• Title/Summary/Keyword: Main Power Transformer

Search Result 192, Processing Time 0.023 seconds

A wide ZVS range two-transformer active-clamp forward converter with low conduction loss (낮은 도통손실을 가지며 넓은 영전압 스위칭 범위를 갖는 두 개의 변압기를 이용한 능동 클램프 포워드 컨버터)

  • Moon Sang-Cheol;Park Ki-Bum;Moon Gun-Woo;Youn Myung-Joong
    • Proceedings of the KIPE Conference
    • /
    • 2006.06a
    • /
    • pp.369-371
    • /
    • 2006
  • Conventional active-clamp forward converter has narrow ZVS range of main switch. Although utilizing high magnetizing current can realize wide ZVS range, it increases the conduction loss. To solve this problem, a new asymmetric two-transformer active clamp forward converter is proposed. Proposed converter achieves wide ZVS range without severe conduction loss penalty, which results in high efficiency and high power density.

  • PDF

A Study on Design of Intelligent Electronic Device(IED) for Power Transformer (전력용 변압기를 위한 IED 설계에 관한 연구)

  • Park, C.W.;Koo, C.S.;Cho, Y.I.;Park, S.W.;Shin, M.C.;Park, J.S.
    • Proceedings of the KIEE Conference
    • /
    • 2003.07a
    • /
    • pp.268-270
    • /
    • 2003
  • This paper proposes a software design and hardware implementation of Intelligent Electronic Device(IED) for power transformer. The relaying algorithm is based on DFT. The protection functions implemented include RDR with a second harmonic restraint for magnetizing inrush, OCR, OCGR, OVR, and UVR etc. The main board of IED is based on the TMS32C32 Processor. The IED was tested with relaying signals obtained for EMTP simulation package.

  • PDF

Development of the Power Supply with Reduced Conduction Loss and Switching Stress on the Full-Bridge DC-DC Converter (풀브리지 DC-DC 컨버터의 도전손실과 스위칭 스트레스를 저감한 전원장치 개발)

  • Ra Byung-Hun;Song Dae-Hyun;Kim Kwang-Tae;Lee Hyun-Woo
    • Proceedings of the KIPE Conference
    • /
    • 2001.07a
    • /
    • pp.608-611
    • /
    • 2001
  • This paper is indicating the problems, which are the conduction loss on the high frequency transformer, the protection of rectification diode as the snubber loss and the stress of switching main devices, as be made high current and high speed in the phase-shift switching full-bridge DC-DC converter is used the power supply's main circuit of high capacity. In this paper, to improve those problems, it is proposed that is the resonant circuit auxiliary can be reduced conduction losses and stabilized output control. And, it is constructed prototype of the power supply as the result of computer simulations.

  • PDF

A study on the cause Analysis and solution of an overheated NGR of the Main Transformer (변압기 중성점 접지리액터 과열원인분석 및 해소방안에 관한 연구)

  • Park, Gil-Soo;Park, Soo-Hong
    • The Journal of the Korea institute of electronic communication sciences
    • /
    • v.6 no.2
    • /
    • pp.262-267
    • /
    • 2011
  • In the power system, the transformer's neutral earth reactor line 1 grounding failure may occur. By limiting the magnitude of the failure grounding current flow, it will aid to reduce the failure of the transformer. Consequently, this also may avoid the failure of the disconnection of the industrial insulator line that cause by melting. Besides, utilizing the decreasing circuit breaker or others related equipment can use to avoid the possibility of explosion of the transformer. If the failure happen during the operation of the power system, a huge interference will definitely may occur. Therefore, by installing the DONGBUSAN S/S #3M.Tr neutral earth reactor among TOP and BOTTOM BRACE part in the power system, the causes of the rising temperature and reason of the over-current flow that cause by over-current can be analyze.

Method to Prevent the Malfunction Caused by the Transformer Magnetizing Inrush Current using IEC 61850-based IEDs and Dynamic Performance Test using RTDS Test-bed

  • Kang, Hae-Gweon;Song, Un-Sig;Kim, Jin-Ho;Kim, Se-Chang;Park, Jong-Soo;Park, Jong-Eun
    • Journal of Electrical Engineering and Technology
    • /
    • v.9 no.3
    • /
    • pp.1104-1111
    • /
    • 2014
  • The digital substations are being built based on the IEC 61850 network. The cooperation and protection of power system are becoming more intelligent and reliable in the environment of digital substation. This paper proposes a novel method to prevent the malfunction caused by the Transformer Magnetizing Inrush Current(TMIC) using the IEC 61850 based data sharing between the IEDs. To protect a main transformer, the current differential protection(87T) and over-current protection(50/51) are used generally. The 87T IED applies to the second harmonic blocking method to prevent the malfunction caused by the TMIC. However, the 50/51 IED may malfunction caused by the TMIC. To solve that problem, the proposed method uses a GOOSE inter-lock signal between two IEDs. The 87T IED transmits a blocking GOOSE signal to the 50/51 IED, when the TMIC is detected. The proposed method can make a cooperation of digital substation protection system more intelligent. To verify the performance of proposed method, this paper performs the real time test using the RTDS (Real Time Digital Simulator) test-bed. Using the RTDS, the power system transients are simulated, and the TMIC is generated. The performance of proposed method is verified in real-time using that actual current signals. The reaction of simulated power system responding to the operation of IEDs can be also confirmed.

