Study on Performance Characteristic of Water-Cooled Type Beat Pump Using Hydrocarbon Refrigerants (탄화수소계 냉매를 이용한 수냉식 히트점프의 성능특성에 관한 연구)

  • Jun Chul-Ho;Lee Ho-Saeng;Kim Jae-Dol;Yoon Jung-ln
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.29 no.8
    • /
    • pp.870-876
    • /
    • 2005
  • This study of the performance characteristics of natural refrigerants such as R-290 (propane), R-6OOa (iso-butane) and R-1270 (propylene) has investigated to compare with conventional HCFC's refrigerant R-22 for water-cooled heat pump system. The experimental apparatus has basic parts of cycle that uses the water as a heat source. The Performance of the water-cooled system using hydrocarbon refrigerants had been getting better than R-22 from start-up to the similar evaporating temperature after stabilizing system. Through the above it is possible that hydrocarbon refrigerants could be drop-in alternatives for R-22.

Study on Heat Transfer Characteristics of Evaporator with Horizontal Small Diameter Tubes using Natural Refrigerant Propane (자연냉매 프로판을 이용한 수평세관 증발기의 열전달 특성에 관한 연구)

  • Ku, H.K.
    • Journal of Power System Engineering
    • /
    • v.14 no.4
    • /
    • pp.11-16
    • /
    • 2010
  • The evaporation heat transfer characteristics of propane(R-290) in horizontal small diameter tubes were investigated experimentally. The test tubes have inner diameters of 1 mm and 4 mm. Local heat transfer coefficients were measured at heat fluxes of 12, $24\;kW/m^2$, mass fluxes of 150, $300\;kg/m^2s$, and evaporation temperature of $15^{\circ}C$. The experimental results showed that the evaporation heat transfer coefficient of R-290 has an effect on heat flux, mass flux, tube diameter, and vapor quality. The evaporation heat transfer of R-290 has an influenced on nucleate boiling at low quality and convective boiling at high quality. The evaporation heat transfer coefficient of R-290 increases with decreasing inner tube diameter. And the evaporation heat transfer coefficient of R-290 is about 1~3 times higher than that of R-134a.

A Study on the Price Evaluation Per 1 Ton of Liquefied Natural Gas According to the Refrigerants Supply Temperature in the Electric Refrigerator (전기식 냉동기에서 냉매의 공급온도에 따른 액화천연가스의 톤당 냉열 가격 산출에 대한 연구)

  • KIM, YONUNGWOO;PARK, ILSOO;CHO, JUNGHO
    • Transactions of the Korean hydrogen and new energy society
    • /
    • v.30 no.5
    • /
    • pp.473-477
    • /
    • 2019
  • In this paper, cold heat price contained in the 1 ton/h of LNG has been evaluated using PRO/II with PROVISION release 10.2 from Aveva company when LNG is used to liquefy several refrigerants instead of using vapor recompression refrigeration cycle. Normal butane, R134a, NH3, R22, propane and propylene refrigerants were selected for the modeling of refrigeration cycle. It was concluded that LNG cold heat price was inversely proportional to the refrigerant supply temperature, even though LNG supply flow rate is not varied according to the refrigerant supply temperature.

Evaporation Heat Transfer Characteristics of Hydrocarbon Refrigerants R-290 and R-600a in the Horizontal Tubes

  • Roh, Geon-Sang;Son, Chang-Hyo;Oh, Hoo-Kyu
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.31 no.1
    • /
    • pp.74-83
    • /
    • 2007
  • This paper presents the experimental results of evaporation heat transfer coefficients of HC refrigerants (e.g. R290 and R600a). R-22 as a HCFCs refrigerant and R-l34a as a HFCs refrigerant in horizontal double pipe heat exchangers, having four different inner diameters of 10.07, 7.73, 6.54 and 5.80 mm respectively. The experiments of the evaporation process were conducted at mass flux of $35.5{\sim}210.4 kg/m^2s$ and cooling capacity of $0.95{\sim}10.1 kW$. The main results were summarized as follows : The average evaporation heat transfer coefficient of hydrocarbon refrigerants(R-290 and R-600a) was higher than the refrigerants, R-22 and R-l34a. In comparison with R-22 the evaporation heat transfer coefficient of R-l34a is approximately $-11{\sim}8.1 %$ higher. R-290 is $56.7{\sim}70.1 %$ higher and R-600a is $46.9{\sim}59.7 %$ higher. respectively. In comparison with experimental data and some correlations, the evaporation heat transfer coefficients are well predicted with the Kandlikar's correlation regardless of a type of refrigerants and tube diameters.

