• Title/Summary/Keyword: Number of tube row

Search Result 38, Processing Time 0.024 seconds

Heat Transfer Characteristics of Individual Rows for Fin-and-Tube Heat Exchangers (핀-관 열교환기의 열별 열전달 특성)

  • Kim, Nae-Hyun;Shin, Tae-Ryong;Han, Sung-Pil
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.19 no.2
    • /
    • pp.149-155
    • /
    • 2007
  • The row-by-row heat transfer characteristics of fin-and-tube heat exchangers were experimentally investigated. Three wavy fin samples having different rows (one, two and three) and one plain fin sample (three row) were tested for $600{\leq}Re_{D}{\leq}4,000$. The heat transfer data were obtained for individual rows, and the corresponding heat transfer coefficients were reduced from the data. Results showed that the heat transfer coefficients were strongly dependent on the tube row. The heat transfer coefficient decreased as the tube row increased. However, the row effect was different depending on the fin shape. For the wavy fin, the row effect significantly decreased as the Reynolds number increased, yielding approximately the same heat transfer coefficients at $Re_{D}{\approx}2,500$. For the plain fin, however, the row effect lasted for the whole Reynolds number range. The increased mixing of bulk flow by wavy channels appears to induce high heat transfer coefficient (accordingly diminishing row effect) at downstream rows. The heat transfer coefficients of individual rows were higher for heat exchangers having larger tube rows.

Heat Transfer Characteristics of Flat Plate Finned-Tube Heat Exchangers with a Variation of Fin Pitch and Number of Tube Row (핀-튜브 열교환기의 핀피치 및 열수 변화에 따른 열전달 성능특성에 관한 연구)

  • Kim Yong-Han;Lee Ho-Seong;Kim Yong-Chan
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.10
    • /
    • pp.930-937
    • /
    • 2005
  • The objective of this study is to investigate the heat transfer performance of flat plate finned-tube heat exchangers with large fin pitch. In this study, twenty-two heat exchangers were tested with a variation of fin pitch, number of tube row, and tube alignment. The heat transfer coefficient decreased with a reduction of the fin pitch and an increase of the number of tube row. The staggered tube alignment improved heat transfer performance more than $10\%$ compared to the inline tube alignment. A heat transfer correlation was developed from the measured data for flat plate finned-tubes with large fin pitch. The correlation yielded good predictions of the measured data with mean deviations of $3.6\%\;and\;6.4\%$ for the inline and staggered tube alignment, respectively.

Heat Transfer Performance of Individual Rows in Fin-Tube Heat Exchangers (2열 핀-관 열 교환기의 열별 전열성능 측정)

  • 권영철;정지환;장근선;홍기수;진심원
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.3
    • /
    • pp.280-286
    • /
    • 2004
  • An experimental study is peformed to examine the heat transfer performance of individual rows of fin-tube heat exchangers. The heat transfer performance is measured using an air-enthalpy type calorimeter. The examined heat exchangers consist of 7mm tube and fin patterns of them are slit and louver types. Equivalent fin spacings are 18 fins per inch(fpi) for all samples, and the number of tube rows are two. In order to confirm that thermal boundary condition on fins of each row are the same, physically separated between two rows as well as connected heat exchangers are used. The frontal air velocity is varied from 0.7 to 2.5㎧. Heat transfer performance for each row is measured. It is observed that the heat transfer coefficient of the second row is smaller than that of the first row at low Reynolds number while larger at high Reynolds number.

Heat Transfer Performance of Individual Rows in Fin-Tube Heat Exchangers (핀-관 열교환기에서 개별 열의 열전달 효과)

  • Jeong, Ji-Hwan;Chang, Keun-Sun;Lee, Hyun-Woo
    • 유체기계공업학회:학술대회논문집
    • /
    • 2003.12a
    • /
    • pp.238-244
    • /
    • 2003
  • An experimental study was performed to examine the heat transfer performance of individual rows of fin-tube heat exchangers. The heat transfer performance was measured using air-enthalpy type calorimeter. The examined heat exchangers consists of $7{\Phi}$ tube and fin patterns of them are slit and louver types. Equivalent fin spacing are 18 FPI for all samples, and the number of tube rows were 2. In order to confirm that thermal boundary condition on fins of each row are the same, physically separated between two rows as well as connected heat exchangers were used. The frontal air velocity varied from 0.7 to 2.5 m/s. Heat transfer performance for each row are measured. It was observed that the heat transfer coefficient of the 2nd row were smaller than that of the 1st row at low Reynolds number while larger at high Reynolds number.

  • PDF

Heat Transfer Coefficients of Individual Rows for Fin-and-Tube Heat Exchangers (휜-관 열교환기의 열별 열전달 계수 측정)

  • Shin, T.R.;Lee, E.R.;Kim, N.H.
    • Proceedings of the KSME Conference
    • /
    • 2004.11a
    • /
    • pp.1034-1039
    • /
    • 2004
  • The row-by-row heat transfer characteristics of fin-and-tube heat exchangers having wavy fins were experimentally investigated. Three samples having different rows (one, two and three) were tested. Results show that the heat transfer coefficient is strongly dependent on the tube row. The heat transfer coefficient of the first row is larger than those of second or third rows. However, the difference decreases as the Reynolds number increases. The heat transfer coefficients of the second and the third row are approximately the same, probably due to increased mixing of bulk flow by wavy channels. Although samples have different tube row, the heat transfer coefficients of same row are approximately the same.

