Plate fin-oval tube 열교환기에서 와류발생체에 의한 fin 표면에서의 국소 열전달 특성 (Local Heat Transfer Characteristics on Fin Surface of Plate Fin - Oval Tube with Delta Wing Vortex Generators)

  • 신석원;정인기;김수연
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2007년도 춘계학술대회B
    • /
    • pp.2390-2395
    • /
    • 2007
  • The present research was experimentally performed to analyze the effect of delta-wing vortex generators(DWVG) on the heat transfer of fin surface of the plate fin-oval tube. The local heat transfer coefficient of the fin surface for four kinds of DWVG's arrangement was measured by the naphthalene sublimation technique for Reynolds numbers ranging from 2000 to 3200. The results showed that the heat transfer of the plate fin-oval tube can be significantly enhanced by DWVG for relatively low Reynolds numbers.

  • PDF

다양한 표면에서 유동 속도에 따른 풀 비등 열전달에 관한 연구 (Study of Pool Boiling Heat Transfer on Various Surfaces with Variation of Flow Velocity)

  • 강동규;이요한;서훈;정동수
    • 대한기계학회논문집B
    • /
    • 제37권4호
    • /
    • pp.343-352
    • /
    • 2013
  • 본 연구에서는 열전달 표면의 형상과 그 위에서의 유동 속도의 변화에 따른 풀 비등 열전달계수의 변화를 살펴보기 위해 평판, 낮은 핀, Thermoexcel-E, Turbo-B 표면을 사용하여 유동 속도를 변화시켜가며 임계 열유속까지 열전달계수를 측정하였다. 작동 유체로는 증류수를 사용하였고 사각 평면 히터($9.53{\times}9.53mm$)를 이용하여 네 가지 표면에서 임계 열유속까지의 데이터를 얻을 수 있도록 장치를 제작하였고 $60^{\circ}C$에서 유동 속도를 0, 0.1, 0.15, 0.2m/s로 변화시켜가며 데이터를 취했다. 실험 데이터를 보면 모든 표면에서 유동이 있을 때의 임계 열유속은 유동이 없을 때에 비해 높은 것으로 나타났다. 또한 표면적의 증가와 기포 이탈에 충분한 핀 간격 등으로 인해 낮은 핀 표면의 임계 열유속은 평판이나 Turbo-B, Thermoexcel-E 표면보다 훨씬 놓았고 평판에 비해서는 무려 5배 정도의 향상을 보였다. 한편 대형 냉동기의 증발기용으로 개발된 Turbo-B와 Thermoexcel-E 표면은 물에서 기포의 이탈 지름이 크므로 열전달계수와 임계 열유속 모두 예상보다 큰 효과를 나타내지 않았다. $50kW/m^2$이하의 저열유속에서는 모든 표면에 대해 유동 속도 증가에 따라 열전달계수가 증가하였다. 결론적으로 핵발전소의 증기발생기에 적용하기에는 낮은 핀 형상의 표면이 가장 좋은 것으로 나타났다.

CFC11, HCFC123, HCFC141b 풀내에서 낮은 핀관의 비등 열전달특성 (Pool Boiling Heat Transfer Charcteristics of Low-Fin Tubes in CFC11, HCFC123 and HCFC141b)

  • 김주형;곽태희;김종보
    • 대한기계학회논문집
    • /
    • 제19권9호
    • /
    • pp.2316-2327
    • /
    • 1995
  • Experimental results from nucleate pool boiling heat transfer with various finned tubes in CFC11, HCF123 and HCFC141b are reported. One plain tube and four low fin tubes of various fin densities were tested in an attempt to find out the optimum fin density in the heat flux range of 10-60 kW/m$^{[-992]}$ at near atmospheric pressure. The results indicated that CFC11 showed the highest heat transfer coefficients. Its alternatives, HCFC123 and HCFC141b, showed 3-5% lower heat transfer coefficients than those of CFC11 at the same heat flux. As the fin density increases, so does the heat transfer surface area. Measured heat transfer coefficients, however, do not necessarily always increase as the fin density increases. This unique phenomenon seems to be caused by the coalescence of the bubblers that prevent the cool liquid from entering into the fin valleys. For all the refrigerants tested, the optimum fin density yielding the highest performance was 28 fins per inch confirming the previous results by other researchers.

