• Title/Summary/Keyword: Natural exhaust vent

Search Result 5, Processing Time 0.02 seconds

Study on the Performance Evaluation of the Exhaust Stack used in High Riser Public House (초고층공동주택 국소배기용 입상덕트의 배기성능평가에 관한 연구)

  • Kwon, Yong-il;Lee, Tae-Kyu;Ahn, Jung-Hun
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.889-894
    • /
    • 2008
  • Exhaust system used in toilet and cooking place of high riser public house is roof fan of two basic types : natural roof ventilator and natural/forced roof ventilator. Natural/forced roof ventilator has a motor in the rotary shaft. There are many high riser public house in Korea. These buildings were not viewed as being major contributors to exhaust pollutants producted in indoor. It was because many engineers thought that exhaust in high riser building depend on stack effect. This study investigates on stack pressure determined by exterior pressure and the difference pressure control in exhaust stack used in high riser public house. This paper focuses mainly on the effect of the time interval for power supply of motor installed in roof fan with function of natural wind velocity and of exhaust air volume of toilet. It is observed there are higher exhaust efficiency than the existing natural roof ventilator.

  • PDF

Study on the Control Performance Evaluation of the Exhaust Stack used in High Riser Public House (초고층공동주택 국소배기용 입상덕트시스템의 제어성능평가에 관한 연구)

  • Kwon, Yong-Il;Ahn, Jung-Hun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.2
    • /
    • pp.103-108
    • /
    • 2009
  • Local exhaust system used in toilet and cooking place of low-rise public house installed roof ventilator at terminal of stack. There are many high riser public houses in Korea. These buildings were not viewed as being major contributors to exhaust pollutants producted in indoor. It was because many engineers thought that exhaust in high riser public house depends on stack effect. But Neutral pressure level represents in a terminal of stack with air tightness for the best exhaust efficiency. Thereby, lower floors have the worst indoor air quality. This paper focuses mainly on the exhaust efficiency improved by roof fan with motor installed in high riser public house. It is observed there is higher exhaust efficiency than the existing natural roof ventilator.

Prediction of the Fire Curtain Effect through a Numerical Simulation of a Reduced Scale Model for Fires in Theaters (공연장 화재 축소모형의 전산시뮬레이션을 통한 방화막 영향 예측)

  • Kim, Dong Hwan;Lee, Chi Young;Kim, Duncan
    • Fire Science and Engineering
    • /
    • v.32 no.3
    • /
    • pp.51-59
    • /
    • 2018
  • Although a fire curtain plays an important role in preventing smoke from spreading to the auditorium in a theater fire, there has been insufficient research on fire curtains. In this study, to check the accuracy of numerical simulation, for previous experiments using a reduced scale model, a numerical simulation was carried out, and the results were compared with previous experimental data. The fire curtain effect was then predicted numerically. A Fire Dynamics Simulator (FDS) was used, and the natural exhaust vent sizes were set to ~10%, ~5%, and ~1% of the stage floor area. The smoke movement was visualized, and the mass flow rates and temperatures were measured and analyzed. In addition, the law of similarity was used to examine the influence of a fire curtain in a real scale theater fire. Without the fire curtain, the present numerical simulation results were in agreement with the previous experimental data within reasonable accuracy. Meanwhile, the fire curtain affects the mass flow rates through the natural exhaust vent and proscenium opening, as well as the start time of soot outflow to the auditorium. Overall, the present results can be used to develop a fire curtain system.

A Study on the Effectiveness to the Life Safety by Enlarging Smoke Vent Size and/or Sprinklered System (배연창 크기와 스프링클러 작동이 인명안전에 미치는 영향 연구)

  • Kim, Hak-Joong;Park, Yong-Hwan;Lim, Choe-Hyun;Kim, Bum-Kyu
    • Fire Science and Engineering
    • /
    • v.24 no.2
    • /
    • pp.133-138
    • /
    • 2010
  • Recently, evacuation safety of a resident of building become the major concern, because building has been higher and more complicated. Buildings in Korea should install the natural smoke venting or mechanical smoke exhaust equipment according to the building law. The smoke control is the most important to guarantee the evacuation safety. This study evaluate the influence to the height and temperature of smoke layer by enlarging smoke vent size and operating sprinkler system using CFAST (Version 6). Smoke venting size is larger, the effect to height and temperature of smoke layer is increased in below 5 MW fire. But, the correlation of these is decreased in above 10 MW fire. The case that opened smoke vent and sprinklered are applied, life safety criteria are satisfied regardless of fire size. After design the fire scenario according to the service and size of building. Install the smoke vent suitable for the fire size and verify that by experiment or simulation.

Study of the Problems and Improvements of the Installation and Maintenance for Natural Smoke Ventilators in Buildings (국내 배연창 설치 및 유지관리의 문제점과 개선방안에 관한 연구)

  • Yun, Hi-Won;Choi, Seung-Hyuck;Ryu, Hyung-Kyou
    • Fire Science and Engineering
    • /
    • v.30 no.6
    • /
    • pp.118-123
    • /
    • 2016
  • In the event of a building fire, it is important to control the smoke generated to ensure the safe evacuation of occupants. A natural smoke ventilator should be installed to exhaust the fire smoke in accordance with the Korean building Act and Code. On the other hand, the present law does not specify the contents regarding natural smoke ventilators sufficiently. The problems that occur in various parts, such as the installation target, installation location, free area, and the control and maintenance of natural smoke ventilators need to be solved. In this study, the problem of the current system was examined through domestic and foreign standards, preliminary research, and field investigations. In addition, suggestions for improvement are provided.