• 제목/요약/키워드: PD monitoring

검색결과 131건 처리시간 0.027초

초고압 전력기기 진단을 위한 UHF PD 센서 및 패턴분석 기술에 관한 연구 (A Study on the UHF PD Sensor and Novel Pattern Analysis Technology for Diagnosis of the High Power Apparatus)

  • 강원종;이창준;강윤식;이희철;박종화
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제53권2호
    • /
    • pp.83-90
    • /
    • 2004
  • This paper describes investigations of the UHF(Ultra High Frequency) PD(Partial Discharge) measuring technology designed for monitoring of PD in high power apparatus. Based on the spiral antenna theory, the hole type sensor for GIS with metal flange spacer and injection type sensor for oil filled transformer are developed. The experimental results show measurement characteristics of the PD sensor for several artificial defects in gas-insulated system(GIS) and oil transformer. Moreover, we proposed the new $\phi$-f-q method for the purpose of condition assessment of high power apparatus.

가스절연개폐장치용 부분방전 감시 시스템을 위한 초광대역 극초단파 신호처리장치 개발 (Development of ultra-high frequency (UHF) ultra-wide bandwidth signal processing unit for UHF partial-discharge monitoring system for gas-insulated switchgears)

  • 최재옥;김영노;이영상;강창원;박기준;구선근;윤진열;구자윤
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 C
    • /
    • pp.1963-1966
    • /
    • 2004
  • An ultra wide band ultra-high frequency (UHF) signal processing module was designed for on-line UHF partial discharge (PD) monitoring systems for gas-insulated switchgears (GIS). Major advantage of the unit is an improved PD detection sensitivity through minimizing the effect of surrounding interference signals. The detection sensitivity of the unit was <-60 dBm that is sufficient to detect UHF PD signals as low as 1 pC. Precise detection of PD occurred in the GIS, due to internal defects, is possible by using the signal processing unit.

  • PDF

다양한 절연열화 분석을 위한 카오스 분석방법 적용 연구 (A POSSIBLE APPLICATION OF CHAOTIC ANALYSIS FOR THE INVESTIGATE OF THE INSULATION DEGRADATION CAUSED BY THE VARIOUS DEFECTS)

  • 윤정훈;임윤석;구자윤
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 하계학술대회 논문집 C
    • /
    • pp.1606-1608
    • /
    • 2001
  • In connection with the monitoring of the insulation degradation of the large power apparatus, a statistical treatment, such as phase resolved partial discharge analysis (PRPDA) has been established for the on-line monitoring system during the past two decades. However, it has shown some inconveniences to distinguish the nature of the PD source in power apparatus. In this regard, a novel approach based on the chaotic analysis(CAPD) is proposed describing the fundamental ideas, outcomes and different view points from conventional PRPDA. In order to make a model for the possible defects causing sudden failures in service, several types of specimen were prepared. And partial discharge signals, originated from those samples, were measured and analyzed by means of PRPDA and CAPD respectively. In this paper, it seems that the correlation between the consecutive PD pulses depending on the nature of PD could be investigated by CAPD. Therefore, it could be considered that the nature of PD source can be distinguished more distinctively when the PRPDA is combined with CAPD.

  • PDF

다양한 결함으로부터 발생되는 절연열화를 검출하기 위한 새로운 접근기법으로써의 카오스 분석 (CHAOTIC ANALYSIS OF PARTIAL DISCHARGE (CAPD) AS A NOVEL APPROACH TO INVESTIGATE INSULATION DEGRADATION CAUSED BY THE VARIOUS DEFECTS)

  • 김성홍;박재준;임윤석;윤정훈;구자윤
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 연구회
    • /
    • pp.221-224
    • /
    • 2001
  • In connection with the monitoring of insulation degradation of large power apparatus in order to predict their unexpected service failures, a statistical treatment, such as phase resolved partial discharge analysis(PRPDA), has been established for the on-line monitoring system during the past decades. However, this method has shown some inconveniences to distinguish the nature of the PD source in power apparatus. In this regard, a novel approach based on the chaotic analysis(CAPD) is proposed describing the fundamental ideas, outcomes and different view points from conventional PRPDA. In order to make a model for the possible defects causing sudden failures in service, several types of specimen were prepared. And partial discharge signals, originated from those samples, were measured and analysed by means of PRPDA and CAPD respectively. Throughout this paper, it seems that the correlation between the consecutive PD pulses depending on the nature of PD could be investigated by CAPD. Therefore, it could be considered that the nature of PD source can be distinguished more distinctively when the PRPDA is combined with CAPD.

