수력발전기 고정자 권선의 운전중 부분방전 특성 (Properties of On-Line Partial Discharge in Hydrogenerator Stator Windings)

  • 김병한;김희동
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제55권4호
    • /
    • pp.172-177
    • /
    • 2006
  • During normal machine operation, partial discharge(PD) tests were performed with partial discharge analyzer(PDA) in two hydrogenerators. Six cable couplers were installed in circuit ring bus and endwinding of three phases. PDA showed that the normalized quantity number(NQN) and the partial discharge magnitude$(Q_m)$ were very low in hydrogenerator #1 and #2, respectively. The trend analyses of NQN and $Q_m$ value are available for monitoring of the insulation condition in hydrogenerator stator windings. The insulation condition of stator winding can be assessed. Discharge at conductor surface was discovered in B phase(C2 coupler) of hydrogenerator #1. Internal discharges were generated in A and C phases(C2 coupler) of hydrogenerator #1 and in A, Band C phases(C1 and C2 couplers) of hydrogenerator #2. Slot discharges occurred in A, Band C phases(C1 coupler) of hydrogenerator #1. The stator windings of two hydrogenerators were in good condition.

가스터빈 발전기 고정자 권선의 절연상태 평가 (Assessment of Insulation Condition in Gas Turbine Generator Stator Windings)

  • 김희동;양규현;주영호
    • 전기학회논문지
    • /
    • 제59권8호
    • /
    • pp.1423-1428
    • /
    • 2010
  • The results of off-line and on-line diagnostic tests performed on the stator winding of an air-cooled gas turbine(G/T) generator are reported in this paper. Off-line diagnostic tests included measurements of the ac current, dissipation factor(tan${\delta}$), and partial discharge(PD). Six epoxy-mica capacitors were installed in the three phases of G/T generator for performing on-line diagnostic testing with the turbine generator analyzer(TGA). The TGA showed that the normalized quantity number(NQN) and the PD magnitude($Q_m$) were high in phase A of the stator winding. Internal discharges were generated in phases B and C, and slot discharge occurred in phase A. According to the trend analyses of the NQN and $Q_m$ values available for insulation condition assessment for G/T generator stator windings, it was concluded that phases B and C were in good condition, whereas phase A has been significantly deteriorated.

4.16kV 전동기 고정자 권선의 절연열화 특성 (Characteristics of Insulation Aging in 4.16kV Motor Stator Windings)

  • 김희동;공태식
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.1381_1382
    • /
    • 2009
  • Nondestructive tests were performed on two 4.16kV motors. Epoxy-mica coupler(80pF) was connected to 4.16 kV motor stator windings. The voltage applied to the stator windings was 2.4 kV, 3.0kV, 3.5kV and 4.16kV, respectively. Digital partial discharge detector(PDD) and turbine generator analyzer(TGA) were used to measure partial discharge(PD) activity. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). The PD levels in pC were measured with PDD. PD patterns of stator windings were indicated the internal discharge. PD patterns are consistent with the result of measurement using PDD and TGA.

  • PDF

양수발전소 발전-전동기 운전중 감시 시스템의 개발 (Development of On-Line Monitoring System for Pumped Storage Generator/Motor)

  • 김희동;주영호
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제53권3호
    • /
    • pp.168-174
    • /
    • 2004
  • On-line monitoring system(OMS) has been developed for the pumped storage generator/motor The OMS is applied to diagnosis of the PD(partial discharge) activity of stator insulation, the shorted-turn of rotor winding and the variation of the air-gap between stator and rotor. The OMS consists of DAS(data acquisition system), main server system, gateway and display PC. The DAS measures the PD, the shorted-turn and air-gap from three sensors installed on the generator/motor. The gateway controls the data which sent by DAS. The main server system saves the data, analyzes the data and conducts the diagnostic algorithm. The display PC shows the diagnostic results of partial discharge, shorted-turn and air-gap. Field tests were conducted using PDA(partial discharge analyzer). The results of the OMS and PDA measurements can be directly correlated with normalized quantity number(NQN), PD magnitude(Qm) and PD pattern.

고압전동기 결함신호의 특징추출에 관한 연구 (Feature Extraction for Fault Signals of High Voltage Motor Stator Windings)

  • 박재준;김희동
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 하계학술대회 논문집 Vol.5 No.2
    • /
    • pp.1154-1157
    • /
    • 2004
  • During normal machine operation, partial discharge(PD) measurements were performed with turbine generator analyzer(TGA) in imitation stator winding of high voltage motors. The motor was energized to 4.47kV, 6.67, respectively. Applied voltage to Imitation winding was used two voltage level, 4.47[KV]and 6.67[KV]. Motors having imitation stator winding were installed with 80pF capacitive couplers at the terminal box Case of PD Pattern regarding applied voltage phase angel, the PD patterns were displayed two dimensional and three dimensional. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). As the result, we could discrimidate using TGA the difference of internal and surface discharge for imitation stator winding. We have used the other technique, in order to feature extraction of faulty signals on stator winding, Daubechies Discrete wavelet transform and Harmonics analysis(FFT) about faulty signals.

