Prediction of the Fire Curtain Effect through a Numerical Simulation of a Reduced Scale Model for Fires in Theaters  

Kim, Dong Hwan (Dept. of Fire Protection Engineering, Pukyong National University)
Lee, Chi Young (Dept. of Fire Protection Engineering, Pukyong National University)
Kim, Duncan (Korea Testing Laboratory)
Publication Information
Fire Science and Engineering / v.32, no.3, 2018 , pp. 51-59 More about this Journal
Abstract
Although a fire curtain plays an important role in preventing smoke from spreading to the auditorium in a theater fire, there has been insufficient research on fire curtains. In this study, to check the accuracy of numerical simulation, for previous experiments using a reduced scale model, a numerical simulation was carried out, and the results were compared with previous experimental data. The fire curtain effect was then predicted numerically. A Fire Dynamics Simulator (FDS) was used, and the natural exhaust vent sizes were set to ~10%, ~5%, and ~1% of the stage floor area. The smoke movement was visualized, and the mass flow rates and temperatures were measured and analyzed. In addition, the law of similarity was used to examine the influence of a fire curtain in a real scale theater fire. Without the fire curtain, the present numerical simulation results were in agreement with the previous experimental data within reasonable accuracy. Meanwhile, the fire curtain affects the mass flow rates through the natural exhaust vent and proscenium opening, as well as the start time of soot outflow to the auditorium. Overall, the present results can be used to develop a fire curtain system.
Keywords
Fire curtain; FDS; Smoke movement; Natural exhaust vent; Fire in theater;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Public Performance Act, $\S$ 2(4) (2016).
2 Y. J. Yeo, "A Study on the Major Design Factors affecting Ventilation in the Performance Hall Fires", Ph.D. Thesis, Hoseo University (2012).
3 J. Kwon, "Assessment of Fire Protection Systems in Proscenium Theaters", Case Studies in Fire Safety, Vol. 2, pp. 9-15 (2014).   DOI
4 W. S. Lee, S. H. Park, D. Kim, J. K. Park, H. S. Jang, J. S. Ryu and M. S. Kang, "Manual for Theatre Safety", Theater Safety Center in Korea Testing Laboratory (2015).
5 Theater Safety Center in Korea Testing Laboratory, "Safety Guidelines and Technical Standards for Stage Facilities in Theatre" (2011).
6 Public Performance Act, $\S$ 12(7) (2015).
7 S. J. Kim, "A Study on the Sprinkler System Standards about a Stage of Performing Arts Centers in Accordance with NFSC and NFPA", Master's Thesis, Gachon University (2013).
8 H. H. Kim, "A Study on the Improvement of Fire Protection System for Performing Art Center", Master's Thesis, Kyonggi University (2009).
9 Y. J. Lee, "An Application of Performance Based Fire Safety Design in Large indoor Space - Focused on Smoke Exhaust System Design in Theater", Journal of Korean Institute of Fire Investigation, Vol. 4, No. 1, pp. 75-81 (2004).
10 J. H. Klote and J. A. Milke, "Principles of Smoke Management", American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, GA, pp. 217-224 (2002).
11 K. McGrattan, S. Hostikka, R. McDermott, J. Floyd, C. Weinschenk and K. Overholt, "Fire Dynamics Simulator Technical Reference Guide Volume 3: Validation", NIST Special Publication 1018-3, Sixth Edition, pp. 70-74 (2017).
12 J. H. Kim, D. Kim and C. Y. Lee, "Effects of Fire Curtain and Forced Smoke Ventilation on Smoke Spread to Auditorium in Stage Fire of Theater", Fire Science and Engineering, Vol. 31, No. 5, pp. 28-36 (2017).   DOI