Characteristic of fatigue properties with tension and bending loading using high strength steel wire (고강도 강선의 인장 및 회전굽힘 피로특성)

  • Woo, Byung-Chul;Kim, Sang-Soo;Kim, Byung-Guel;Suh, Chang-Min
    • Proceedings of the KSME Conference
    • /
    • 2000.11a
    • /
    • pp.274-279
    • /
    • 2000
  • The overhead transmission wires operating both at warm temperature and tighten state for a long period of time in a power transmission plant are degraded by air pollution, wind, creep and slip between steel wire and aluminium conductor. The objective of this study is to investigate a high carbon steel wire. We tested for basic mechanical properties and 3 types fatigue behavior, tension-tension, 4 points bending and 3 points bending fatigues. In this study, a conventional fatigue strengths between 4 points bending and tension-tension fatigue were determined by Gerber, Sorderberg and Goodman's theory and we investigated S-N diagram for bending and tensile loading.

  • PDF

Optimum Locations of Passe Conductor Loops for Magnetic Field Mitigation of Transmission Line using GA (유전 알고리듬을 이용한 송전선로 자계 저감용 도체루프의 최적 위치 선정)

  • Shin Myong-Chul;Kim Jong-Hyung
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.54 no.5
    • /
    • pp.234-241
    • /
    • 2005
  • The performance of passive conductor loop (hereinafter 'loop') method which is used to mitigate the magnetic field around overhead power transmission line is dependent on its configuration and installed location, which are affected by installation conditions of the loops such as objective areas and levels of magnetic field mitigation. Thus, because the design problem of loops is difficult and cumbersome by variety of their configuration and complexity of magnetic coupling mechanism, it is need to be formulated as a computer-based optimum problem to determine the most effective and reasonable loop model satisfying the installation conditions. In this paper, the optimum locations of the multi-wired multiple loops including series reactance compensations are searched by using the genetic algorithm (GA) to mitigate effectively the magnetic fields of relatively near points or far points from transmission line at Am height, and the magnetic fields mitigation characteristics of each loop are analyzed in the view of magnitude, direction and phase of cancellation fields by polarized vector concept to identify their adequacy and rationality for the installation objectives.

Study on Thermal Load Capacity of Transmission Line Based on IEEE Standard

  • Song, Fan;Wang, Yanling;Zhao, Lei;Qin, Kun;Liang, Likai;Yin, Zhijun;Tao, Weihua
    • Journal of Information Processing Systems
    • /
    • v.15 no.3
    • /
    • pp.464-477
    • /
    • 2019
  • With the sustained and rapid development of new energy sources, the demand for electric energy is increasing day by day. However, China's energy distribution is not balanced, and the construction of transmission lines is in a serious lag behind the improvement of generating capacity. So there is an urgent need to increase the utilization of transmission capacity. The transmission capacity is mainly limited by the maximum allowable operating temperature of conductor. At present, the evaluation of transmission capacity mostly adopts the static thermal rating (STR) method under severe environment. Dynamic thermal rating (DTR) technique can improve the utilization of transmission capacity to a certain extent. In this paper, the meteorological parameters affecting the conductor temperature are analyzed with the IEEE standard thermal equivalent equation of overhead transmission lines, and the real load capacity of 220 kV transmission line is calculated with 7-year actual meteorological data in Weihai. Finally, the thermal load capacity of DTR relative to STR under given confidence is analyzed. By identifying the key parameters that affect the thermal rating and analyzing the relevant environmental parameters that affect the conductor temperature, this paper provides a theoretical basis for the wind power grid integration and grid intelligence. The results show that the thermal load potential of transmission lines can be effectively excavated by DTR, which provides a theoretical basis for improving the absorptive capacity of power grid.

