• Title/Summary/Keyword: Megger

Search Result 12, Processing Time 0.035 seconds

A Study on Site Application Techniques for Insulation Reliability of Rotating Machine (고압회전기 절연열화진단의 현장적용기술연구)

  • Kim, K.Y.;Jo, K.H.;Kim, T.S.;Han, S.O.;Lee, H.S.
    • Proceedings of the KIEE Conference
    • /
    • 1991.07a
    • /
    • pp.286-291
    • /
    • 1991
  • Most of the failures of rotating machine are stator coil insulation failures. The insulation diagnostic testing for high voltage motors and generators are only megger test and P. I Test which is applied DC voltage until now. But it was impossible to judge insulation deterioration status of high voltage rotating machinery by above testing. In other words, even though the megger measurement values are fairly high, they used to be failed from time to time. Therefore in order to excute reliable and detailed diagnosis of insulation deterioration for rotating machinery, the tangent delta test, the alternating current test and the partial discharge test shall be applied to the insulation diagnostic testing on site.

  • PDF

절연시험논고

  • 노은래
    • 전기의세계
    • /
    • v.16 no.2
    • /
    • pp.39-46
    • /
    • 1967
  • 절연시험방법은 여러가지 있으나 이들은 공장에서 또는 특수한 시설을 갖추지 않고는 어려운 경우가 대부분이므로 이에 현장에서 또는 연재 전력을 사용하는 공장및 발변전소가 갖이고 있는 계측기류와 절연시험기(megger)등을 사용하여 발전기 전동기등의 절연의 절연물에 대한 절연도및 cable과 고압 Bushing의 절연도를 결정하므로써 예방설비의 실효를 거두어 전기기기관리의 적정을 기하기 위하여 그 기술과 방법을 고안검토하고져 한다.

  • PDF

Study on Development of the Isolation Resistance Measurement System for Hydrogen Fuel Cell Vehicle (수소연료전지자동차용 절연저항 측정시스템 개발에 관한 연구)

  • Lee, Ki-Yeon;Kim, Dong-Ook;Moon, Hyun-Wook;Kim, Hyang-Kon
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.5
    • /
    • pp.1068-1072
    • /
    • 2011
  • Hydrogen Fuel Cell Vehicle(HFCV) is system that uses electrical energy of fuel cell stack to main power source, which is different system with other vehicles that use high-voltage, large-current. Isolation performance of this system which is connected with electrical fire and electrical shock is important point. Isolation resistance of electric installation is divided according to working voltage, it follows criterion more than $100{\Omega}$/VDC (or $500{\Omega}$/VAC) about system operation voltage in a hydrogen fuel cell vehicle. Although measurement of isolation resistance in a hydrogen fuel cell vehicle is two methods, it uses mainly measurement by megger. However, the present isolation resistance measurement system that is optimized to use in electrical facilities is unsuitable for isolation performance estimation of a hydrogen fuel cell vehicle because of limit of maximum short current and difference of measurement resolution. Therefore, this research developed the isolation resistance measurement system so that may be suitable in isolation performance estimation of a hydrogen fuel cell vehicle, verified isolation performance about known resistance by performance verification of laboratory level about developed system, and executed performance verification through comparing results of developed system by performance verification of vehicle level with ones of existing megger. Developed system is judged to aid estimation and upgrade of isolation performance in a hydrogen fuel cell vehicle hereafter.

Design of Diagnosis System for Insulation Degradation of Motor by using Electromagnetic Wave(2) (전자파를 이용한 전동기 절연열화 진단시스템의 설계(2))

  • 유권종;김이곤
    • Proceedings of the Korean Institute of Information and Commucation Sciences Conference
    • /
    • 2000.10a
    • /
    • pp.677-682
    • /
    • 2000
  • 본 연구는 전동기의 부분방전에 의해 발생되는 전자파를 측정하여 전동기의 열화상태를 진단할 수 있는 진동기 절연열화 진단시스템을 설계하였다. 청장 전동기에서 부분방전에 의한 전자파를 on-line으로 측정하고, 측정된 데이터로부터 정량화된 특징 데이터를 추출한 후 전자파의 평균 에너지 분포를 이용하여 전동기의 절연열화 상태를 판단하는 방법을 제시하였으며, 현장에서 사용 중인 Megger시험과 비교하였다.

  • PDF

주요송배전시설에 대한 절연열화진단

  • 전춘생
    • 전기의세계
    • /
    • v.25 no.6
    • /
    • pp.55-59
    • /
    • 1976
  • 송전시설의 주요한 부분을 점하고 있는 변압기, Bushing 및 전력 Cable등에 대한 종래의 절연열화의 판정방법으로서 Megger 시험, 직류분시험등의 비파괴시험등에 여러가지 형태로 실시되고 있다. 이와같은 시험결과에서 절연물이 어떤 상태에 있는가를 확실하게 알 수 있지만 그 수명까지는 정확하게 알 수 있는 단계까지는 도달하지 못하고 있다. 따라서 전력기기의 보수관리방식으로써 새로 도입된 생산보전이라는 면에서 절연진단을 새로운 각도에서 보더라도 100% 완전한 방법을 얻는다는 것은 현재로는 곤란한 일이다. 그러나 다음에 기술하는 진단방법을 적절히 생산보전의 면에 도입하여 보수관리를 하면 점차적으로 그 효과가 좋은 실적으로 나타날 것으로 기대하여 이 분야에 관계하는 분들에게 다소나마 도움이 된다는 생각으로 현행의 절연열화진단법을 소개한다.