  • PDF

An Experimental Study on the Airside Performance of Fin-and-Tube Heat Exchangers Having Wide Louver Fin (광폭 루버 핀이 장착된 핀-관 열교환기의 공기측 전열 성능에 관한 실험적 연구)

  • Kim, Nae-Hyun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.27 no.5
    • /
    • pp.254-262
    • /
    • 2015
  • Heat transfer rate can be increased by increasing the heat transfer area. In this study, wide louver fin-and-tube heat exchangers with $P_t/P_l=1.03$ were tested and compared with louver fin-and-tube heat exchanger with $P_t/P_l=0.6$. Results show that heat transfer capacities of wide louver samples are larger (9.8% at one row, 13.6% at two row and 4.1% at three row) than those of conventional louver samples. Considering the area ratio of 1.78, the increase of heat transfer capacity is rather small, possibly due to the smaller heat transfer coefficient and fin efficiency of the wide louver sample. The j factor of the louver fin was 67% larger at one row, 42% larger at two row and 52% larger at three row. The f factor of the louver fin was 81% larger at one row, 63% larger at two row and 60% larger at three row. The effect of fin pitch on j and f factors are not pronounced and the j factor decreased as the number of tube row increased.

Study on Heat Transfer Characteristics of Discrete Fin-and-tube Heat Exchangers (독립 핀-튜브 열교환기의 열전달 성능특성에 관한 연구)

  • Lee, Ho-Seong;Kim, Yong-Han;Choi, Jong-Min;Kim, Yong-Chan
    • Proceedings of the SAREK Conference
    • /
    • 2005.11a
    • /
    • pp.274-280
    • /
    • 2005
  • The objective of this study Is to investigate the heat transfer performance of plate discrete fin-and-tube heat exchangers with large fin pitch. In this study, twenty-two heat exchangers were tested with a variation of fin pitch, number of tube row, longitudinal tube pitch and fin alignment. Discrete fin type exchangers improved heat transfer performance more than 10% compared to tile continuous fin type heat exchangers. The air-side heat transfer coefficient decreased with a reduction of the fin pitch and an increase of the number of tube row, The staggered fin alignment improved heat transfer performance more than 6% compared to the inline fin alignment. The effect of longitudinal tube pitch was insignificant on the j-factor and experiments found opposite effects on the j-factor with respect to fin alignment. Heat transfer correlations were developed from the measured data for flat plate discrete fin-and-tube heat exchangers with large fin pitch. The correlations yielded good predictions of the measured data with mean deviations of 1,4% and 0.3% for tire inline and staggered tube alignment, respectively.

  • PDF

NUMERICAL ANALYSIS FOR LONGITUDINAL PITCH EFFECT ON TUBE BANK HEAT TRANSFER (관군 배열에서의 종간 간격이 열전달에 미치는 영향에 대한 수치 해석적 연구)

  • Lee, D.;Ahn, J.;Shin, S.
    • Journal of computational fluids engineering
    • /
    • v.17 no.3
    • /
    • pp.39-44
    • /
    • 2012
  • In this study, a longitudinal pitch effect on in-line tube bank heat transfer has been analyzed numerically. To verify the accuracy of the solver model and boundary conditions, global Nusselt number(Nu) and pressure drop across the 2 row tube bank are compared with the existing experimental correlations under 500 ~ 2,000 Reynolds number(Re) range. By changing transverse pitch($S_T$) or longitudinal pitch($S_L$) separately in tube bank, we're trying to identify the each effect on heat transfer. We found that the effect of transverse pitch can be accounted for Reynolds number evaluated with maximum velocity($V_{max}$) at the smallest flow area similar to most existing correlations. Variation of the longitudinal pitch($S_L$) has a greater impact on the heat transfer compared to the transverse pitch($S_T$). Overall Nusselt number increases with larger longitudinal pitch($S_L$), however individual Nusselt number of the tube row has significant difference after the first row.

Measurement of Flow Field through a Staggered Tube Bundle using Particle Image Velocimetry (PIV기법에 의한 엇갈린 관군 배열 내부의 유동장 측정)

  • 김경천;최득관;박재동
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.7
    • /
    • pp.595-601
    • /
    • 2001
  • We applied PIV method to obtain instantaneous and ensemble averaged velocity fields from the first row to the fifth row of a staggered tube bundle. The Reynolds number based on the tube diameter and the maximum velocity was set to be 4,000. Remarkably different natures are observed in the developing bundle flow. Such differences are depicted in the mean recirculating bubble length and the vorticity distributions. The jet-like flow seems to be a dominant feature after the second row and usually skew. However, the ensemble averaged fields show symmetric profiles and the flow characteristics between the third and fourth measuring planes are not so different. comparison between the PIV data and the RANS simulation yields severe disagreement in spite of the same Reynolds number. It can be explained that the distinct jet-like unsteady motions are not to be accounted in th steady numerical analysis.

  • PDF

An Experimental Study on Air-Side Performance of Fin-and-Tube Heat Exchangers Having Compound Enhanced Fins (복합 전열 촉진 핀이 적용된 핀-관 열교환기의 성능에 대한 실험적 연구)

  • Kim, Nae-Hyun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.16 no.7
    • /
    • pp.4364-4374
    • /
    • 2015
  • In this study, heat transfer and friction characteristics of compound enhanced fin-and-tube heat exchangers were experimentally investigated. Louver-finned heat exchangers were also tested for comparison purpose. The effect of fin pitch on j and f factor was negligible. The j factor decreased as number of tube row increased. However, f factor was independent of number of tube row. Louver fin samples yielded higher j and f factors than compound enhanced fin samples. For one row, j and f factors of louver fin were 23% and 27% higher than those of compound enhanced fin. For two row, those were 11% and 8%, and for three row, those were 10% and 9%. However, heat transfer capacities at the same pressure drop of the compound enhanced fins were 6.4% for one row, 11.1% for two row and 13.6% for three row larger than those of louver fins, Existing louver fin correlation overpredicted the present j factors and underpredicted the present f factors.