  • PDF

가스절연개폐장치용 부분방전 감시 시스템을 위한 초광대역 극초단파 신호처리장치 개발 (Development of ultra-high frequency (UHF) ultra-wide bandwidth signal processing unit for UHF partial-discharge monitoring system for gas-insulated switchgears)

  • 최재옥;김영노;이영상;강창원;박기준;구선근;윤진열
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 춘계학술대회 논문집 전기설비전문위원
    • /
    • pp.128-131
    • /
    • 2004
  • An ultra wide band ultra-high frequency (UHF) signal processing module was designed for on-line UHF partial discharge (PD) monitoring systems for gas-insulated switchgears (GIS). Major advantage of the unit is an improved PD detection sensitivity through minimizing the effect of surrounding interference signals. The detection sensitivity of the unit was <-60 dBm that is sufficient to detect UHF PD signals as low as 1 pC. Precise detection of PD occurred in the GIS, due to internal defects, is possible by using the signal processing unit.

  • PDF

GIS 감시진단용 다양한 센서를 적용한 PD 검출 및 패턴분석 결과 비교연구 (A Comparate Study for the PD Pattern Analysis using Different Type of Sensors Applicable to the On-line Monitoring of GIS)

  • 구자윤;장용무;최재옥;연만승;이지철
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제54권5호
    • /
    • pp.198-205
    • /
    • 2005
  • Many precedent investigations hate been made for the reliable assessment of the insulation state of large power apparatus for which partial discharge detection is one of tile plausible way. In this work, experimental investigations have been carried out to make the comparison on the PD(partial discharge) pattern analysis related to the five different types of artificial defects such as SFMP (Single Free Moving Particle), MFMP (Multi Free Moving Particle), Void, CFP (Conductor-Fixed Protrusion), EP (Enclosure Protrusion). For each PD pattern, PD detection has been done by tee different types of PD sensors such as HFCT(High Frequency Current Transformer), AE(Acoustic Emission) and UHF(Ultra High Frequency). And, in addition, frequency spectrum by the UHF sensor has been also made for each defect respectively. As a result, it is observed that the possibility of obtaining PD pattern based on PRPD(Phase Resolved Partial Discharge) in connection with the defects tinder investigation is dependant on the type of the sensor while the spectrum analysis is always successful to be achieved for every defect. Therefore, it could be suggested that the nature of PD source can be identified more distinctively when the conventional PRPDA is combined with spectrum analysis.

XLPE에서 공간전하가 PD 패턴에 미치는 영향 (Effect of Space Charge on the PD Pattern in XLPE)

  • 황보승;심재위;이진종;이동영;박대희
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 연구회
    • /
    • pp.96-100
    • /
    • 2001
  • We have measured the space charge distribution and PD patterns simultaneously in XLPE under AC voltages by modified PEA method in order to investigate the effect of space charge on PD patterns in XLPE with air-gap. From the experimental results, we found that the dynamic space charge accumulated on the surface of XLPE due to the PD dominantly affects the PD pattern in the dielectric-barrier structure and governs the voltage across the air-gap. Moreover, the space charge formed by applying DC voltage still remained after applying AC voltage, which means that the space charge formed during DC strength test is likely to be fatal to the long-time AC insulating characteristics of HV equipments. On the other hand, the PD patterns was much influenced by the pre-formed space charge by DC application. Therefore, it is possible to detect the effects of space charge by monitoring the infinitesimal change of PD patterns before and after DC strength.

