• Title/Summary/Keyword: PD monitoring

Search Result 131, Processing Time 0.029 seconds

Asymmetric Capacitive Sensor for On-line and Real-time Partial Discharge Detection in Power Cables

  • Changhee Son;Hyewon Cheon;Hakson Lee;Daekyung Kang;Jonghoo Park
    • Journal of Sensor Science and Technology
    • /
    • v.32 no.4
    • /
    • pp.219-222
    • /
    • 2023
  • Partial discharges (PD) have long been recognized as a major contributing factor to catastrophic failures in high-power equipment. As the demand for high voltage direct current (HVDC) facilities continues to rise, the significance of on-line and real-time monitoring of PD becomes increasingly prominent. In this study, we have designed, fabricated, and characterized a highly sensitive and cost-effective PD sensor comprising a pair of copper electrodes with different arc lengths. The key advantage of our sensor is its non-invasive nature, as it can be installed at any location along the entire power cable without requiring structural modifications. In contrast, conventional PD sensors are typically limited to installation at cable terminals or insulation joint boxes, often necessitating invasive alterations. Our PD sensor demonstrates exceptional accuracy in estimating PD location, with a success rate exceeding 95% in the straight sections of the power cable and surpassing 89% in curved sections. These remarkable characteristics indicate its high potential for realtime and on-line detection of PD.

Direct and Indirect Membrane Integrity Tests for Monitoring Microbial Removal by Microfiltration (정밀여과(MF)막 미생물 제거율 모니터링을 위한 막 완전성시험)

  • Hong, Seungkwan;Miller, Frank;Taylor, James
    • Journal of Korean Society of Water and Wastewater
    • /
    • v.18 no.6
    • /
    • pp.801-806
    • /
    • 2004
  • The pilot study was conducted to (i) investigate the ability of various membrane integrity monitoring methods to detect changes in membrane integrity during operation, and (ii) determine the impact of membrane damage on microbial removal by microfiltration. Two variations of air pressure hold tests were investigated for direct integrity monitoring: pressure decay (PD) and diffusive air flow (DAF) tests which are most commonly used integrity tests for microfiltration (MF) membranes. Both PD and DAF tests were sensitive enough to detect one damaged fiber out of 66,000 under field operaing conditions. Indirect integrity monitoring such as turbidity and particle counting, however, responded poorly to defects in membrane systems. Microbial challenge study was performed using both new and deliberately damaged membranes, as well as varying the state of fouling of the membrane. This study demonstrated that MF membrane with nominal pore size $0.2{\mu}m$ was capable of removing various pathogens including coliform, spore, and cryptosporidium, at the level required by drinking water regulations, even when high operating pressures were applied. A sharp decrease in average log reduction value (LRV) was observed when one fiber was damaged, emphasizing the importance of membrane integrity in control of microbial contamination.

Usage Patterns and Incidence of Thyroid-related Adverse Events in Patients Treated with PD-1 Inhibitors (PD-1 억제제의 사용패턴 및 갑상선 관련 유해사례 발현 양상 분석)

  • Hwang, Seoyoung;Kim, Heuijae;Chung, Seonyoung;Min, Myungsook;Suh, Dong-Churl
    • Korean Journal of Clinical Pharmacy
    • /
    • v.31 no.3
    • /
    • pp.188-197
    • /
    • 2021
  • Objective: PD-1 inhibitors have demonstrated improved health outcomes in cancer patients. PD-1 inhibitors are well-tolerated and associated with immune-related adverse events. The objectives of this study are to analyze use patterns of PD-1 inhibitors in patients with cancer and to investigate the incidence of thyroid-related adverse reactions in patients treated with PD-1 inhibitors. Methods: The study included patients who had been administered PD-1 inhibitors (either nivolumab or pembrolizumab) at the Samsung Medical Center between October 1, 2016 and June 30, 2017. Data was collected from electronic medical records and tested using Mann-Whitney tests and Chi-Square tests for statistical significance. Associations between PD-1 inhibitors and incidence of adverse events were tested using Cox regression for age, gender, BMI, ECOG PS and medication. Results: Two hundred fifteen patients were identified as eligible for analyses. Thyroid-related adverse events occurred in 20% of patients (n=43). Thyroid function tests (TFTs) was performed in 109 patients (50.7%). Positive results of PD-L1 testing were found in 53.2% of the 94 patients who had the test. Approved doses of nivolumab (3 m/kg) and pembrolizumab (200 mg) were administered in 70.4% and 53% of patients, respectively. The analysis of risk factor of thyroid-related adverse reaction did not show statistically significant differences (Cox regression). Conclusion: Thyroid-related adverse events are common in patients treated with PD-1 inhibitors and hypothyroidism is the most frequent adverse reaction. Routine TFTs monitoring is strongly recommended to evaluate thyroid function in real-world clinical practice.

