• Title/Summary/Keyword: PD magnitude

Search Result 104, Processing Time 0.019 seconds

Partial Discharge Characteristics on Protrusion Defects in SF6-N2 Mixture Gases (SF6-N2 혼합가스 중 돌출 결함의 부분방전 특성)

  • Jo, Hyang-Eun;Wang, Guoming;Kim, Sun-Jae;Park, Kyoung-Soo;Kil, and Gyung-Suk
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.29 no.1
    • /
    • pp.44-49
    • /
    • 2016
  • Studies on a $SF_6$-mixture and -alternative gas has been in progress to reduce the use of $SF_6$ gas as an insulation material of GIS (gas insulated switchgears). In this paper, we dealt with PD (partial discharge) characteristics in pure $SF_6$ and $N_2$, and their mixtures on aspects of insulation design and risk assessment for GIS. A POC (protrusion on conductor) and a POE (protrusion on enclosure) as the major defects were fabricated to simulate PD. We analyzed the DIV (discharge inception voltage), DEV (discharge extinction voltage), pulse magnitude, counts and phase distribution of PD pulse in $SF_6-N_2$ mixtures ($SF_6$ 100%, $SF_6$ 80%-$N_2$ 20%, $SF_6$ 50%-$N_2$ 50%, $SF_6$ 20%-$N_2$ 80%, and $N_2$ 100%) according to the IEC60270. The DIV, DEV as well as magnitude of PD pulse decreased on the POC as increase of $N_2$ ratio. For the POE, the DIV and DEV in $N_2$ ratio below 50% were the same voltages as those in $SF_6$ 100%. In this experiment, $SF_6$ 80%-$N_2$ 20% mixture could be considered with the equivalent insulation performance to a GIS.

Analysis of Insulation Condition in High Voltage Motor Stator Windings Following Cleaning and Insulation Reinforcement (세척과 절연보강에 따른 고압전동기 고정자 권선의 절연상태 분석)

  • Kim, Hee-Dong
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.25 no.6
    • /
    • pp.474-480
    • /
    • 2012
  • Diagnostic tests were performed on two high voltage(HV) motor stator windings. These tests included the measurement of insulation resistance, polarization index, AC current, dissipation factor($tan{\delta}$) and partial discharge(PD) magnitude. Surface contamination of HV motor stator windings has an effect on the AC current and $tan{\delta}$. When the stator windings were finished cleaning and insulation reinforcement, the increase rate of AC current(${\Delta}I$) and dissipation factor(${\Delta}tan{\delta}$) were very small compared to those before cleaning. However, the PD magnitude remained the same. These tests show that cleaning and insulation reinforcement of HV motor stator windings can reduce the insulation failure.

Properties of On-Line Partial Discharge in Hydrogenerator Stator Windings (수력발전기 고정자 권선의 운전중 부분방전 특성)

  • Kim, Byong-Han;Kim, Hee-Dong
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.55 no.4
    • /
    • pp.172-177
    • /
    • 2006
  • During normal machine operation, partial discharge(PD) tests were performed with partial discharge analyzer(PDA) in two hydrogenerators. Six cable couplers were installed in circuit ring bus and endwinding of three phases. PDA showed that the normalized quantity number(NQN) and the partial discharge magnitude$(Q_m)$ were very low in hydrogenerator #1 and #2, respectively. The trend analyses of NQN and $Q_m$ value are available for monitoring of the insulation condition in hydrogenerator stator windings. The insulation condition of stator winding can be assessed. Discharge at conductor surface was discovered in B phase(C2 coupler) of hydrogenerator #1. Internal discharges were generated in A and C phases(C2 coupler) of hydrogenerator #1 and in A, Band C phases(C1 and C2 couplers) of hydrogenerator #2. Slot discharges occurred in A, Band C phases(C1 coupler) of hydrogenerator #1. The stator windings of two hydrogenerators were in good condition.

Study on the characteristics of discharges caused by defects at cable joints under the accesslated aging test (접속재 결함의 가속열화에 따른 방전특성 연구)

  • Lee, Woo-Young;Sun, Jong-Ho;Ryu, Hee-Suck;Song, Il-Keun;Kim, Joo-Yong;Kim, Sang-Jun
    • Proceedings of the KIEE Conference
    • /
    • 1997.07e
    • /
    • pp.1740-1742
    • /
    • 1997
  • The trend of partial discharges(PD) magnitude which occured in a artificial void at cable joint is investigated as the function of a time. The results have shown that more than 500pC could be sustained for the considerable duration so the efficiency of monitoring a PD magnitude for diagnosing cable joints is confirmed. The other defects at cable joints are now under the same test, we can get the experimental data sooner or later.

  • PDF

Partial Discharge Property of Hydrogenerator Stator Windings (수력발전기 고정자 권선에서 부분방전 특성)

  • Kim, Hee-Dong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.05a
    • /
    • pp.86-90
    • /
    • 2000
  • Partial discharge(PD) tests were performed when the hydrogenerator(rated 11kV and 25MVA) was shut down(off-line). Six cable couplers were installed in the ring bus as well as within hydrogenerator terminal box. PD tests were conducted using partial discharge analyzer(PDA) and digital partial discharge detector(PDD). PDA showed that the normalized quantity number(NQN) and the partial discharge magnitude increased with increase of ac voltage. Slot discharges were discovered in three phases(A, B and C) at the rated voltage. PDA and PDD test results are in accordance with the pattern and magnitude of partial discharge. This hydrogenerator stator windings were in good condition.

