• Title/Summary/Keyword: Metal-clad switchgear

Search Result 4, Processing Time 0.017 seconds

Experimental Verification According to an Accident Model in a Metal-Clad Switchgear at 22.9kV (22.9kV 폐쇄 배전반내의 사고모델을 통한 실험적 검증)

  • Shong, Kil-Mok;Han, Woon-Ki;Choi, Chung-Seog
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.55 no.2
    • /
    • pp.110-114
    • /
    • 2006
  • This paper describes the accident analysis by modelling the current transformer mounting in a metal-clad switchgear at 22.9kV. In analyzing the accident, the reconstruction at the current transformer mounting(VCB connecting guide) has to be taken into account. The accident was modelled as a 3-phase ground fault occurring between the end plate of 22.9kV lines and the safety shutter at the current transformer mounting of the VCB inside the metal clad switchgear. Since the outside maintenance of the metal clad switchgear is restricted by the enclosed compartments, Its circumference has to be kept clean. Through the reconstruction results, it was confirmed that the fault of the enclosed switchboard could be reduced when the shutter made of Fe material was chanted into an insulation.

Accident Risk Assessment between Power Cable Head and Safety Shutter in Medium Voltage Metal-Clad Switchgear (고압폐쇄분전반의 전력케이블 헤드와 안전셔터에서의 사고위험 평가)

  • Shong, Kil-Mok;Han, Woon-Ki;Kim, Young-Seok
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2006.05a
    • /
    • pp.264-267
    • /
    • 2006
  • This paper describes the accident analysis by modeling the current transformer mounting in meaium voltage metal-clad switchgear(MCSG). In analyzing the accident the reconstruction at the current transformer mounting(VCB connecting guide) has to be taken into account. The accident was modelled as a 3-phase ground fault mounting between the end plate of a high voltage lines and the safety shutter at the current transformer mounting of the VCB inside the metal clad switchgear. Since the outside maintenance of the metal clad switchgear is restricted by the enclosed compartments, its circumference has to be kept clean. Through the reconstruction results, it was confirmed that the fault of the enclosed switchboard could be reduced when the shutter made of Fe material was changed into an insulation.

  • PDF

A Study on the Diagnostic Method for Fault Prevention Of Metal Clad Switchgear Using Electromagnetic Detection Techniques (전자파 측정을 이용한 폐쇄 배전반의 사고예방진단 기법에 관한 연구)

  • 김재철;서인철;김영노;전영재
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.16 no.5
    • /
    • pp.29-37
    • /
    • 2002
  • This paper presents the diagnostic method for fault prevention in metal clad switchgear(MCS) through comparison of signals before and after detecting the partial discharge using electromagnetic detection technique. Electromagnetic waves detected by antennas of the inside and outside of MCS are analyzed and compared by frequency spectrum analysis method which can estimate an insulation abnormality and normality of MCS. As a result of the experiment by the proposed method, we can detect the insulation abnormality as partial discharge in MCS and these results can be applied to preventive diagnosis of MCS.

Detection of partial Discharge in the Metal Clad Switchgear Using the Electromagnetic Technique (전자파 측정기법을 이용한 폐쇄 배전반내 부분방전 검출)

  • Seo, In-Chul;Kim, Jae-Chul;Kim, Young-No;Jeon, Young-Jae
    • Proceedings of the KIEE Conference
    • /
    • 2001.11b
    • /
    • pp.403-405
    • /
    • 2001
  • This paper presents the detection method of partial discharge in metal clad switchgear(MCS) using electromagnetic technique. Two antennas are located in the inside and outside of the MCS, and electromagnetic waves detected by these antennas are analyzed and compared by FFT method in order to identify an insulation abnormality. As a result of the experiment by the proposed method, we show the detection possibility for partial discharge in the MCS. The proposed method is expected to apply to insulation condition observation and an accident prevention in the MCS effectively.

  • PDF