• Title/Summary/Keyword: NFPA 13D

Search Result 6, Processing Time 0.021 seconds

A Study on the Seismic Protection Performance of Press Fittings for Light Gauge Stainless Steel Pipes (일반배관용 스테인리스강관에 대한 프레스식 관이음쇠의 내진성능에 관한 연구)

  • Baek, Yeal-Sun;Nam, Jun-Seok
    • Fire Science and Engineering
    • /
    • v.31 no.4
    • /
    • pp.65-70
    • /
    • 2017
  • The seismic performance of press fittings is studied, which is one of the weldless joints of stainless steel pipe used in the water piping of recent fire protection system. The piping of this study was constructed based on the piping connection reference of NFPA 13. The permissible displacement of the piping was set as the allowed amount which is given in the Building Structure Standard, and the measurements were repeated 10 times. The Von-mises stress of the piping was 2.48 and 1.25 times of the allowed amount of stress, which was less than the standard, noted three times on the NPPs Allowable Stress for Level D service loading. Therefore, the press fittings shows enough seismic performance.

A Study on the Increase Installation of Sprinkler System in Residential Occupancies (주거용 스프링클러설비 설치의 확대에 관한 연구)

  • Jeong, Hyun-Gyu;Song, Yong-Sig;Lee, Jun-Suk;Cho, Won-Chol;Lee, Tae-Shik
    • 한국방재학회:학술대회논문집
    • /
    • 2007.02a
    • /
    • pp.522-525
    • /
    • 2007
  • This study is for reduce the damage of human life and property occurred by a fire in the normal house and market according to increase rate of a fire. this is focused on the present domestic code about prevent a fire and sprinkler system in residential occupancies.

  • PDF

Study on the effective response method to reduce fire risk of wood fuel heating system (화목 연료 난방설비의 화재 위험 감소 방안에 관한 이론적 연구)

  • Park, Kyong-Jin;Lee, Bong-Woo;Lee, Guen-Cull;Nam, Ki-Hun
    • Journal of the Korean Society of Industry Convergence
    • /
    • v.22 no.2
    • /
    • pp.163-171
    • /
    • 2019
  • Recently, rural housing in urban areas has been increasing due to the improvement of income level. With the increase of the construction of the power house, the installation of the heating system using the harmonious fuel for the purpose of heating and the beauty of the room is increasing rapidly. In addition to the increasing use of firewood heating equipment, the incidence of fire is also increasing. Analysis of the National Fire Data System of the Fire Department The result of the analysis of the National Fire Data System Many parts of the fire are incinerated by the accumulation of tar due to the incompleteness of periodic cleaning inside the cylinder. The distance between the fire extinguisher and the combustible materials such as ceiling, Resulting in fire. In addition, it was found that much of the fire of the firewood heating system in the time zone occurs during the sleeping and resting time and there is not enough time for the residents to cope. This, in turn, causes serious harm to the lives and property of the users of the pyrotechnic heating system. Therefore, in this study, domestic and foreign standards and laws related to fuel oil heating facilities were analyzed and 12 cases of fire accidents were analyzed. Through the revision of the fire prevention and firefighting facilities installation and maintenance law, the installation standards of the alarm and fire extinguishing facilities were presented.

Study on Theoretical Research to Reduce Fire Risk of Solar Power System (태양광 발전 시스템의 화재 위험 감소 방안에 관한 이론적 연구)

  • Park, Kyong-Jin;Lee, Guen-Cull;Lee, Bong-Woo
    • Journal of the Korean Society of Industry Convergence
    • /
    • v.23 no.2_2
    • /
    • pp.219-224
    • /
    • 2020
  • This study is based on the principle of solar power system and fire breakout. The result of the survey indicates that a solar power system is vulnerable to fire due to lack of maintenance after the installation. Currently the national fire safety agency does not have standards and legal provisions for the installation and maintenance of solar power facilities. Therefore, it increases the risk of fire breakouts as well as possibility of electric shock for the firefighters during fire fighting. This results possible damages to the human and equipments. In this study is proposing an automatic fire extinguishing system to reduce the power generation of solar panels during fire breakouts. Also, propose an over load current alarm system and fire prevention measures for fire fighters. The results of this study will be used as basic data for further fire testing of solar power systems.

