변속실외기펜을 사용한 텐텀형냉방기의 과열도제어에 관한 연구 (A Study on the Superheat Control of a Tandem-type Airconditioner by Using a Variable Speed Outdoor Fan)

  • 김재현;한도영
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2005년도 동계학술발표대회 논문집
    • /
    • pp.474-479
    • /
    • 2005
  • For the safe operation of an air conditioner, the liquid car η 'over to compressors should be minimized and compressors should be operated in the specified region of suction and discharge pressures recommended by compressor manufactures. In this study, a capillary assisted tandem-type airconditioner was considered. A variable speed outdoor fan was used to control operating points of the system. Test results showed the possibilities to move system operating points to the safe region by controlling the speed of an outdoor fan.

  • PDF

고온냉매 우회방법을 적용한 열펌프의 성능 개선 연구 (A Study on Performance Improvement of Heat Pump Adopting the Hot Gas Bypass Method)

  • 강신형;변주석
    • 에너지공학
    • /
    • 제15권4호
    • /
    • pp.235-242
    • /
    • 2006
  • 본 연구는 공기 열원 열펌프의 성능 향상을 위한 연구로써 제상 방법으로 고온냉매 우회방법을 사용하고 내부열교환기를 장착한 열펌프 시스템의 성능을 ISO5151의 표준제상 조건에서 실험하였다. 실험은 고온냉매 우회방법과 가장 일반적인 제상 방법인 시간주기 제상방법을 비교하였으며 착상 발생 후 압축기 출구의 고온냉매를 실외기 입구로 우회시킬 때 실외기 홴 속도를 정상속도에 대하여 0%, 30%, 60%, 90%로 변화 시키면서 열펌프의 성능변화를 관찰하였다. 연구결과 210분의 열펌프 가동시간 동안 고온냉매 우회방법은 시간주기 제상방법 보다 $2.2{\sim}6%$ 높은 평균 성능계수를 나타냈으며 고온냉매 우회방법에서는 실외기의 홴 속도가 60%일 때 가장 좋은 성능계수와 난방용량을 나타냈다.

부분부하 조건에서 히트펌프의 운전변수 최적화를 통한 냉방계절성능(SEER) 향상에 관한 실험적 연구 (An Experimental Study on the Performance Improvement of the Seasonal Energy Efficiency Ratio(SEER) of a Heat Pump by Optimizing Operating Parameters under Partial Load Conditions)

  • 최성경;이상헌;김선재;김용찬
    • 설비공학논문집
    • /
    • 제29권3호
    • /
    • pp.111-118
    • /
    • 2017
  • Performance factors such as the EER(Energy Efficiency Ratio) and the COP (Coefficient of Performance) are being replaced by seasonal energy efficiency factors, like the SEER (Seasonal EER) and the SCOP (Seasonal COP) to evaluate the performance of a heat pump by the time of the year. Seasonal performance factors, such as the CSPF (Cooling Seasonal Performance Factor) and the HSPF (Heating Seasonal Performance Factor) are used to describe the heat pump's performance during the cool and hot seasons. In this study, the optimization of all heat pump's operating parameters was experimentally conducted to enhance the SEER based on the EU standard (EN 14825). Moreover, the SEER was improved by the compressor frequency, as well as indoor and outdoor fan speeds. In addition, the performance characteristics of the heat pump were studied under partial load conditions. As a result, the SEER was enhanced by 17% when the compressor frequency was optimized. An additional 2% improvement was achievable with the optimization of indoor and outdoor fan speeds.

상업용 냉장고의 상황 감지를 위한 인버터형 실외기 신호 분석 (Signal Analysis of Inverter-Type Outdoor Unit for Detecting Operation Changes of Commercial Refrigerator)

  • 임효준;이주경;황준현;이경창;이석
    • 한국정밀공학회지
    • /
    • 제33권6호
    • /
    • pp.517-523
    • /
    • 2016
  • Unlike household refrigerators, commercial refrigerators are composed of separate indoor and outdoor units. The outdoor unit of most commercial refrigerators is designed to run at a fixed speed, which results in low energy efficiency and loud fan noise. Moreover, it cannot respond flexibly to changing thermal load in the indoor unit. Inverter type outdoor units can address such problems through speed changes based on information obtained from the indoor unit. However, using two units from different manufacturers is often not a viable solution. If condition changes in the indoor unit can be detected without communication between the two units, it is possible to adjust the speed of the outdoor unit. This paper attempts to analyze the signal from the outdoor unit when the condition of the indoor unit changes by varying the thermal load.

변풍량 공조시스템의 요구외기량 확보를 위한 제어방식 (Control Methods of the VAV Air Handling Unit for the Required Outdoor Air Demand)

  • 한도영;주영덕;김진;이준호
    • 설비공학논문집
    • /
    • 제15권3호
    • /
    • pp.203-209
    • /
    • 2003
  • Control algorithms of an air handling unit by using the mixing box plenum pressures were developed and verified by experiments. Control algorithms developed for this study were the setpoint algorithms for the outdoor damper position, the outdoor/fixed plenum pressure, and the return/exhaust plenum pressure. The outdoor/fixed plenum pressure setpoint was used to control the bypass damper position, and the return/exhaust plenum pressure setpoint was used to control the return fan speed. Experimental results showed the good control of the required outdoor air demand. Therefore, setpoint algorithms developed for this study may effectively be applied for the control of the VAV air handling unit.

