• 제목/요약/키워드: MCCB

검색결과 93건 처리시간 0.031초

저압 배선용차단기 절연회복특성 파악을 위한 절연회복전압 측정기법 연구 (Study on Measurement Method of Dielectric Recovery Voltage to analysis Dielectric Recovery Characteristic of Molded Case Circuit Breaker)

  • 송태헌;조영만;고광철
    • 조명전기설비학회논문지
    • /
    • 제29권8호
    • /
    • pp.49-54
    • /
    • 2015
  • Molded Circucit Breaker(MCCB) is a most widely used device to protect loads from the over-current in low power level distribution system. When the MCCB interrupts the over-current, the arc discharge occurred between fixed contact and moving contact to create hot gas. By the Lorentz force due to arc current, the occurred arc is bent to the grids. The grids extend and cool and divide it for arc extinguish. In the majority cases, the MCCB protects loads by interrupting the over-current successfully but in some cases the re-ignition is occurred by hot-gas created during process of interruption. The re-ignition arises when the recovery voltage(RV) is more higher than the recovery strength between contacts and it leads to interruption fault. Therefore to find out the dielectric recovery characteristics of protecting device has a great importance for preventing interruption fault. In this paper, we studies measurement method of the dielectric recovery characteristics considering inherent attribute of the MCCB. To measure the dielectric recovery characteristic of MCCB, we makes an experiment circuit for applying the over-current and the randomly recovery voltage. The measurement methode to find out the dielectric recovery voltage of the MCCB was established and the result was based on experiment results.

460[V]/400[A]/85[kA] 배선용 차단기의 아크런너 변형을 통한 차단성능 향상 (Improvement of Short Circuit Performance in 460[V]/400{A]/85(kA] Molded Case Circuit Breakers)

  • 이승수;허준;윤재훈;강성화;임기조
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2009년도 하계학술대회 논문집
    • /
    • pp.394-394
    • /
    • 2009
  • Owing to the increasing number of intelligent homes(or called Smart home), the corresponding cost is much higher. Low voltage circuit breakers are widely used in the intelligent homes to interrupt fault current rapidly and to assure the reliability of the power supply. The distribution of magnetic field induced by arc current in the contact system of molded case circuit breaker(hereafter MCCB) depends on the shape, arrangement, and kinds of material of arc runner. This paper is focused on understanding the interrupting capability, more specifically of the arc runner, based on the shape of the contact system in the current MCCB. The magnetic driving force was calculated by using the flux densities induced by the arc current, which are obtained by three-dimensional finite element method. There is a need to assure that the optimum design required to analyze the electromagnetic forces of the contact system generated by current and the flux density be present. This is paper present our computational analysis on contact system in MCCB.

  • PDF

저압 배전선로의 누전 및 배선용 차단기의 오동작 방지를 위한 고속형 전기안전 보호장치 (Electric Safety Protection Device of High Speed for Incapable Operation of ELB and MCCB Using the Low Voltage Distribution Line)

  • 곽동걸;정도영
    • 전기학회논문지
    • /
    • 제56권11호
    • /
    • pp.1925-1929
    • /
    • 2007
  • This paper is studied on a novel Electric Safety Protection Device (ESPD) of high speed for incapable operation of Earth Leakage Circuit Breaker (ELB) and Molded_case Circuit Breaker (MCCB) using the low voltage distribution line. The major causes of electrical fire are classified to short circuit fault, overload fault, electric leakage and electric contact failure. The occurrence factor of the fire is electric arc or spark accompanied with electrical faults. Residual Current Protective Device (RCD), that is ELB and MCCB, of high sensitivity type used at low voltage wiring cuts off earth leakage and overload, but the RCD can't cut off electric arc or spark to be a major factor of electrical fire. As the RCDs which are applied low voltage distribution panel are prescribed to rated breaking time about 30[ms] (KS C 4613), the RCDs can't perceive to the periodic electric arc or spark of more short wavelength level. To be improved on such problem, this research development is proposed to a novel ESPD of high speed to trip of distribution line on electric arc or spark due to electrical fire. Some experimental results of the proposed ESPD are confirmed to the validity of the analytical results.

온도상승에 따른 배선용 차단기의 동작특성에 관한 연구 (A Study on the Operating Characteristics of Molded Case Circuit Breakers according to Temperature Rise)

  • 정다운;김재호
    • 한국안전학회지
    • /
    • 제30권5호
    • /
    • pp.8-13
    • /
    • 2015
  • Molded Case Circuit Breakers (MCCBs) are typically used to provide over current protection for electrical safety caused by short circuit faults and overloads in indoor low voltage power systems. The MCCB automatically connects and disconnects loads from the electrical source when the current reaches a value and duration that will cause an excessive. However, the MCCB sometimes is not interrupted due to a malfunction, nuisance tripping, or in a fire. Ensuring electrical safety is very important in a indoor low voltage power system. This paper presents the operating characteristics of MCCBs according to a temperature rise from room temperature to 160 degrees Celsius delivered by a radiant panel heater. The ABS 54c(rated current: 30A) of the hydraulic magnetic trip type was used in the experiments. The signals of temperature, voltage, and current were measured using the high accuracy Signal Conditioning Extensions for Instrumentation (SCXI) measurement system with the LabVIEW program manufactured by National Instruments. The operating characteristics were measured as functions of current amplitude and ramp-up rate. The MCCB tripping time decreased as a result of increasing current amplitude and ramp-up rate under a temperature rise condition, because the temperature and level of the current are directly proportional to the tripping time. Additionally, an instantaneous operation was observed after 8 times of the rated current, and the MCCB began to melt a surface temperature of around 300 degrees Celsius of. The experimental results coincided well with the operating curve.