Experimental study on the sound attenuation of the fire alarm sounder system in apartment buildings (공동주택 화재경보 발생음 특성에 관한 실험연구)

  • Lee, Min-Joo;Kang, Hee-Hyuk;Kwon, Bong-Suk;Kim, Myung-Jun
    • Proceedings of the Korean Society for Noise and Vibration Engineering Conference
    • /
    • 2007.05a
    • /
    • pp.1162-1168
    • /
    • 2007
  • In many fire emergencies, the audible fire alarm signals are very important to save the occupant's life. But as the sound insulation of building elements has been improved, it is more difficult for occupant to recognize the fire alarm signals when the fire alarm worked. This is the study to show the sound attenuation of the fire alarm sounder system in apartment buildings. We measured and analyzed the sound attenuation level in 17 units, and the results were compared with the minimum sound level at sleeping area by NFPA(National Fire Protection Association) 72. When only the fire alarm worked in stair hall, the sound levels in bedroom were in the range of $30.6{\sim}42.8dB(A)$ and the differences between sound level and ambient sound level in bedrooms were in the range of $7.1{\sim}13.8dB(A)$. And when the emergency broadcasting device in the livingroom and the fire alarm worked simultaneously, the sound levels in bedrooms were in the range of $54.2{\sim}63.0dBA$. Finally, it was showed that the fire alarm sounder system didn't give a sufficient sound level in bedroom to awake out of sleep.

  • PDF

Study on analytical method of fluoroquinolone residues in eggs by LC/MS/MS (LC/MS/MS를 이용한 식용란 중 fluoroquinolone계 항균물질의 분석법에 관한 연구)

  • Choi, You-Jeong;Yun, I-Ran;Nam, Sang-Yun;Park, Young-Ho;Kim, Byeong-Hun;Son, Seong-Gi
    • Korean Journal of Veterinary Service
    • /
    • v.30 no.1
    • /
    • pp.13-21
    • /
    • 2007
  • An atmospheric pressure chemical ionization (APcI) LC/MS/MS method was developed for the simultaneous analysis of fluoroquinolones (norfloxacin, ciprofloxacin, enrofloxacin, danofloxacin) residues in eggs. The spiked and blank samples were extracted from whole eggs using 50mM phosphate buffer (pH 7.4). The extract was cleaned up by passage though $Oasis^{(R)}$ MAX extraction cartridge for solid-phase extraction followed by elution with 4% formic acid in methanol. The extract of sample was separated on a Waters $Atlantis^{TM}$ $dC_{18}$ reversed-phase column ($4.6{\times}150mm,\;5{\mu}m$) and analyzed by APcI positive mode mass spectrometry. The mobile phase consists of aqueous 0.2% nonafluoropentanoic acid (NFPA) and methanol. Multiple reaction monitoring (MRM) using the precursor to product ion combinations of m/z $320\;{\dashrightarrow}\;302,\;332\;{\dashrightarrow}\;314,\;360\;{\dashrightarrow}\;342$ and m/z $358\;{\dashrightarrow}\;340$ were used to quantify norfloxacin (NOR), ciprofloxacin (CIP), enrofloxacin (ENR) and danofloxacin (DAN), respectively. The limits of quantification (LOQ) were 7.8ppb for NOR, 8.5ppb for CIP, 8.9ppb for ENR, and 4.8ppb for DAN. Average recoveries of fortified sample at levels of 0.025 to 0.1 ppm were estimated 71.29% for NOR, 75.27% for CIP, 85.51% for ENR and 81.22% for DAN. These results could be applied for the confirmation and quantification in eggs.