• Title/Summary/Keyword: Molded case circuit breaker (MCCB)

Search Result 42, Processing Time 0.034 seconds

Design of Electromagnetic Force driving Actuator for Molded Case Circuit Breaker (배선용 차단기(MCCB) 구동용 전자석 조작기(EMFA) 설계)

  • Kim, Rae-Eun;Kang, Jong-Ho;Kwak, Sang-Yeop;Jung, Hyun-Kyo
    • Proceedings of the KIEE Conference
    • /
    • 2008.04c
    • /
    • pp.29-31
    • /
    • 2008
  • Recent years have witnessed that the Korean government prompts the 'Power IT' enterprise to combine electric Power industry with information technology (IT). Especially, in a move to shore up the distribution automation system, the necessity for remote control of molded case circuit breaker (MCCB) is getting more and more important. In this paper, we aimed to propose a remote-controlled MCCB of which the driving device is substituted to electrical equipment for mechanical parts. Driving device of MCCB was designed with the Electromagnetic Force driving Actuator (EMFA). Electromagnetic force and dynamic characteristics of the designed EMFA are analyzed using 2-D finite element method (FEM).

  • PDF

A Study on Authoritativeness of Electric Fire by Activating of Fire Damaged MCCB (소손된 배선용 차단기 동작상태에 의한 전기화재 규명의 신뢰성에 관한 연구)

  • Lee, Jong-Hwa;Mun, Yong-Soo;Kong, Ha-Sung
    • Journal of the Korea Safety Management & Science
    • /
    • v.11 no.2
    • /
    • pp.87-94
    • /
    • 2009
  • In the fire there are fusion signs and damage by fire, and insulation aging and carbonization of the electric wiring in the ignition spot because of special characteristic of the appliance in the electricity fire. Because of the physical factor applied in the damage of fire, the decision of ignition spot by eye investigation is insufficient. In this paper, the cause of electricity fire is researched. The focus is on the operation state of operated MCCB(Molded Case Circuit Breaker) at the time of electricity fire. Through grasping the operation principle of MCCB and the experiment, the state of MCCB after fire suppression is discriminated. The distinction possibility on the exist of electricity fire is proposed.

A Numerical Study on Temperature Fields in MCCB (MCCB 내의 온도장에 대한 수치적 연구)

  • Park, S.K.;Lee, Jong-Chul;Kim, Youn-J.
    • Proceedings of the KSME Conference
    • /
    • 2003.11a
    • /
    • pp.145-150
    • /
    • 2003
  • In this paper we have studied the characteristics of temperature fields in a Molded Case Circuit Breaker (MCCB). A switch and a trip device are arranged in narrow space of the MCCB. Thus, thermal factors have been risen to important problem. The temperature rise means an energy loss and it becomes the reason of fatal fault in devices. Also, the temperature rise on the connection and the contact parts is regulated up to $115^{\circ}C$ and $105^{\circ}C$, respectively. Therefore, a study for preventing the temperature rise should be investigated. A numerical analysis method that has confidence might be preceded for this purpose. In order to verify the confidence of temperature field analysis, the results of the numerical analysis are compared with those of experimental one for the same model. Comparison results show a qualitatively good agreement within ${\pm}5%$ errors.

  • PDF

Development of 460[V]/225[A]/50[kA] Contact System in Current Limiting MCCB using an estimation and analysis method for the interrupting capability (차단성능 평가해석기법을 적용한 강자계 구동방식의 460[V]/225[A]/50[kA]급 한류형 MCCB 소호부 개발)

  • 최영길;박찬교
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.18 no.1
    • /
    • pp.78-84
    • /
    • 2004
  • Low voltage circuit breakers which interrupt rapidly and raise the reliability of power supply are widely used in power distribution systems. In the paper, it has been investigated how much interrupting capability is improved by correcting the shape of the contact system in molded case circuit breaker(below MCCB), especially contacts and arc runner. Prior to the interrupting testing, it is necessary for the optimum design tc analyze electromagnetic forces on the contact system generated by current and flux density. This paper presents both our computational analysis and test results on contact system in MCCB

Methods for Increasing the Interrupting Performance of Are Chamber in 460V / 50KA / 100AF Molded Case Circuit Breaker (460V / 50KA / 100AF 급 배선용 차단기의 소호부 차단 성능 향상 방법)

  • Cho, Sung-Hoon;Jung, Eui-Hwan;Lee, Han-Ju;Lim, Kee-Joe;Kim, Kil-Sou
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2010.06a
    • /
    • pp.105-105
    • /
    • 2010
  • Voltage circuit breakers are widely used in power distribution systems to interrupt fault current rapidly and to assure the reliability of the power supply. Power distribution system requires the transformer with higher capacity than ever, but this ever, but this may be the cause. of the increasing of short circuit current in contrast to conventional one when short-circuit accident is occurred. Therefore molded case circuit breaker improved in aspects of interrupting capacity of short circuit current in this system is needed. By using the proposed methods in this paper, such as new arc quenching structure of grid would contribute to minimizing the MCCB, realization of high interrupting performance and reducing the design time and development cost.

