from the partial discharge source with new designed UWB sensor. In this study, we designed new type of compact low frequency UWB sensor based on microstrip antenna technology to detect both low frequency and high frequency band of partial discharge signal. And experiments of offline PD testing on in medium voltage (22.9kV) underground cable and mention the comparative results with the traditional HFCT as a reference sensor in the laboratory. In the series of comparative test, the calibration signal injection test provided with conventional IEC 60270 method and high voltage injection testing are included.

  • PDF

부분방전검출 신뢰도 향상을 위한 UHF 센서개선 및 성능검증 (Performance Verification and Improvement of UHF Sensor for the Increasement of the Partial Discharge Detection Reliability)

  • 김원규;김민수;백영식
    • 전기학회논문지
    • /
    • 제63권10호
    • /
    • pp.1461-1466
    • /
    • 2014
  • GIS(Gas Insulated Switchgear) is important power apparatus which have strong dielectric strength, supply electric power and is a part of the power system. Most substation type is configured as GIS. Recently, because of continuous increasement of GIS demand resulted from high quality & big capacity of electric power, the necessity of the preventive & diagnosis system is being expanded gradually. GIS partial discharge occurred on the UHF band is detected effectively by the method to IEC 60270 that recommend to be able to detect the apparent minimum discharge, 5 pC. Additionally, the UHF sensor should be installed to detect PD signal if Partial discharge signal, 5 pC occur in every part of GIS. Currently PD diagnosis system applying UHF sensor for GIS with various voltage level like 154 kV, 345 kV, 765 kV have been operated. And it is necessary to measure and analyze insulation breakdown phenomenon of inside GIS exactly. In this paper, we proposed Fat-dipole patch UHF sensor that is developed and more sensitive, excellent wide-range characteristic than the exising UHF sensor. And we performed KERI (Korea Electrotechnology Research Institute) reference test, which showed the excellent result for the all tests.

OFDM 신호의 사전 왜곡제거기를 이용한 비선형 왜곡보상 (Linearization of OFDM signal using Predistorter)

  • 신은영;방성일
    • 대한전자공학회:학술대회논문집
    • /
    • 대한전자공학회 2002년도 하계종합학술대회 논문집(1)
    • /
    • pp.339-342
    • /
    • 2002
  • In this paper, the structure of OFDM system is studied, and causes of inter carrier interference (ICI) are analyzed. Based on analysis, this paper shows a technique to prevent a distortion due to nonlinearity of high Power amplifier. The proposed scheme is a predistorter for high power amplifier linearization in orthogonal frequency division multiplexing (OFDM) system used in wireless local area network(WLAN). This is verified by comparing BER characteristics of OFDM system, between used PD and not used PD.

  • PDF

음향기술을 이용한 전력용 변압기 예방진단 (Diagonoses of Power Transformer Using Acoustic Emission Techniques)

  • 황선주;곽희로;전희종;김재철;박재완;최수안
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1992년도 하계학술대회 논문집 B
    • /
    • pp.938-941
    • /
    • 1992
  • This paper presents an acoustic emission(AE) technique using ultrasonic sensors to diagonize power transformers. Conventional methods detect and measure the electrical signal of the partial discharge(PD) of transformers in operation. The proposed techniques measures the acoustic signal generated by the partial discharge, and counts the number of the waveforms above a threshold to diagonize transformers. Experiments showed that the proposed method improved diagonosis capability over the conventional PD method.