• 제목/요약/키워드: PD(Partial discharge) sensor

검색결과 135건 처리시간 0.023초

초고주파 광대역 부분방전 센서를 내장한 지능형 스페이서 개발 (A development of intelligent spacer built in the Internal type UHF partial discharge sensor)

  • 김동석;황철민;김영노;최재옥;서왕벽;한봉수;최수헌
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 Techno-Fair 및 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.163-164
    • /
    • 2007
  • In this study, we developed intelligent spacer built in the internal type UHF PD sensors. 3-Dimensional electro-magnetic simulations were performed to analyze electric-field distribution of the single-phase GIS and three-phase GIS. After considering the spacer's specification, Sensor structures were designed and analyzed using the 3-D EM Simulator. As a result of the simulation the internal type UHF PD sensors were built in. Performance of the sensor built into real scale GIS spacer was measured in terms of return loss and detected Max voltage. And we identified a character of the intelligent spacer by using 5pC partial discharge ceil.

  • PDF

XLPE 케이블의 PD 검출 필터 시험 (Filter Test for Detecting Partial Discharge in XLPE Cable)

  • 조재철;최용성
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 추계학술대회 논문집 전기설비전문위원
    • /
    • pp.218-221
    • /
    • 2008
  • Due to a variable noises in the field underground lines, clear technology of noises is very important in the diagnosis technology of partial discharge. Therefore we progressed filter test to improve the measuring test of partial discharge in a field. We applied to field test after making W-LC filter for partial discharge measurement, and then designed experimental environment such as under- ground distribution lines of field. Measuring sensor for test was UHF sensor. And we analysed those using the Lemke Probe and oscilloscope (TDS-3054, Tektro- nix). Finally, we obtained excellent data of noise decrement in the joint box of 22.9[kV] distribution lines from above experiment.

  • PDF

XLPE 케이블의 PD 검출 필터 시험 (Filter Test for Detecting Partial Discharge in XLPE Cable)

  • 김대열;윤주호;최용성;박대희;이경섭
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 춘계학술대회 논문집 전기설비전문위원
    • /
    • pp.72-74
    • /
    • 2007
  • Due to a variable noises in the field underground lines, clear technology of noises is very important in the diagnosis technology of partial discharge. Therefore we progressed filter test to improve the measuring test of partial discharge in a field. We applied to field test after making W-LC filter for partial discharge measurement, and then designed experimental environment such as underground distribution lines of field. Measuring sensor for test was UHF sensor. And we analysed those using the Lemke Probe and oscilloscope (TDS-3054, Tektronix). Finally, we obtained excellent data of noise decrement in the joint box of 22.9[kV] distribution lines from above experiment.

  • PDF

22.9kV XLPE 케이블 PD 검출용 필터 시험 (Filter Test for Detecting Partial Discharge in 22.9kV XLPE Cable)

  • 이용성;김정윤;김석종;이경용;최용성;박대희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 C
    • /
    • pp.2277-2279
    • /
    • 2005
  • Due to a variable noises in the field underground lines, clear technology of noises is very important in the diagnosis technology of partial discharge. Therefore we progressed filter test to improve the measuring test of partial discharge in a field. We applied to field test after making W-LC filter for partial discharge measurement, and then designed experimental environment such as under-ground distribution lines of field. Measuring sensor for test was UHF sensor. And we analysed those using the Lemke Probe and oscilloscope (TDS-3054, Tektronix). Finally, we obtained excellent data of noise decrement in the joint box of 22.9[kV] distribution lines from above experiment.

  • PDF

SF6 가스절연에서 부분방전의 특성분석 (Analysis of Partial Discharge Characteristics in SF6 Gas Insulation)

  • 김선재;왕국명;박서준;길경석;안창환
    • 한국전기전자재료학회논문지
    • /
    • 제29권7호
    • /
    • pp.429-434
    • /
    • 2016
  • This paper deals with the characteristics of partial discharge (PD) for the purpose of a condition based maintenance (CBM) of gas insulated switchgears (GIS) in power equipment. Four types of electrode systems such as a protrusion on enclosure (POE), a particle on spacer (POS), a free particle (FP) and a Floating were designed and fabricated. PD pulses were measured using UHF sensor with a frequency range of 300 MHz~1.4 GHz and a DAQ with a sampling rate of 250 MS/s. Discharge inception voltage (DIV), discharge extinction voltage (DEV), and phase resolved partial discharge (PRPD) were analyzed depending on electrode systems. The average DIV in the POS was 28.8 kV. It was about 1.7 times higher than that in the FP, which was the lowest value of 17.2 kV. The FP shuffled and jumped at the applied voltage of 23.5 kV. Over 95% of PD pulses in the POE were generated in the negative polarity ($181^{\circ}{\sim}360^{\circ}$) of applied voltage. The results showed the phase (${\Phi}$)-magnitude (dBm) of PD pulses by UHF sensor, a cluster was formed separately depending on electrode systems.

