Improvement on Property of Insulation in PT of Epoxy Mold Type (에폭시 몰드형 PT의 절연특성 개선)

  • Song, Jae-Joo;Kim, Sung-Hong;Choi, Myeong-Ho;Lee, Jae;Lim, Sung-Hun;Han, Byung-Sung
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.09a
    • /
    • pp.67-71
    • /
    • 2001
  • PT of epoxy mold type have tendency to occur dielectric breakdown in high voltage system. These are using for measurement of voltage or protection of system and application voltage is 25.8kV. Therefore, for improving a lots of problems like as partial discharge, we had analyze on the destroyed Epoxy molded type PT and processing of production. As a results, we concluded that the reason of dielectric breakdown was defect of processing and degradation of insulation by electrical stress. In this work, We presented a method of solution in processing of production. which is reduction of the PO which was occurred at the insulation material. so we must many try to remove faults, these problems are mainly to winding methods of 1st coil. the other side, Reformation of 1st coil improved property of PD and we could prove it with experiments.

  • PDF

Accident Risk Assessment between Power Cable Head and Safety Shutter in Medium Voltage Metal-Clad Switchgear (고압폐쇄분전반의 전력케이블 헤드와 안전셔터에서의 사고위험 평가)

  • Shong, Kil-Mok;Han, Woon-Ki;Kim, Young-Seok
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2006.05a
    • /
    • pp.264-267
    • /
    • 2006
  • This paper describes the accident analysis by modeling the current transformer mounting in meaium voltage metal-clad switchgear(MCSG). In analyzing the accident the reconstruction at the current transformer mounting(VCB connecting guide) has to be taken into account. The accident was modelled as a 3-phase ground fault mounting between the end plate of a high voltage lines and the safety shutter at the current transformer mounting of the VCB inside the metal clad switchgear. Since the outside maintenance of the metal clad switchgear is restricted by the enclosed compartments, its circumference has to be kept clean. Through the reconstruction results, it was confirmed that the fault of the enclosed switchboard could be reduced when the shutter made of Fe material was changed into an insulation.

  • PDF