  • PDF

A Study on the Physical Characteristics of the Low-voltage Circuit Breaker Based on the Accelerated Degradation Test (가속 열화 시험에 따른 저압용 차단기의 물리적 특성에 관한 연구)

  • Sin dong, Kang;Jae-Ho, Kim
    • Journal of the Korean Society of Safety
    • /
    • v.37 no.6
    • /
    • pp.1-8
    • /
    • 2022
  • This study analyzed the characteristics of insulation resistance and operating time based on an accelerated degradation test of a low-voltage circuit breaker. The experimental sample used a molded case circuit breaker (MCCB) and an earth leakage circuit breaker (ELCB). After measuring the insulation resistance of the circuit breakers, the leakage current was affected by an external rather than an internal structure. Furthermore, the insulation resistance of the circuit breakers with accelerated degradation was measured using a Megger insulation tester. In the accelerated degradation test, aging times of five, ten, 15, and 20 years were applied according to a temperature derived using the Arrhenius equation. Circuit breakers with an equivalent life of ten, 15, and 20 years had increased insulation resistance compared to those with less degradation time. In particular, the circuit breaker with an equivalent life of ten years had the highest insulation resistance. Component analysis of the circuit breaker manufactured through an accelerated degradation test confirmed that the timing of the increase in insulation resistance and the time of additive loss were the same. Finally, after analyzing the operating time of the circuit breakers with degradation, it was confirmed that the MCCB did not change, but the ELCB breaker failed.

Study on Measurement Method of Dielectric Recovery Voltage to analysis Dielectric Recovery Characteristic of Molded Case Circuit Breaker (저압 배선용차단기 절연회복특성 파악을 위한 절연회복전압 측정기법 연구)

  • Song, Tae-Hun;Cho, Young-Maan;Ko, Kwang-Cheol
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.29 no.8
    • /
    • pp.49-54
    • /
    • 2015
  • Molded Circucit Breaker(MCCB) is a most widely used device to protect loads from the over-current in low power level distribution system. When the MCCB interrupts the over-current, the arc discharge occurred between fixed contact and moving contact to create hot gas. By the Lorentz force due to arc current, the occurred arc is bent to the grids. The grids extend and cool and divide it for arc extinguish. In the majority cases, the MCCB protects loads by interrupting the over-current successfully but in some cases the re-ignition is occurred by hot-gas created during process of interruption. The re-ignition arises when the recovery voltage(RV) is more higher than the recovery strength between contacts and it leads to interruption fault. Therefore to find out the dielectric recovery characteristics of protecting device has a great importance for preventing interruption fault. In this paper, we studies measurement method of the dielectric recovery characteristics considering inherent attribute of the MCCB. To measure the dielectric recovery characteristic of MCCB, we makes an experiment circuit for applying the over-current and the randomly recovery voltage. The measurement methode to find out the dielectric recovery voltage of the MCCB was established and the result was based on experiment results.

신소호구조가 차단성능에 미치는 영향

  • Kim, Gil-Su;Lee, Seung-Su;Im, Gi-Jo;Gang, Seong-Hwa
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2009.11a
    • /
    • pp.227-227
    • /
    • 2009
  • To prevent such accidents, molded case circuit breakers with improved short-circuit current interrupting capacity are needed. This paper is focused on understanding the interrupting capability with respect to double contact structure and puffer assisted self quenching that are based on the shape of the contact system in the current molded case circuit breaker. The new arc quenching structure for increasing the interrupting capacity of molded case circuit breakers is investigated by simulation and experiment.

  • PDF

A Survey on the Actual Conditions of False-Tripping of MCCB ard ELB (배선용 및 누전차단기 오동작 실태조사)

  • Yoo, Jae-Geun;Lee, Sang-Ick;Jeon, Jeong-Chay;Jeong, Jong-Wook;Lim, Yong-Bae
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.11a
    • /
    • pp.223-227
    • /
    • 2004
  • False-tripping of MCCB(Molded Case Circuit Breaker) and ELB(Earth Leakage Circuit Breaker), using to protect overload and ground-fault accidents in power system raise direct and indirect losses like as information loss, facilities damage, slipup of goods production in industry place. Cause of false-tipping of MCCB and ELB is various and cause analysis of false-tripping is mostly made up by inference because trip is not reappeared. This paper investigated and analyzed causes and influences of false-tripping of MCCB and ELB by making up a question to safety managers of two hundred and eighteen electrical facilities for private use. Also, the necessity of experimental study on the effect of harmonics on false-tipping of MCCB and ELB was presented.

  • PDF

A Study on FMECA Application to Life Time Test of MCCB (배선용 차단기 수명평가를 위한 FMECA 적용 방안에 대한 연구)

  • Seo, Jung-Youl;Shin, Hee-Sang;Kim, Jae-Chul
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.2063_2064
    • /
    • 2009
  • Recently, load circuits and components of customer are various. Therefore failures of ELB(Earth Leakage Breaker) and MCCB(Molded case circuit breakers) are more frequent. Lite time of MCCB even if there is same units differ from environment, condition of operation. FEMCA is a efficiency method of system operation or maintenance for system reliability. We study on FMECA procedures and method. In this paper, we focused on FMECA application to MCCB life time test.

  • PDF