고압 회전기 On-line 부분방전 측정용 Ceramic Coupler 특성 (Characteristics of Ceramic Coupler for On-line Partial Discharge Measurement in High Voltage Rotating Machines)

  • 강동식;윤대희;김용주;이홍식;윤영호;박정후
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제51권5호
    • /
    • pp.204-212
    • /
    • 2002
  • In order to improve the reliability of high voltage rotating machines, it is necessary to understand the breakdown mechanism of stator windings. Especially partial discharge(PD) inception and growth are important in stator winding insulation. Recently, many research on the diagnosis of stator winding insulation for large rotating machines have been developed since the 1970s. Capacitive couplers have been the most widely used sensor for on-line partial discharge detection in rotating machines. This paper deals with the electrical on-line monitor characteristics of ceramic coupler(CC) which has been developed to continuously measure the PD activity in operating high voltage motor stator windings on site. We investigated the electrical characteristics(PD quantity, breakdown voltage and frequency response) to develop CC. This paper presents frequency characteristics and laboratory test result to compare conventional 80([F] epoxy-mica coupler(EMC) and 105[pF] CC for PD measurement with 6.6㎸ model stator windings.

웨이블렛 변환을 이용한 부분 방전 신호 분석 (An Analysis of Partial Discharge signal Using Wavelet Transforms)

  • 박재준;장진강;임윤석;심종탁;김재환
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1999년도 춘계학술대회 논문집
    • /
    • pp.169-172
    • /
    • 1999
  • Recently, the wavelet transform has been a new and powerful tool for signal processing. It is more suitable specially for the feature extraction and detection of non-stationary signals than traditional methods such as, the Fourier Transform(FT), the Fast Fourier Transform(FFT) and the Least Square Method etc. because of the characteristic of the multi-scale analysis and time-frequency domain localization. The wavelet transform has been developed for the analysis of PD pulse signal to raise in the progress of insulation degradation. In this paper, the wavelet transform was applied to one foundational method for feature extraction. For the obtain experimental data, a computer-aided partial discharge measurement system with a single acoustic sensor was used. If we are applying to the neural network method the accumulated data through the extracted feature, it is expected that we can detect the PD pulse signal in the insulation materials on the on-line.

  • PDF

EMTP를 이용한 GIS내 부분방전 펄스의 감쇠특성 해석 (Analysis of Partial Discharge Pulse Damping Characteristics in GIS Using EMTP)

  • 이도훈;김재철;송승엽;신중은;노광현;김광화
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2003년도 학술대회논문집
    • /
    • pp.103-105
    • /
    • 2003
  • The principle of the ultra-high frequency (UHF) method to detect partial discharge(PD) in GIS is to measure the UHF electromagnetic waves excited by PD pulses. Such electromagnetic waves propagate along the GIS busbar in the TEM-mode, TE-mode, TM-mode. And the coaxial busbar of the GIS acts as a waveguide in which the UHF electromagnetic waves travel. This paper was studied the analysis on damping characteristic of electromagnetic waves excited by PD in GIS and presented the method to yield the cutoff frequency for determine the minimum band of sensor that detect the PD pulse.

  • PDF

고압 전동기 고정자 권선의 절연진단을 위한 운전중 부분방전 측정 시스템 개발 (Development of On-Line Partial Discharge Measuring System for Insulation Diagnosis of High-Voltage Motor Stator Windings)

  • 황돈하;강동식;신병철;이영진;이광식
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2006년도 춘계학술대회 논문집
    • /
    • pp.481-486
    • /
    • 2006
  • In this paper, a new on-line high-voltage motor monitoring system is proposed. This system monitors the insulation condition of the stator winding by on-line measurements of partial discharge (PD). And this system displays magnitude and phase angle distribution of PD. Sensor, CC (Ceramic Coupler) is used for PD measurement. PD signals are continuously measured and digitized with a A/D converter to build the database of the high-voltage motor's insulation condition. Also, this system can communicate with the central monitoring system via RS-232, 422, and TCP/IP. This helps more efficient operation and maintenance of the high-voltage motor.

  • PDF

지중배전케이블의 PD 검출용 필터 시험 연구 (Filter Test for Partial Discharge Detection of Underground Distribution Cables)

  • 이용성;김정윤;이관우;최용성;박대희
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2005년도 하계학술대회 논문집 Vol.6
    • /
    • pp.215-216
    • /
    • 2005
  • To decrease and remove of much noises that is detected in PD (partial discharge) measuring test. we forced on detection of those. We made W-LC filter for measuring PD. which adapted that to field test. We tested after design laboratory circumstances like field line. and then the phase change properties of detected signal in UHF sensor were measured by Lemke Probe and oscilloscope (TDS-3054. Tektronix). Eventually we checked decrement of noises from experimental result. Also from experimental result at the joint box of 22.9[kV] distribution line. we obtained reasonable data which enable noises to decrease. Hereafter those results will be adapted at ultra-high voltage for trouble prevention and on-line cable watch. diagnosis of those.

  • PDF