Prevalence of Glucose-6-Phosphate Dehydrogenase (G6PD) Deficiency among Malaria Patients in Southern Thailand: 8 Years Retrospective Study

  • Khammanee, Thunchanok;Sawangjaroen, Nongyao;Buncherd, Hansuk;Tun, Aung Win;Thanapongpichat, Supinya
    • Parasites, Hosts and Diseases
    • /
    • v.60 no.1
    • /
    • pp.15-23
    • /
    • 2022
  • Erythrocytes deficient in glucose-6-phosphate dehydrogenase (G6PD) is more susceptible to oxidative damage from free radical derived compounds. The hemolysis triggered by oxidative agents such as primaquine (PQ) is used for the radical treatment of hypnozoites of P. vivax. Testing of G6PD screening before malaria treatment is not a common practice in Thailand, which poses patients at risk of hemolysis. This retrospective study aimed to investigate the prevalence of G6PD in malaria patients who live in Southern Thailand. Eight hundred eighty-one malaria patients were collected for 8-year from 2012 to 2019, including 785 (89.1%) of P. vivax, 61 (6.9%) of P. falciparum, 27 (3.1%) of P. knowlesi, and 8 (0.9%) of mixed infections. The DiaPlexC genotyping kit (Asian type) and PCR-RFLP were employed to determine the G6PD variants. The result showed that 5 different types of G6PD variants were identified in 26 cases (2.9%); 12/26 (46.2%) had Mahidol (487G>A) and 11/26 (42.3%) had Viangchan (871G>A) variants, while the rest had Kaiping (1388G>A), Union (1360C>T), and Mediterranean (563C>T) variants. G6PD Songklanagarind (196T>A) variant was not found in the study. Our result did not show a significant difference in the malaria parasite densities in patients between G6PD-deficient and G6PD-normal groups. According to our findings, testing G6PD deficiency and monitoring the potential PQ toxicity in patients who receive PQ are highly recommended.

Comparison of Classification Rate for PD Sources using Different Classification Schemes

  • Park Seong-Hee;Lim Kee-Joe;Kang Seong-Hwa
    • Journal of Electrical Engineering and Technology
    • /
    • v.1 no.2
    • /
    • pp.257-262
    • /
    • 2006
  • Insulation failure in an electrical utility depends on the continuous stress imposed upon it. Monitoring of the insulation condition is a significant issue for safe operation of the electrical power system. In this paper, comparison of recognition rate variable classification scheme of PD (partial discharge) sources that occur within an electrical utility are studied. To acquire PD data, five defective models are made, that is, air discharge, void discharge and three types of treeinging discharge. Furthermore, these statistical distributions are applied to classify PD sources as the input data for the classification tools. ANFIS shows the highest rate, the value of which is 99% and PCA-LDA and ANFIS are superior to BP in regards to other matters.

Implementation of an Inductively Coupled EM Probe System for PD Diagnosis

  • Kim, Hee-Dong;Park, Noh-Joon;Park, Dae-Hee
    • Journal of Electrical Engineering and Technology
    • /
    • v.6 no.1
    • /
    • pp.111-118
    • /
    • 2011
  • In recent years, various types of partial discharge (PD) methods such as capacitive, inductive, electromagnetic, and acoustic coupling techniques have been developed for diagnosing rotating machines. An electromagnetic (EM) probe, which is an inductively coupled type of sensor, is required for detecting corona and internal discharges during off-line tests. In this study, a new technique for enhancing the measurement sensitivities for corona and internal discharge based on an EM inductive position sensor is proposed. An EM probe that winds wires around horseshoe-shaped and cylindershaped ferrites as helices is designed and optimized for the implementation of off-line PD monitoring of the stator winding of a rotating machine. The measurement system based on this design is implemented, and it is verified from the results of the experiment performed in this study that the probe provides similar performance as existing commercial products.