  • PDF

Example study of the dissipation factor change according to the oil filtering in large oil-filled transformer (유입변압기 오일필터링에 따른 유전정접 변화사례 고찰)

  • Kong, Tae-Sik;Kim, Hee-Dong
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.2035_2036
    • /
    • 2009
  • This paper is purpose to understand the dissipation factor properties of the oil-filled large transformer according to the oil filtering. In order to know the insulation characteristic change by insulating oil filtering, we carried out the insulation diagnostic test for the same transformer before oil filtering and after. The insulation diagnosis tests are consist of the megger, the polarization index, the AC current test, the dissipation factor test and the partial discharge test, Especially we took notice of dissipation factor change, we analyzed and made a comparison of the two cases test result.

  • PDF

Example study of the insulation characteristic change according to the dryness condition in high voltage motor stator winding (고압전동기 고정자권선의 건조상태에 따른 절연특성 변화사례 고찰)

  • Kong, Tae-Sik
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.2056-2057
    • /
    • 2008
  • This paper is purpose to understand the insulation properties of the high voltage motor stator winding according to the different dryness conditions. we carried out the three times insulation diagnosis test for the same motor stator winding. the first test object is the contaminated winding, second is the washed-out, and natural dried during the 24 hours, and the last is the heating dried in 110$^{\circ}C$ during the 48 hours. the insulation diagnosis tests are consist of the megger, the polarization index, the AC current test, the dissipation factor test and the partial discharge test, we analyzed and made a comparison of the three cases test result.

  • PDF

Study on the Evaluation Method of Electrical Isolation Property for Hydrogen Fuel Cell Vehicle (수소연료전지자동차의 절연성능 평가방법에 관한 고찰)

  • Lee, Ki-Yeon;Kim, Dong-Ook;Kim, Hyang-Kon
    • Transactions of the Korean hydrogen and new energy society
    • /
    • v.22 no.6
    • /
    • pp.810-818
    • /
    • 2011
  • This paper analyzed the suitability about the isolation performance criteria which was based on human impedance and effect of current in IEC 60479-1 on the safety of human being was examined. The method of evaluation by megger and DC voltmeter was analyzed. The differences of isolation performance according to design of high-voltage system were analyzed. The factors which affect the insulation performance were analyzed for HFCV, EV, HEV, etc. through analysis of the isolation performance evaluation method. Finally, design for improved isolation performance was proposed.

A Study on the Physical Characteristics of the Low-voltage Circuit Breaker Based on the Accelerated Degradation Test (가속 열화 시험에 따른 저압용 차단기의 물리적 특성에 관한 연구)

  • Sin dong, Kang;Jae-Ho, Kim
    • Journal of the Korean Society of Safety
    • /
    • v.37 no.6
    • /
    • pp.1-8
    • /
    • 2022
  • This study analyzed the characteristics of insulation resistance and operating time based on an accelerated degradation test of a low-voltage circuit breaker. The experimental sample used a molded case circuit breaker (MCCB) and an earth leakage circuit breaker (ELCB). After measuring the insulation resistance of the circuit breakers, the leakage current was affected by an external rather than an internal structure. Furthermore, the insulation resistance of the circuit breakers with accelerated degradation was measured using a Megger insulation tester. In the accelerated degradation test, aging times of five, ten, 15, and 20 years were applied according to a temperature derived using the Arrhenius equation. Circuit breakers with an equivalent life of ten, 15, and 20 years had increased insulation resistance compared to those with less degradation time. In particular, the circuit breaker with an equivalent life of ten years had the highest insulation resistance. Component analysis of the circuit breaker manufactured through an accelerated degradation test confirmed that the timing of the increase in insulation resistance and the time of additive loss were the same. Finally, after analyzing the operating time of the circuit breakers with degradation, it was confirmed that the MCCB did not change, but the ELCB breaker failed.

Relationship Between Humidity and Insulation Status of XLPE 6.6kV Cables for the Load of Electric Turbine Generator (터빈 발전기 부하용 XLPE 6.6kV 케이블의 절연층 절연상태와 습도의 상관관계)

  • Um, Kee-Hong
    • The Journal of the Institute of Internet, Broadcasting and Communication
    • /
    • v.16 no.5
    • /
    • pp.185-190
    • /
    • 2016
  • The high-power 6.6 kV XLPE (or CV) cables at Korean electric power stations have been in operation for the last 40 years. Most of the XLPE cables starts deteriorating in 6-8 years from the operating instant of time, some cables may be breakdown at any moment even though they were installed in recent years, causing, huge socioeconomic losses. In order to prevent unexpected cable accident, the operating status of power cables should be monitored in regularly, timely bases. We have invented a device in order to systematically monitor and prevent an abrupt accidents of high-power cables in operation at power station. It has been installed at Korean Western Power Co. Ltd. at Taean, and operating normally for the last 4 years. In this paper, we introduce the functions and operating principles of the measuring device, and present the relationship between humidity and insulation status of XLPE cables for the load of electric turbine generator.