알루미늄 다채널 평판관내 R-22 응축에 관한 연구 (R-22 Condensation in Flat Aluminum Multi-Channel Tubes)

  • 김정오;조진표;김내현
    • 대한기계학회논문집B
    • /
    • 제24권2호
    • /
    • pp.241-250
    • /
    • 2000
  • In this study, condensation heat transfer tests were conducted in flat aluminum multi-channel tubes using R-22. Two internal geometries were tested ; one with smooth inner surface and the other with micro-fins. Data are presented for the followin~ range of variables ; vapor quality($0.1{\sim}0.9$), mass flux($200{\sim}600kg/m^2s$) and heat flux($5{\sim}15kW/m^2$). The micro-fin tube showed higher heat transfer coefficients compared with those of the smooth tube. The difference increased as the vapor quality increased. Surface tension force acting on the micro-fin surface at the high vapor quality is believed to be responsible. Different from the trends of the smooth tube, where the heat transfer coefficient increased as the mass flux increased, the heat transfer coefficient of the micro-fin tube was independent of the mass flux at high vapor quality, which implies that the surface tension effect on the fin overwhelms the vapor shear effect at the high vapor quality. Present data(except those at low mass flux and high quality) were well correlated by equivalent Reynolds number, Existing correlations overpredicted the present data at high mass flux.

응축용 특수 전열관의 열전달 특성에 관한 연구 (Experimental Study on Condensation Heat Transfer Characteristics of Special Heat Transfer Tubes)

  • 한규일;박종운;권영철;조동현
    • 설비공학논문집
    • /
    • 제13권9호
    • /
    • pp.827-835
    • /
    • 2001
  • In this study, condensation heat transfer characteristics were conducted with special heat transfer tubes of SH-C type. Experiments were carried out the saturated vapor temperature of 334K and the wall subcooling of 1.5-4.5K. The refrigerant was R-113 and the enhanced tubes used in the present study were SH-CDR, SH-CYR and SH-CHR. The experimental results showed that the condensation heat transfer coefficients of SH-C type tubes were about 23-66% higher than those of a low integral-fin tube. It was visualized that the condensed liquid on the outer surface of SH-C type tubes flowed continuously down unlike a low integral-fin tube and a plain tube, due to a 3-D extending fin on the outer surface of SH-C type tubes. As a result, the thermal resistance of the condensed liquid decreased and the heat transfer coefficient increased. Also, the enhancement ratio of SH-CDR tube was the highest, and it was about 9-11 times as compared to that of a plain tube.

  • PDF

핀-관 열교환기의 착상 거동에 대한 표면 접촉각의 영향 (The effect of surface contact angle on the behavior of frost formation in a fin-tube heat exchanger)

  • 이관수;지성;이동욱
    • 설비공학논문집
    • /
    • 제12권1호
    • /
    • pp.95-101
    • /
    • 2000
  • The effect of surface contact angle on the behavior of frost formation in a fin-tube heat exchanger is investigated experimentally. It is shown that both heat exchangers with hydrophilic and hydrophobic surfaces appear to have a better thermal performance than bare aluminium heat exchanger, but the improvements are very small. There is a little increase in the amount of the frost deposited onto the heat exchanger with both hydrophilic and hydrophobic surface. However, the effect of contact angle on the frost density is observed ; the frost with high density forms on the heat exchanger with hydrophilic surface ; and the frost with low density is deposited onto the heat exchanger with hydrophobic surface when compared with the frost deposited onto the heat exchanger with bare aluminium surface. This may be attributed to the fact that the shape of water droplets which condense on the surface of heat exchanger at the early stage of frosting varies with contact angle, and thus makes a difference on the structure of frost formation. From the experiments with different relative humidity of inlet air, it is shown that the variations of operating parameter make no influence on the effect of surface contact angle on the frosting behavior in the heat exchanger.