  • PDF

A Method to Monitor Vacuum Degree Using Capacitive Partial Discharge Coupler

  • Sun, Jong-Ho;Youn, Young-Woo;Hwang, Don-Ha;Yi, Sang-Hwa;Kang, Dong-Sik
    • Journal of Electrical Engineering and Technology
    • /
    • 제7권6호
    • /
    • pp.959-964
    • /
    • 2012
  • Internal pressure of vacuum interrupter (VI) is one of the most important parameters in VI operation and may increase due to the outgassing from the materials inside VI or gas permeation through metal flange or ceramic vessel. The increase of the pressure above a certain level leads to the failures of switching or insulation. Therefore, an effective pressure check of VI is essential and an analysis of partial discharge (PD) characteristics is an effective monitoring method to identify the degree of the internal pressure of VI. This paper introduces a research work on monitoring the internal pressure of VI by analyzing PDs which were measured using a capacitive PD coupler. The authors have developed cost effective capacitive coupler based on the ceramic material that has an excellent insulation properties and the main component of the capacitive coupler is made by SrTiO3. Detectable internal pressure range and distinguishability of the internal pressure of VI were investigated. From the PD tests results, the internal pressure range, from $10^{-2}$ torr to 500 torr, can be monitored by PD measurements using the capacitive coupler and PD inception voltage (PDIV) follows the Paschen's law. In addition, rise time of PD pulse at 13.2kV decreases with the increase of the internal pressure of VI.

온라인 및 오프라인 PD 모니터링에 관한 연구 동향 (A Research Trend on On-Line/Off-Line PD Insulation Diagnostic System)

  • 추종훈;홍창일;최용성;이경섭
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.2008-2009
    • /
    • 2007
  • The paper considers the relation between on-line monitoring and diagnostics on the one hand and high-voltage (HV) withstand and partial discharge (PD) on-site testing on the other. HV testing supplies the basic data (fingerprints) for diagnostics. In case of warnings by on-line diagnostic systems, off-line withstand and PD testing delivers the best possible information about defects and enables the classification of the risk. Because alternating voltage (AC) is the most important test voltage, the AC generation on site is considered. Frequency tuned resonant (ACRF) test systems are best adapted to on-site conditions. They can be simply combined with PD measuring equipment. The available ACRF test systems and their application to electric power equipment -from cable systems to power transformers - is introduced.

  • PDF

GIS내부의 부분방전신호 감도개선 및 주파수변환기법에 의한 GIS UHF Sensor 모듈의 외부노이즈차폐기법에 관한 연구 (A Study of the Method for External Noise Shielding using the GIS UHF Sensor Module Applied to the Partial Discharge Signal Sensitivity and Method of Frequency Transforming in the Internal GIS)

  • 이승민
    • 전기학회논문지
    • /
    • 제59권4호
    • /
    • pp.728-732
    • /
    • 2010
  • GIS(Gas insulated switching gear) is power equipment with excellent dielectric strength and is economy merit in high confidence and stability. Recently, because equipment of GIS was occurring problem of confidence used for a long time, partial discharge on-line diagnosis systems have been importantly recognized. Partial discharge (PD) detection is an effective means for monitoring and evaluation of dielectric condition of gas insulated system (GIS). The ultra-high-frequency (UHF) PD detection technique can detect and locate the PD sources inside GIS by detecting electromagnetic wave emitted from PD source. Therefore, real-time diagnostic system using UHF detection method has been developed for this application is being expanded gradually. However, the signal of partial discharge occurring in SF6 gas is very weak and susceptible to external noises which mainly consist of PD in air. Thus, it is important to distinguish the PD in SF6 gas more sensitively from the external noises. Unfortunately, these external noise signals and the partial discharge signals have very similar characteristics. Therefore, to solve this problem, we need the signal processing method for distinguish partial discharge signals with external noise signals for improvement of SNR(signal to noise ratio) and sensitivity. In this paper, we proposed internal signal processing method for removing external noise signals with built-in pre.amplifier and frequency conversion circuit.