Magnetostriction Modeling for the Analysis of Electromagnetically Induced Vibration of Transformers (전자기력에 의해 유도된 변압기의 진동 해석을 위한 자왜 현상 모델링)

  • Yoo, Seong-Yeol;Lee, Jun-Sin;Lee, Uk-Ryun;Noh, Myoung-Gyu
    • Journal of the Korean Society for Precision Engineering
    • /
    • v.25 no.1
    • /
    • pp.108-114
    • /
    • 2008
  • Recently, there have been several instances that the nuclear power plants were shut down due to the mechanical faults in the main transformer of the plants. These mechanical faults are primarily originated from the electromagnetically induced mechanical vibrations. Magnetostriction is identified to be the main cause of the mechanical vibration after analyzing the vibration data of the main transformers in nuclear power plants. In this study, we derived a mathematical model of the magnetostriction based on the Jiles-Atherton hysteresis model. The validity of the model is checked by matching the simulations with the experimental observations. The magnetostriction model used in this study will be the first step toward developing a design tool far the transformers that have minimal mechanical vibrations and are robust to mechanical faults.

New Battery Balancing Circuit using Magnetic Flux Sharing

  • Song, Sung-Geun;Park, Seong-Mi;Park, Sung-Jun
    • Journal of Power Electronics
    • /
    • v.14 no.1
    • /
    • pp.194-201
    • /
    • 2014
  • To increase the capacity of secondary cells, an appropriate serial composition of the battery modules is essential. The unbalance that may occur due to the series connection in such a serial composition is the main cause for declines in the efficiency and performance of batteries. Various studies have been conducted on the use of a passive or active topology to eliminate the unbalance from the series circuit of battery modules. Most topologies consist of a complex structure in which the Battery Management System (BMS) detects the voltage of each module and establishes the voltage balancing in the independent electrical power converters installed on each module by comparing the module voltage. This study proposes a new magnetic flux sharing type DC/DC converter topology in order to remove voltage unbalances from batteries. The proposed topology is characterized by a design in which all of the DC/DC convertor outputs connected to the modules converge into a single transformer. In this structure, by taking a form in which all of the battery balancing type converters share magnetic flux through a single harmonic wave transformer, all of the converter voltages automatically converge to the same voltage. This paper attempts to analyze the dynamic properties of the proposed circuit by using a Programmable Synthesizer Interface Module (PSIM), which is useful for power electronics analysis, while also attempting to demonstrate the validity of the proposed circuit through experimental results.

Zero-Voltage and Zero-Current Switching Interleaved Two-Switch Forward Converter

  • Chu, Enhui;Bao, Jianqun;Song, Qi;Zhang, Yang;Xie, Haolin;Chen, Zhifang;Zhou, Yue
    • Journal of Power Electronics
    • /
    • v.19 no.6
    • /
    • pp.1413-1428
    • /
    • 2019
  • In this paper, a novel zero-voltage and zero-current switching (ZVZCS) interleaved two switch forward converter is proposed. By using a coupled-inductor-type smoothing filter, a snubber capacitor, the parallel capacitance of the leading switches and the transformer parasitic inductance, the proposed converter can realize soft-switching for the main power switches. This converter can effectively reduce the primary circulating current loss by using the coupled inductor and the snubber capacitor. Furthermore, this converter can reduce the reverse recovery loss, parasitic ringing and transient voltage stress in the secondary rectifier diodes caused by the leakage inductors of the transformer and the coupled inductance. The operation principle and steady state characteristics of the converter are analyzed according to the equivalent circuits in different operation modes. The practical effectiveness of the proposed converter was is illustrated by simulation and experimental results via a 500W, 100 kHz prototype using the power MOSFET.

Development of a Topology for the Power Supply with Reduced Conduction Loss and Swithing Stress (도전손실과 스위칭 스트레스 저감한 전원장치 토폴로지의 개발)

  • 라병훈;권순걸;이현우
    • Proceedings of the IEEK Conference
    • /
    • 2001.06e
    • /
    • pp.245-248
    • /
    • 2001
  • This paper is indicating the problems, which are the conduction loss on the high frequency transformer, the protection of rectification diode as the snubber loss and the stress of switching main devices, as be made high current and high speed in the phase-shift switching full-bridge DC-DC converter is used the power supply’s main circuit of high capacity. To improve those problems, in this paper, it is proposed that is the resonant circuit auxiliary can be reduced conduction losses and stabilized output control. And, it is constructed prototype of the power supply as the result of computer simulations.

  • PDF

154kV Main TR. Bay IED Based On IEC 61850 (IEC 61850 기반의 154kV M.Tr Bay IED 적용 사례)

  • Roh, Jae-Keun;Oh, Jae-Hoon;Yang, Hang-Jun
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.11
    • /
    • pp.2028-2034
    • /
    • 2011
  • Substation Automation System (SAS) based on IEC 61850 is becoming more and more reality in applying power systems. As well, the development of various engineering tools and the convergence with diagnostic systems are underway. To reflect recent advancements in SAS technology, the Korea Electric Power Corporation initiated a 154kV SAS pilot project and a smart power grid business in 2010. In this paper, the authors will summarize the overview and the lessons learned in applying the IEC 61850-based 154kV Main transformer bay IED solutions to these two project.