Study on Tension and Thermal Properties of Corrosive-fractured Steel Sleeve (강 슬리브 파단 직선 슬리브의 장력 및 열적 특성 분석 연구)

  • Ahn, Sang-Hyun;Kim, Byung-Geol;Kim, Sang-Shu;Sohn, Hong-Kwan;Kim, In-Pyo;Kim, Sung-Kyu
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.21 no.11
    • /
    • pp.1036-1041
    • /
    • 2008
  • According to previous report, aged sleeves of old transmission line showed several defaulted installation patterns, which was biased or corrosive-fractured of steel sleeve installed cases. These defects can cause serious accidents such as rapid increasing of sag or falling out of overhead conductor from sleeves. Consequently, the defects lead to the major power outage. Corrosion of steel sleeve is a typical defect by aging of sleeves. And it occupied almost 25 percent of investigated aged sleeves. This paper studied thermal properties and tension for ACSR conductor in case of fractured steel sleeve model by corrosion. The temperature distribution within overhead conductor has a specific gradient. Thermal properties of splice connectors(sleeve and clamp) showed normal behavior. However, mechanical properties were worse than normal sleeves. The detailed results were presented in the text.

Ion Effects of HVDC ±500 kV Double Bipole Overhead Transmission Line with Metallic Return Conductor Using Full-scale Test Line (실증시험선로를 이용한 도체귀로형 HVDC ±500 kV Double Bipole 가공송전선로의 이온류 특성 평가)

  • Shin, Kooyong;Kwon, Gumin;Ju, Munno;Woo, Jeong Min
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.5 no.4
    • /
    • pp.249-256
    • /
    • 2019
  • A full-scale test line was established to verify the electrical environmental interferences caused by the HVDC ±500 kV Double Bipole overhead transmission line with metallic return conductor, which is scheduled for construction in Korea and the fullscale test was conducted for one year. And through the human perception test of the DC electric-field under the HVDC Double Bipole line, the threshold value at which the human detects DC electric field was investigated to verify the validity of the design guide for the HVDC ±500 kV Double Bipole overhead transmission line. The polarity configuration of the HVDC ±500 kV Double Bipole test line was arranged diagonally with the same polarity in terms of the electrical environment disturbance and operation. The test line utilized the 6-bundle arrangement to prevent the corona discharge taking into account the domestic social acceptability. The test results show that the HVDC ±500 kV Double Bipole transmission line generated very little corona discharge from the conductors. Therefore, both DC electric field and ion current density met the domestic design guide for DC overhead transmission lines. Also, the human perception test of DC electric fields under the test line showed that 70% of participants did not recognize the DC electric field even when exposed to 23 kV/m.

The Study on Tension and Thermal Properties of Baised Installed Sleeve (편중 시공된 직선 슬리브의 장력 및 열적 특성 분석 연구)

  • Ahn, Sang-Hyun;Kim, Byung-Geol;Kim, Sang-Shu;Shon, Hong-Kwan;Park, In-Pyo;Kim, Sung-Kyu
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.1209-1210
    • /
    • 2008
  • According to previous report, aged sleeves for old transmission lines have variable defects such as biased installed case or corrosion of steel sleeve. Biased installed sleeve occupied 20 percent among the investigated aged sleeves. This defect must cause local heating of splice connector and limit power transmission capacity. It even inspire falling out of overhead conductor from sleeves. This paper studies thermal properties and tension for ACSR conductor in case of biased installed sleeve model. The detailed results were presented in the text.

  • PDF

Aerodynamic Characteristics and Galloping Possibility of Ice Accreted Transmission Conductors by Wind Tunnel Tests (풍동실험을 통한 착빙 가공송전선의 공력 특성 측정 및 갤러핑 발생 분석)

