굴뚝효과와 외부출입문 개방을 고려한 부속실 제연 (Vestibule Smoke Control Considering the Stack Effect and the Opening of the Outside Door)

  • 김용광;손주달;김서영;공하성
    • 대한안전경영과학회지
    • /
    • 제26권1호
    • /
    • pp.15-24
    • /
    • 2024
  • The purpose of this study is to improve the stack effect of the staircase and the failure to take into account the opening of the outside door of the staircase, which are the disadvantages of the existing smoke control only vestibule. As a result of the study, the new vestibule and the staircase simultaneous smoke control are equipped with an exhaust flap damper with an effective opening area of about 0.25 m2 in the upper part of the staircase, and a ventilator-type air supply fan of about 5 m3/s in the lower part, and take measures to prevent overpressure in the staircase. If you use the new simultaneous smoke control method of the vestibule and staircase, you can achieve the following effects. First, it is possible to open the external entrance door. Second, it can reduce the stack effect. Third, the staircase door closes automatically without fail. And a new method of preventing overpressure was proposed for the vestibule.

편복도식 아파트에서 복도 외측 창호의 설치 유무에 따른 열손실 시뮬레이션 비교 연구 (A Study on the Comparison of Simulation for Heat Loss According to the Installation of Windows for Openings in External Wall of One Side Corridor Type Apartments)

  • 김대원;정광섭;김영일;김성민
    • 에너지공학
    • /
    • 제22권1호
    • /
    • pp.51-57
    • /
    • 2013
  • 에너지가 국가경쟁력의 중요 원동력이 됨에 따라 정부 각 부처 민간에 이르기까지 에너지를 절감하고자 노력하고 있다. 본 연구는 편복도형 아파트 출입 개방부에 대해서 창호를 설치하여 복도부분의 창이 있을 때와 없을 때를 구분하여 에너지소요량을 비교하고 평가하는데 그 목적이 있다. 이런 개선과정에 대해 에너지 사용실태를 조사하고 개선 전, 후를 시뮬레이션통해 에너지소요량을 비교하고 분석하여 정부의 그린리모델링 사업 방향에 조금이나마 도움이 되었으면 한다.