  • PDF

발전기 고정자 권선의 운전중 부분방전 측정에 의한 절연진단 시스템 개발 (Development of Insulation Diagnosis System by On-Line Partial Discharge Measurement of Generator Stator Windings)

  • 신병철;황돈하;김용주;김정우
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 추계학술대회 논문집 학회본부 C
    • /
    • pp.1025-1027
    • /
    • 1999
  • Recently, many researches on a diagnosis of stator winding insulation of large generators are reported. They mostly utilize a trend analysis of Partial Discharge (PD). In this paper, a novel on-line monitoring system for an insulation diagnosis is proposed. This system obtains the parameters such as Maximum Partial Discharge Magnitude (QM), Normalized Quantity Number (NQN) and Dynamic Stagnation Voltage (DSV) by continuous on-line monitoring of winding insulation. It is capable of diagnosing the insulation condition by analyzing the trend of PD and utilizing the database built by the system.

  • PDF

양수발전기 고정자 권선에서 운전중 및 정지중 부분방전 특성 (On-Line and Off-Line Partial Discharge Properties in the Pumped Storage Generator Stator Windings)

  • 김희동;주영호;윤대헌
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 E
    • /
    • pp.2089-2092
    • /
    • 1999
  • Partial discharge(PD) tests were performed both when the pumped storage generator(rated 13.8kV and 220MVA) was on-line and off-line. This generator has been equipped with 12 bus coupler sensors in directional mode. PD tests were conducted using partial discharge analyzer(PDA), partial discharge meter(PDM) and digital partial discharge detector. PDA showed that the patterns of the normalized quantity number(NQN) and the partial discharge magnitude are in accord with on-line and off-line. The insulation condition was estimated by diagnostic tests(off-line) such as PD magnitude and dissipation factor.

  • PDF

PDA를 이용한 고압전동기 고정자 권선에서 부분방전 특성 (Partial Discharge Properties of High Voltage Motor Stator Insulation using Partial Discharge Analyzer)

  • 김희동;이상길
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 연구회
    • /
    • pp.225-228
    • /
    • 2001
  • Partial discharge(PD) testing for different capacitive couplers was performed on a 6.6kV, 448kW pulverizer motor. The motor has been in service for twenty years. PD tests were measured using digital partial discharge detector(DPDD) and partial discharge analyzer(PDA), respectively. PDA is used to in the motor stator insulation, which three 80pF or three 500pF epoxy-mica couplers were installed, one per phase. The 500pF couplers did detect more normalized quantity number(NQN) than the 80pF couplers. DPDD and PDA showed that PD and NQN magnitudes increased with increase of ac voltage. Internal discharge was discovered in the motor stator insulation. DPDD and PDA test results are in accordance with the pattern and magnitude of PD.

  • PDF

고압전동기 운전중 부분방전 추이 분석 (Analysis of On-Line Partial Discharge Trend in High Voltage Motors)

  • 김희동;공태식;김충효
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 C
    • /
    • pp.1472-1473
    • /
    • 2006
  • During normal machine operation, partial discharge(PD) measurements were peformed with turbine generator analyzer(TGA) in two high voltage motors(rated 6.6 kV). These high voltage motors were installed with 80 pF capacitive couplers at the terminal box. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude (Qm). The trend analyses of NQN and $Q_m$ value are available for monitoring of the insulation condition in stator windings of high voltage motors.

  • PDF

수력발전기 고정자 권선에서 부분방전 특성 (Partial Discharge Property of Hydrogenerator Stator Windings)

  • 김희동
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 춘계학술대회 논문집 유기절연재료 방전 플라즈마
    • /
    • pp.86-90
    • /
    • 2000
  • Partial discharge(PD) tests were performed when the hydrogenerator(rated 11kV and 25MVA) was shut down(off-line). Six cable couplers were installed in the ring bus as well as within hydrogenerator terminal box. PD tests were conducted using partial discharge analyzer(PDA) and digital partial discharge detector(PDD). PDA showed that the normalized quantity number(NQN) and the partial discharge magnitude increased with increase of ac voltage. Slot discharges were discovered in three phases(A, B and C) at the rated voltage. PDA and PDD test results are in accordance with the pattern and magnitude of partial discharge. This hydrogenerator stator windings were in good condition.

  • PDF