225[AF]/200[A]/50[kA] 배선용 차단기 고정자 변화를 통한 차단용량 향상

  • 이승수;윤재훈;정의환;임기조;강성화
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2009년도 추계학술대회 논문집
    • /
    • pp.221-221
    • /
    • 2009
  • This paper is focused on understanding the interrupting capability, more specifically of the fix contact, based on the shape of the contact system in the current MCCB. The magnetic driving force was calculated by using the flux densities induced by the arc current, which are obtained by three-dimensional finite element method. There is a need to assure that the optimum design required to analyze the electromagnetic forces of the contact system generated by current and the flux density be present. This is paper present our computational analysis on contact system in MCCB.

  • PDF

460[V]/400[A]/85[kA] 한류형 배선용 차단기 소호부 해석 (Analysis of Contact System in 460[V]/400[A]/85[kA] Molded Case Circuit Breakers)

  • 이승수;허준;윤재훈;강성화;임기조
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2008년도 추계학술대회 논문집 Vol.21
    • /
    • pp.364-365
    • /
    • 2008
  • 배선용 차단기(MCCB)는 신속한 고장전류 차단과 전원시스템의 안정성을 확보하기 위해 배선시스템에 폭넓게 사용되고 있다. 배선용 차단기(MCCB)는 과부하 및 단로 등의 이상 상태시 전류를 차단하는 기구로, 오작동 시에는 중대한 사고를 초래한다. 따라서 배선용 차단기에 대한 보호성능의 항상, 신뢰성의 향상의 시장요구에 부응하기 위해 본 논문에서는 소호부 형상에 따른 차단성능을 파악하고 이를 통하여 성능향상을 이루고자 3차원 유한요소 프로그램(MAX-WELL)을 이용한 자계해석을 통해 차단성능 평가를 하였다. 이를 통하여 배선용 차단기의 소호부 설계시 차단성능 검증과 제품의 소형화 및 고성능화를 이끌고자 한다.

  • PDF

배선용 차단기의 전자 반발력에 관한 연구 (Analysis of Electromagnetic Repulse Forces of MCCB)

  • 김길수;임기조;강성화;조현길
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 추계학술대회 논문집 Vol.14 No.1
    • /
    • pp.593-596
    • /
    • 2001
  • It is necessary for calculation of repulsion forces acting on the closed electric contacts flowing over-current. e.g. inrush current and overload currents, to do optimum design of switching devices. In this paper. the forces and flux densities generated by currents at the contact point when circuit breakers are in closed state are obtained by using 3D finite element methode. To be convinced of the results, we measure electrogmanetic repulsion forces on contacts by measuring voltage between opened contacts in MCCB

  • PDF

Simple Analysis Method for the Interrupting Capability of a Contact System in a Molded Case Circuit Breaker

  • Choi, Young-Kil;Jee, Seung-Wook
    • Journal of Electrical Engineering and Technology
    • /
    • 제12권3호
    • /
    • pp.1257-1261
    • /
    • 2017
  • This paper focuses on understanding the interrupting capability of an arc contact system in a molded case circuit breaker (hereafter MCCB). We selected four types of MCCBs and analyzed the magnetic flux density distributions in the contact systems caused by the fault currents. We ascertained that the magnetic flux density profile varies according to the shape of the contact system and was asymmetric at both the ends of an arc, perpendicular to the arc column because of the magnetic grid installed in the contact system. The asymmetric difference creates a magnetic force that pushes the arc current outwards and provides an interrupting capability. We have introduced a simple analysis method for determining the interrupting capability of the contact system for an MCCB by the arc-driving magnetic flux density.

배선용차단기의 구동자계 증가를 위한 자성체 구조물의 와전류 해석 (Eddy Current Analysis of Magnetic Plate to Increase Magnetic Force in MCCB)

  • 이세연;백명기;이보람;김영선;박일한
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.909-910
    • /
    • 2007
  • To design the Molded Case Circuit Breaker(MCCB) requires electromagnetic analysis in contact system when the circuit breakers interrupt fault currents. This paper has made sure that there are two ways increasing arc driving force, one is a change of contact point and the other way inserts additionally the magnetic plate. Finally, we have carried out the analysis of eddy current to identify a decrease of arc driving force because of fault currents. In this paper, MCCB models have been analyzed base on 3D-FEM by Maxwell program.

  • PDF

3D FEM해석을 통한 배선용 차단기의 전자반발력 해석 (Magnetic Repulsion Forces in MCCB by 3-D FEM Analysis)

  • 송중천;유만종;김용기
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 하계학술대회 논문집 B
    • /
    • pp.711-713
    • /
    • 2001
  • MCCB(Molded Case Circuit Breakers) is a multi-function safety device which, unlike other forms of protection, combines many protection features in a single unit. This paper is the analysis of magnetic repulsion forces with the breaking current 11.28kA, 22.5kA, 38.9kA and 45kA.

  • PDF