An Experimental Study on Miscibility and Vapor Pressure of R-744/Oil Mixtures (R-744/오일 혼합물의 상용성 및 증기압에 관한 실험적 연구)

  • 최희성;강병하;박경근;김석현
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.2
    • /
    • pp.150-157
    • /
    • 2004
  • Carbon dioxide ($CO_2$, R-744) has become a very popular issue in application to refrigeration and air conditioning systems as a natural refrigerant. An experimental study has been carried out to investigate miscibility and the vapor pressure of refrigerant R-744 in the presence of lubricant oil. This is of particular interest in the selection of the lubricant oil for the compressor of a refrigeration system or an air conditioning system using the refrigerant R-744. The experimental set-up consists of the equilibrium cell, measuring devices, the vacuum pump, the constant temperature bath and relevant connecting pipes made of stainless steel. Five lubricant oils, such as mineral oil (Naphthenic), AB (Alkyl Benzene) oil, PAO (Poly Alpha Olefin) oil, PAG (Poly Alkylene Glycol) oil and POE (Polyol Ester) oil are considered in the present study. Test runs were conducted with the oil concentration range from 5 to 50 wt%, and the temperature range from -10 to 1$0^{\circ}C$ with 2$^{\circ}C$ intervals. The miscibility results are visualized and correlated with the vapor pressure for the individual test components.

Cycle performance of refrigeration and air-conditioning system using the hydrocarbon refrigerant R-290 (탄화수소계 냉매 R-290을 사용하는 냉동.공조 장치의 사이클 특성에 관한 연구)

  • 박기원
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.23 no.4
    • /
    • pp.447-452
    • /
    • 1999
  • This paper describes the cycle performance of heat-pump system using R-22 and R-290. Experiments were performed in the smooth tube with inside diameter of 10.07mm and outside diameter of 12.07 mm and grooved inner tube having 75 fins with a height of 0.25mm Condensing temperatures were held constantly between 318K and 328 K while evaporating temperatures were varied from 257 K to 288 K mass velocities from 51 to $280 kg/m^2s$. From the experiments it was known that the evaporating temperature and condensing temperature had more affected by the compressor shaft power than the tube geometries. Cooling capacity of the R-22 and R-290 had similar values in the smooth and grooved inner tubes. The coefficient of performance(COP) was calculated using the compressor shaft power volumetric refrigeration capacity compression ratio and cooling capacity. The COP of the R-290 had slightly higher values than that of R-22 The major parameters affecting the heat pump cycle performance wee the refrigerant proper-ties and operating conditions rather than the geometric shapes of the heat exchanger

  • PDF

Characteristics of Cryogenic Cascade Refrigeration Cycle for Liquefaction of Natural Gas with the Pressure Drop of Heat Exchanger (LNG 열교환기의 압력강하에 따른 천연가스 액화용 초저온 캐스케이드 냉동사이클 특성)

  • Yoon, Jung-In;Choi, Kwang-Hwan;Son, Chang-Hyo;Kwag, Jin-Woo;Baek, Seung-Moon
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.36 no.6
    • /
    • pp.756-761
    • /
    • 2012
  • Natural gas is converted in to LNG by chilling and liquefying the gas to the temperature of $-162^{\circ}C$, when liquefied, the volume of natural gas is reduced to 1/600 of its standard volume. This gives LNG the advantage in transportation. In this study, the effects of the pressure drop of refrigerant and natural gas in the LNG heat exchanger of cryogenic cascade refrigeration cycle were investigated and then the design criteria for the pressure drop of refrigerant and natural gas of the LNG heat exchanger were proposed. The pressure drop of the cascade liquefaction cycle was investigated and simulated using HYSYS software. The simulation results showed that the pressure drop in the LNG heat exchanger is set to 50 kPa considering the increase in the compressor work and COP of cryogenic cascade liquefaction cycle.