국내 아파트의 미세먼지 유입 특성 (Infiltration Characteristics of Particulate Matter at a Korean Apartment House)

  • 주상우;지준호
    • 한국입자에어로졸학회지
    • /
    • 제15권4호
    • /
    • pp.149-157
    • /
    • 2019
  • Infiltration characteristics of airborne particulate matter had been investigated in real-life for about 90 days over 2 years in a Korean apartment building where a 3-person household had lived and the exclusive private area was 84.9 ㎡. Airtightness was measured by fan depressurization, and the ACH50 was 2.41 times per hour. In and outdoor particle concentrations were measured by optical particle counters. Infiltration factors and filtration efficiencies of the house, which reflect the removal of outdoor particles penetrating building envelope and the deposition inside a building, were obtained from data screened based on an empirical evaluation process. Infiltration factor of fine particles showed a range from about 42% at 0.4 m/s of wind speed to 72% at 4.2 m/s of wind speed with closed windows and doors. Filtration efficiency was like a MERV 13 grade filter with an open window outside at a balcony at low outdoor wind speed under 1 m/s. The grade decreased to MERV 11 by opening another outside window at the other balcony. Filtration efficiencies decreased as much as 29% in average at a range of 0.3~2.5 ㎛.

외부부하에 의해 회전중인 표면부착형 영구자석동기전동기의 센서리스 제어 알고리즘 (Sensorless Control Algorithm of a Surface Mounted PM Synchronous Motor Under Naturally Rotating by Load)

  • 이한솔;조관열;김학원
    • 전력전자학회논문지
    • /
    • 제23권1호
    • /
    • pp.16-23
    • /
    • 2018
  • PM synchronous motor may be rotated to an arbitrary direction and speed by outside wind under natural condition in cases where the fan is applied outside, such as in vehicle radiators and outdoor air-conditioners. Sensorless controls that cannot detect rotor position requires additional sensorless control algorithm because a rotor is rotated by an external load. In this study, the sensorless control of a PM synchronous motor under naturally rotating condition is proposed. The natural rotation conditions are classified as forward high-speed rotation, reverse high-speed rotation, and low-speed rotation. Experiment results verify the performance of the sensorless control, including the rotor speed and position detection at natural rotation mode and switch to the closed-loop sensorless control.

제어 알고리즘 개발을 위한 GHP 냉방모드 동특성 모델링 (Dynamics modeling of a GHP in cooling mode for development of control algorithm)

  • 신영기;김영일
    • 설비공학논문집
    • /
    • 제17권3호
    • /
    • pp.243-249
    • /
    • 2005
  • The present study has been conducted to simulate dynamics of a gas engine-driven heat pump(GHP) for design of control algorithm. The dynamic modeling of a GHP was based on conservation laws of mass and energy. For automatic control of refrigerant pressures, actuators such as engine speed, outdoor fan, coolant three-way valves and liquid injection valve were PI or P controlled. The simulation results showed physical behavior that is realistic enough to apply for control algorithm design.

온수배관을 이용한 온실의 난방성능 (Heating Performance of Hot Water Supplying System in Greenhouse)

  • 윤용철;신익수;김현태;배승범;최진식;서원명
    • 생물환경조절학회지
    • /
    • 제21권2호
    • /
    • pp.79-87
    • /
    • 2012
  • 본 연구는 온실의 난방 에너지 절감을 목적으로 온실 내부에 알루미늄 온수배관을 설치하여 난방효과에 대한 기초자료를 구축하고자 수행되었다. 그 연구결과를 요약하면 다음과 같다. 전체 실험을 포함하여 온실내의 높이별 온도편차는 4.0~$7.0^{\circ}C$ 정도의 범위로서 그 차이가 크게 나타났다. 팬코일유니트(FCU)를 작동시킨 경우가 작동시키지 않은 경우에 비해 유출입수의 온도차가 $3.3^{\circ}C$ 정도 크고, 소비전력량은 36.2~40.1%정도 증가하였으며, 시간당 방열량은 44.6~52.0% 정도 증가하는 것으로 나타났다. 실험기간동안 순환유량은 0.48~$0.49L{\cdot}s^{-1}$ 정도의 범위에 있었고, 평균유속은 1.53~$1.56m{\cdot}s^{-1}$ 정도였다. 유출입수의 평균 온도차는 6.24~$11.50^{\circ}C$이었다. 최저 외기온 -14.0~$-0.6^{\circ}C$ 범위에서 설정온도별 방열량은 135,930~307,150kcal 정도의 범위로서 시간당 9,610~$19,630kcal{\cdot}h^{-1}$ 정도의 범위에 있었다. 이것은 최대난방부하의 약 23~53% 정도의 난방에너지를 공급할 수 있을 것으로 나타났다. 전체 방열량과 소비전력량은 각각 2,548,306kcal 및 3,075.7kWh이다. 화석연료인 경유로 난방할 경우, 소요되는 경유의 총 소비량은 281.6L 정도이고 비용은 321,000won인 것으로 나타났다. 농가용 전력요금을 적용하면 전력사용에 대한 총비용은 110,730won 정도로서 경유 소비 비용의 33.5% 정도로 나타났다. 실험구의 온도가 대조구보다 약 8.3~$14.6^{\circ}C$ 정도 높게 나타났다.