• Title/Summary/Keyword: Multi-pass heat exchanger

Search Result 5, Processing Time 0.021 seconds

Performance Analysis on a Multi-Pass Multi-Branch Heat Exchanger According to Pass Arrangement (다패스 다분지 열교환기의 패스 수에 따른 성능 분석)

  • Kim Min-Soo;Lee Kwan-Soo
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.30 no.8 s.251
    • /
    • pp.741-748
    • /
    • 2006
  • This paper numerically investigates the effects of pass arrangement on the flow distribution characteristics and the performance of a multi-pass multi-branch heat exchanger. Four cases of pass arrangement (2, 4, 6, 8 pass) are chosen to select a proper pass arrangement. A JF factor is used as an evaluation characteristic value to consider the heat transfer and the pressure drop. The present results indicate that 4-pass heat exchanger shows the best performance, and the design parameters in 4-pass heat exchanger are optimized. The design parameters are the locations of the inlet, outlet and separator, and are optimized using a response surface methodology. The JF factor of the optimum model is increased by about 9.3%, compared to that of the reference model (2-pass heat exchanger).

A study of heat transfer characteristics on the Multi-pass Heat exchanger with Minichannel (다분지 미니 채널 열교환기의 액단상 열전달 특성에 관한 연구)

  • Im, Yong-Bin;Lee, Seung-Hun;Kim, Jeung-Hoon;Kim, Jong-Soo
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.357-362
    • /
    • 2006
  • This research focused on the multi-pass heat exchanger using the minichannel possessing the spring fin. An air-water was used as working fluid. The characteristics of liquid single phase heat transfer were verified. The compact heat exchanger (heat transfer area density : ${\beta}=2,146 m^2/m^3$), based on the shape of header(Top combining header), 63 minichannels ($D_i$ : 1.4 mm, L : 0.25 m) and the air side adopting the copper wire spring fin, was fabricated. The heat transfer area density of the air side was improved up to 161% when compared with the conventional fin-tube heat exchanger that adopts the heat transfer tube with the inner diameter of 5 mm. With regard to heat transfer performance, heat transfer rate per unit volume increased up to 142% when compared with the fin-tube heat exchanger adopting the heat transfer tube with the inner diameter of 5 mm.

  • PDF

Flow Distribution Characteristics in a Multi-Pass Heat Exchanger (다패스 열교환기에서의 유량분배 특성)

  • Kim, Min-Soo;Kang, Soo-Jin;Lee, Kwan-Soo
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.737-742
    • /
    • 2006
  • This paper numerically investigates to evaluate the performance according to the number of passes and the inlet/outlet diameter in a multi-pass multi-branch heat exchanger. A JF factor is used as an evaluation characteristic value to consider the heat transfer rate and the pressure drop simultaneously. It estimates the performance according to the number of passes and the inlet diameter of the reference heat exchanger. When the ratio of the inlet diameter to the header height is about 0.5, the optimum number of passes is selected along with the inlet diameter.

  • PDF

Experimental Study of the Superheat and Control of the Refrigerant Flow-Rate in the Evaporator of a Multi-type Air-Conditioning System (멀티형 공조시스템의 증발기 과열도에 관한 실험적 연구 및 냉매유량 제어)

  • 김태섭;홍금식;손현철
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 2000.10a
    • /
    • pp.221-221
    • /
    • 2000
  • The heat exchange part in a modern multi-type air-conditioning system employs multiple-pass heat exchangers. The heat-transfer performance of an each pass in such an exchanger depends strongly on the length of the two-phase region and the mass flow of the refrigerant. The total length and diameters of the pipes, the exit conditions, and the arrangement of each pass as well as the geometrical shape of the distributor at the branching sections are considered to be major factors affecting the heat-transfer performance. The refrigerant commonly used in these systems is HCFC-22. The two objectives of this paper are to investigate the characteristics of the refrigerant flow rate and the superheat in the evaporator of a multi-type air-conditioning system for a single or simultaneous operating conditions and to control the superheat and the refrigerant flow rate of the evaporator.

  • PDF

An Experimental Study of Operating Characteristics on Fouling Auto Removal Apparatus of Multi Pass Type Heat Exchanger using Ejector (이젝터를 이용한 다관식 열교환기 파울링 자동제거장치의 구동특성에 관한 실험적 연구)

  • Kim, J.D.
    • Journal of Power System Engineering
    • /
    • v.13 no.6
    • /
    • pp.63-69
    • /
    • 2009
  • The experiment was performed to check operating characteristics of fouling auto removal apparatus for multi pass type heat exchanger using ejector. The results showed as following. The ejector suction flow rate increased with the head of operating pump of ejector. Proper suction flow rate showed $7.2{\sim}10.2m^3/h$ for ball collection in case of pump head 35~50m. The head of ejector outlet pipe is below 4.1m in case of 40m, the head of operating pump of ejector to confirm ejector suction flow rate 8.4m3/h. Lattice space of ball separator is allowed 6~10.3mm in ranges of ball diameter are 15~25mm and when mass flow of cooling water is 3.0m/sec. Average of passing time of balls is 1.2~2.8sec depend on the velocity of flow and the size of balls.

  • PDF