Characteristics on Evaporating Heat Transfer and Pressure Drop of HCs Refrigerants (탄화수소계 냉매의 증발 열전달 및 압력강하 특성)

  • Lee Kwang-Bae;Lee Ho-Saeng;Kim Jae-Dol;Yoon Jung-In
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.7
    • /
    • pp.681-687
    • /
    • 2005
  • Experimental results for heat transfer characteristic and pressure gradients of HCs refrigerants R-290, R-600a, R-1270 and HCFC refrigerant R-22 during evaporating inside horizontal double pipe heat exchangers are presented. The test sections which has one tube diameter of 12.70 m with 0.86 mm wall thickness, another tube diameter of 9.52 mm with 0.76 mm wall thickness are used for this investigation. The local evaporating heat transfer coefficients of hydrocarbon refrigerants were higher than that of R-22. The average evaporating heat transfer coefficient increased with the increase of the mass flux. It showed the higher values in hydrocarbon refrigerants than R-22. Hydrocarbon refrigerants have higher pressure drop than R-22 in 12.7 mm and 9.52 mm. This results form the investigation can be used in the design of heat transfer exchangers using hydrocarbons as the refrigerant for the air- conditioning systems.

Condensing Heat Transfer of Natural Refrigerants with Nanoparticles in Enhanced Tube (나노입자를 포함한 자연냉매의 마이크로 휜관 응축 열전달 특성)

  • Lee, H.S.
    • Journal of Power System Engineering
    • /
    • v.12 no.3
    • /
    • pp.19-25
    • /
    • 2008
  • This paper deals with the heat transfer and pressure drop characteristics of R-290 (Propane), R-600a (Iso-butane) and R-1270 (Propylene) as an environment friendly refrigerant and R-22 as a HCFC's refrigerant for condensing. The test section is a horizontal double pipe heat exchanger. Condensing heat transfer and pressure drop measurements were Peformed for 12.70 mm micro-fin tube and compared with the results in smooth tube. The local condensing heat transfer coefficients of hydrocarbon refrigerants were superior to those of R-22 and the maximum increasing rate of heat transfer coefficient was found in R-600a. The average condensing heat transfer coefficients in hydrocarbon refrigerants showed 20 to 28% higher values than those of R-22. Hydrocarbon refrigerants have a higher pressure drop than that of R-22 with respect to refrigerant qualify and mass flux. Also, the condensing heat transfer coefficient and pressure drop of working fluids in smooth and micro-fin tube were compared. The heat transfer enhancement factor (EF) between smooth and micro-fin tube varied from 2.2 to 2.6 in all experimental conditions.

  • PDF

Study on the Evaporation Heat transfer of $CO_2$ in a Horizontal tube (수평관내의 $CO_2$의 증발 열전달에 관한 연구)

  • Jang, Seong-Il;Choi, Sun-Muk;Kim, Dae-Hui;Oh, Hoo-kyu
    • Proceedings of the Korean Society of Marine Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.240-241
    • /
    • 2005
  • The experiments were conducted without oil in a closed refrigerant loop which was driven by a magnetic gear pump. The main components of the refrigerant loop are a receiver, a variable-speed pump, a mass flow meter, a pre-heater and evaporator(test section). The test section was made of a horizontal stainless steel tube with the inner diameter of 4.57 mm, and length of 4 m. The experiments were conducted at mass flux of 200 to 700 kg/$m^2s$, saturation temperature of 0$^{circ}C$ to 20$^{circ}C$, and heat flux of 10 to 30 kW/$m^2$. The test results showed the evaporation heat transfer of $CO_2$ has great effect on more nucleate boiling than convective boiling. The evaporation heat transfer coefficients of $CO_2$ are highly dependent on the vapor quality, heat flux and saturation temperature. In comparison with test results and existing correlations, correlations failed to predict the evaporation heat transfer coefficient of $CO_2$, therefore, it is necessary to develop reliable and accurate predictions determining the evaporation heat transfer coefficient of $CO_2$ in a horizontal tube.

  • PDF