The Study on tree growth in XLPE using PD patterns (부분방전 패턴을 이용한 가교폴리에틸렌에서의 트리성장에 관한 연구)

  • Kang, Dae-Yong;Wu, Guangning;Shin, Chang-Myon;Park, Myoung-Seop;Cho, Kyu-Bock;HwangBo, Seung;Park, Dae-Hee
    • Proceedings of the KIEE Conference
    • /
    • 1998.11c
    • /
    • pp.941-943
    • /
    • 1998
  • Exploitation of equipment with cross linked polyethylene (XLPE) insulation requires its condition monitoring and diagnostic. Traditionally diagnostics of insulation is carried out by means of partial discharge detection. Many researchers have developed a lot of methods to identify the defect by the PD form. However, such identification of a defect, for example, void, inclusion or treeing, does not say about its danger from a point of view of full insulation gap breakdown and insulation construction failure. The information about the form and size of formed upon high voltage treeing is necessary for prediction of the remained resource of XLPE insulation. For this purpose we carry out experimental research for determination of the dependencies between PD characteristics in XLPE upon time and three dimension PD patterns of corresponding treeing. The investigations were carried out by means of electrical measurement of PD current and simultaneous optical recording of treeing image. Test results show that the PD patterns can be applied for detecting tree growth well.

  • PDF

Partial Discharge Signal Denoising using Adaptive Translation Invariant Wavelet Transform-Online Measurement

  • Maheswari, R.V.;Subburaj, P.;Vigneshwaran, B.;Iruthayarajan, M. Willjuice
    • Journal of Electrical Engineering and Technology
    • /
    • v.9 no.2
    • /
    • pp.695-706
    • /
    • 2014
  • Partial discharge (PD) measurements have emerged as a dominant investigative tool for condition monitoring of insulation in high voltage equipment. But the major problem behind them the PD signal is severely polluted by several noises like White noise, Random noise, Discrete Spectral Interferences (DSI) and the challenge lies with removing these noise from the onsite PD data effectively which leads to preserving the signal for feature extraction. Accordingly the paper is mainly classified into two parts. In first part the PD signal is artificially simulated and mixed with white noise. In second part the PD is measured then it is subjected to the proposed denoising techniques namely Translation Invariant Wavelet Transform (TIWT). The proposed TIWT method remains the edge of the original signal efficiently. Additionally TIWT based denoising is used to suppress Pseudo Gibbs phenomenon. In this paper an attempt has been made to review the methodology of denoising the PD signals and shows that the proposed denoising method results are better when compared to other wavelet-based approaches like Fast Fourier Transform (FFT), Discrete Wavelet Transform (DWT), by evaluating five different parameters like, Signal to noise ratio, Cross-correlation coefficient, Pulse amplitude distortion, Mean square error, Reduction in noise level.

A Quasi-Distributed Fiber-Optic Sensor System using an InGaAs PD Array and FBG Sensors for the Safety Monitoring of Electric Power Systems (InGaAs PD 어레이와 광섬유 격자를 이용한 준분배형 전력설비 안전진단 시스템)

  • Kim, Hyun-Jin;Park, Hyoung-Jun;Song, Min-Ho
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.2
    • /
    • pp.86-91
    • /
    • 2010
  • We constructed a quasi-distributed fiber-optic sensor network for the safety monitoring in power systems. It is possible to construct many of FBG sensors in a line and to be immune from electromagnetic noise. For demodulation analysis of reflected wavelength from FBG sensor, we proposed a simple and fast system using a InGaAs photo-diode array and a holographic diffraction grating. For accuracy improvement of the proposed demodulation system, we applied a Gaussian line-fitting algorithm. We obtained about 4[pm] of wavelength resolution and stability.

The Development of the Condition Monitoring Equipment for distribution Facilities by using the UHF Partial Discharge Sensors (UHF PD 센서를 이용한 배전기기 상태감시장치 개발)

  • Cho, Yong-Jun;Hwang, Chul-Min;Kim, Young-Noh;Choi, Jae-Ok;Song, Il-Keun;Lee, Byung-Sung
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.406-407
    • /
    • 2008
  • This paper is analyzed the internal type UHF partial Discharge sensors and Condition Monitoring Module that be able to monitor the condition of the distribution facilities. It set the PD cell on the inside of 22.9kV load switchgear and then it executed Partial Discharge test. it introduced the result of the test.

  • PDF