  • Lee, Dooyoung;Goo, Jaeryang;Park, Sooman;Kim, Donghwan
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.3 no.2
    • /
    • pp.79-88
    • /
    • 2017
  • In this paper, the wind tunnel test for the measurement of aerodynamic characteristics of transmission conductors with asymmetric sections is described. A single conductor model and bundled conductor models with ice accreted shapes are tested both in steady and turbulent flow, and the aerodynamic coefficients are acquired. Transmission conductor galloping is a kind of wind-induced vibration which is characterized by primarily vertical oscillation with a very low frequency and a high amplitude. It is well known that transmission conductor galloping is generally caused by moderately strong, steady winds when a transmission conductor has an asymmetric cross-section shaped by accreted ice. Galloping should be considered from the design stage of overhead lines because it can cause severe wear and fatigue damage to attachments as well as transmission conductors. It is reported that there have been normally 20 events of galloping per year in Korea, which may be followed by serious consequences in the electric power system. Therefore, this research is performed to measure aerodynamic characteristics of ice accreted transmission conductors to understand and control transmission conductor galloping so that it would help to prevent unexpected failures and reduce the maintenance costs caused by galloping.

Development of Modular Scaffold for Overhead Transmission Line Wiring Work (송전선로 가선공사용 모듈형 발받침 개발)

  • Min, Byeong-Wook;Baik, Seung-Do;Kang, Dae-Eon;Bang, Hang-Kwon;Choi, Jin-Sung;Baek, Soo-Gon
    • Proceedings of the KIEE Conference
    • /
    • 2006.07a
    • /
    • pp.450-451
    • /
    • 2006
  • The method of conductor wiring is that a messenger wire is installed, the end of the wire is connected to the conductor and a engine puller pulls the conductor. The length of one section of wiring is $3{\sim}5km$ and one group messenger wire pulls simultaneously $2{\sim}4$ group conductor, while a tensioner maintains wiring tension to prevent the deflection of the conductor. However, there are many obstacles such as roads, power lines, communication lines, buildings, farms and crops. Therefore to prevent damage from conductor deflection a staging is used. The currently used staging is scaffolding lumber which is difficult to secure and it's construction efficiency is very low because it requires a lot of time and manpower. So this study developed a insulating defense tube and pipe connecting device, and a truss structure fabrication module using steel pipe which reduces construction time and cost through a compressive and dielectric strength test.

  • PDF

Application and Evaluation of Emergency Rates in Overhead Transmission Lines (가공송전선로의 비상용량 응용과 평가)

  • Kim, Sung Duck
    • Journal of IKEEE
    • /
    • v.18 no.4
    • /
    • pp.442-446
    • /
    • 2014
  • A method for applying emergency ratings to improve the reliability of power supply in ACSR overhead transmission lines is described in this paper. Due to re-regulate power industry, most power companies worldwide as well KEPCO have been searching for only economical strategies without new investment. Power demand was rapidly increasing, however, generation amount did not follow sufficiently. Hence in order to increase the transmission capacity for the existing transmission lines in case of peak load, or contingency in transmission lines, an application method of emergency ratings such as short or long term rating is proposed. If applying long term emergency rating instead of static line rating for the period of a peak load, power transmission can be increased to 10 % or more. Furthermore, it was shown that emergency rating can be effectively used in the contingency of double-circuit transmission lines and/or overload cases.

An Evaluation Method for Short-Term Ratings of Double-Circuit Overhead Transmission Lines (2회선 가공송전선의 단시간정격에 관한 평가방법)

  • Kim, Sung-Duck;Sohn, Hong-Kwan;Jang, Tae-In
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.7
    • /
    • pp.20-28
    • /
    • 2007
  • This paper describes an analytical method to determine the short-term ratings to reliably operate the overhead transmission lines with double-circuit lines when faulting one circuit of the two. As linearizing the thermal equilibrium equation that represents the temperature characteristic of conductors, we show that the linear equation can be easily represented the over-current and it's temperature property during overloading the one line. Generally, it is well hewn that the short-term line ratings should be determined by considering both conductor life and dip. However, most power companies have their own different guides for the short-term ratings. Using the suggested method in this paper, it can be re-accessed the short-term ratings given in Kepco's overhead transmission lines constructed during the past three different periods. As a result, it is verified that the short-term ratings could be increased mil efficiently. Furthermore, it would be directly applied the given method to determine the short-term dynamic line ratings when occurring faults in one of the double-circuit lines, without doing my other actions for the current lines.