  • PDF

Analysis of Partial Discharge Phenomena by means of CAPD (CAPD기법을 이용한 부분방전 현상 해석에 관한 연구)

  • Kim, Sung-Hong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.07b
    • /
    • pp.939-944
    • /
    • 2002
  • PD phenomena can be regarded as a deterministic dynamical process where PD should be occurred if the local electric field be reached to be sufficiently high. And thus, its mathematical model can be described by either difference equations or differential equations using several state variables obtained from the time sequential measured data of PD signals. These variables can provide rich and complex behavior of detectable time series, for which Chaos theory can be employed. In this respect, a new PD pattern recognition method is proposed and named as 'Chaotic Analysis of Partial Discharges (CAPD)' for this work. For this purpose, six types of specimen are designed and made as the models of the possible defects that may cause sudden failures of the underground power transmission cables under service, and partial discharge signals, generated from those samples, are detected and then analyzed by means of CAPD. Throughout the work, qualitative and quantitative properties related to the PD signals from different defects are analyzed by use of attractor in phase space, information dimensions ($D_0$ and D2), Lyapunov exponents and K-S entropy as well. Based on these results, it could be pointed out that the nature of defect seems to be identified more distinctively when the CAPD is combined with traditional statistical method such as PRPDA. Furthermore, the relationship between PD magnitude and the occurrence timing is investigated with a view to simulating PD phenomena.

  • PDF

Partial Discharge Characteristics in LLDPE-Natural Rubber Blends: Correlating Electrical Quantities with Surface Degradation

  • Aulia, Aulia;Ahmad, Mohd Hafizi;Abdul-Malek, Zulkurnain;Arief, Yanuar Z.;Lau, KwanYiew;Novizon, Novizon
    • Journal of Electrical Engineering and Technology
    • /
    • v.11 no.3
    • /
    • pp.699-706
    • /
    • 2016
  • Partial discharges (PD) lead to the degradation of high voltage cables and accessories. PD activities occur due to the existence of impurities, voids, contaminants, defects and protrusions during the manufacture and installation of power cables. Commonly, insulation failures occur at cable joints and terminations, caused by inhomogeneous electric field distributions. In this work, a blend of natural rubber (NR) and linear low density polyethylene (LLDPE) was investigated, and the optimal formulation of the blend that could resist PD was discussed. The experiments were conducted under a constant high voltage stress test of 6.5 kV AC and the magnitude of partial discharge activities was recorded using the CIGRE method II. Pattern analysis of PD signals was performed along with the interpretation of morphological changes. The results showed that the addition of 10 wt% of NR and 5 wt% of Alumina Trihydrate (ATH) provided promising results in resisting PD activities. However, as the NR content increased, more micropores existed, thus resulting in increased PD activities within the samples.

Partial Discharge Measurements of High Voltage Rotating Machine Stator Windings (고압회전기 고정자 권선의 부분방전 측정)

  • Kim, Hee-Dong;Lee, Young-Jun;Kong, Tae-Sik
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1828-1830
    • /
    • 2003
  • Partial discharge(PD) tests are used to evaluate the insulation condition of stator windings in two 4.16kV and three 6.6kV motors. These tests were conducted using a conventional partial discharge detector(PDD) and turbine generator analyzer(TGA). Off-line PD measurements were performed on five high voltage motors. PD magnitudes ranged from 1000 pC to 5400 pC at the normal line-to-ground voltage. Five high voltage motors have been equipped with 80pF epoxy-mica coupler on the motor terminal box. The PD pulse from sensors were measured with the TGA instrument. TGA summarizes each plot with two Quantities such as the peak PD magnitude(Qm) and the total PD activity(NQN). The defect mechanisms of high voltage motor can be associated with PD patterns such as internal, slot and conductor surface discharges. The PDD and TGA test results of No. 4 motor showed that internal discharge was detected in voids of the groundwall insulation.

  • PDF

Development of On-Line Monitoring System for Pumped Storage Generator/Motor (양수발전소 발전-전동기 운전중 감시 시스템의 개발)

  • 김희동;주영호
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.53 no.3
    • /
    • pp.168-174
    • /
    • 2004
  • On-line monitoring system(OMS) has been developed for the pumped storage generator/motor The OMS is applied to diagnosis of the PD(partial discharge) activity of stator insulation, the shorted-turn of rotor winding and the variation of the air-gap between stator and rotor. The OMS consists of DAS(data acquisition system), main server system, gateway and display PC. The DAS measures the PD, the shorted-turn and air-gap from three sensors installed on the generator/motor. The gateway controls the data which sent by DAS. The main server system saves the data, analyzes the data and conducts the diagnostic algorithm. The display PC shows the diagnostic results of partial discharge, shorted-turn and air-gap. Field tests were conducted using PDA(partial discharge analyzer). The results of the OMS and PDA measurements can be directly correlated with normalized quantity number(NQN), PD magnitude(Qm) and PD pattern.

Feature Extraction for Fault Signals of High Voltage Motor Stator Windings (고압전동기 결함신호의 특징추출에 관한 연구)

  • Park, Jae-Jun;Kim, Hee-Dong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.07b
    • /
    • pp.1154-1157
    • /
    • 2004
  • During normal machine operation, partial discharge(PD) measurements were performed with turbine generator analyzer(TGA) in imitation stator winding of high voltage motors. The motor was energized to 4.47kV, 6.67, respectively. Applied voltage to Imitation winding was used two voltage level, 4.47[KV]and 6.67[KV]. Motors having imitation stator winding were installed with 80pF capacitive couplers at the terminal box Case of PD Pattern regarding applied voltage phase angel, the PD patterns were displayed two dimensional and three dimensional. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). As the result, we could discrimidate using TGA the difference of internal and surface discharge for imitation stator winding. We have used the other technique, in order to feature extraction of faulty signals on stator winding, Daubechies Discrete wavelet transform and Harmonics analysis(FFT) about faulty signals.

  • PDF