  • PDF

초저온 액화가스 단일 모듈 기화기의 열변형 구조해석 (Structure Analysis on Thermal Deformation of Super Low Temperature Liquefied Gas One-module Vaporizer)

  • 박기태;이용훈;심규진;정효민;정한식
    • 동력기계공학회지
    • /
    • 제11권3호
    • /
    • pp.22-28
    • /
    • 2007
  • Liquefied gas vaporizer is a machine to vaporize liquefied gas such as liquid nitrogen($LN_{2}$), liquefied natural gas(LNG), liquid oxygen($LO_{2}$) etc. For the air type vaporizer, the frozen dew is created by temperature drop (below 273 K) on vaporizer surface. The layer of ice make a contractions on vaporizer. The structure analysis on the heat transfer was studied to see the effect of geometric parameters of the vaporizer, which are length 1000 mm of various type vaporizer. Structure analysis result such as temperature variation, thermal stress and thermal strain have high efficiency of heat emission as increase of thermal conductivity. As the result, Frist, With-fin model shows high temperature distribution better than without-fin on the temperature analysis. Second, Without-fin model shows double contractions better then with-fin model under the super low temperature load on the thermal strain analysis. Third, Vaporizer fin can be apply not only heat exchange but also a stiffener of structure. Finally, we confirm that All model vaporizer can be stand for sudden load change because of compressive yield stress shows within 280 MPa on thermal stress analysis.

  • PDF

초저온 액화가스용 기화기의 열전달 수치해석 (Study on the Heat Transfer Numerical Analysis of Supper Low Temperature Liquefied Gas Vaporizer)

  • 이용훈;지명국;박기태;김필환;정효민;정한식
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2007년도 춘계학술대회B
    • /
    • pp.2211-2216
    • /
    • 2007
  • Liquefied gas vaporizer means machine to vaporize the liquefied gas as liquid nitrogen($LN_2$), liquefied natural gas(LNG), liquid oxygen($LO_2$) etc. In the air type vaporizer, the frozen dew is also created by temperature drop (below 273 K) on vaporizer surface. This problem increases as the time progresses and humidity increases. In addition, the frozen dew gradually becomes frost deposit consequently, heat transfer through vaporizer decreases because frost deposit form adiabatic sheet. Because of this reason, recent vaporizer system is installed as parallel type, this vaporizer system needs more expensive installation costs and more space. This paper was investigated on the heat transfer characteristics of liquefied gas vaporizer with super low temperature and this paper was carried out the numerical about air heating vaporizer with super low temperature. The numerical analysis on the heat transfer was studied on the effect of geometric parameters of the vaporizer, which are length 1000 mm of 4fin75le type vaporizer. 4fin75le means number of fin is 4 and height of fin is 75 mm.

  • PDF

장력 감김으로 부착된 가로방향 휜-미니채널의 공기측 열전달 특성 (Air Side Heat Transfer Charactieristics of Tension Wound Transverse Fin with Minichannel)

  • 김종수;임용빈
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제29권6호
    • /
    • pp.701-706
    • /
    • 2005
  • Pipes, tubes. and tubular sections with external transverse high fins have been used extensively for heating cooling, and degumidifying air and other gases. This work was performed to investigate an air side heat transfer charactieristics of minichannel with tension wound transverse fin. This estimate was confirmed conversion heat capacity the air side surface area enlargement and heat transfer charactieristics performed available inlet tube side hot water mass flux or outlet tube side air frontal air velocity. The most suitable tension wound transverse finned minichannel was measured extremely low in air side pressure drop and fin effectiveness $3.3\~4.4$. The pressure drop $0.9\~2.8Pa$ was ranged frontal air velocity $0.5\~1.2m/s$. It is also appeared that heat transfer in air side could be better conversion heat area which has been increased $330\%$ of heat capacity compared with the bare tube.

열전달 촉진 표면에서 R1234yf의 풀 비등 열전달계수 (Pool Boiling Heat Transfer Coefficients of R1234yf on Various Enhanced Surfaces)

  • 이요한;강동규;서훈;정동수
    • 설비공학논문집
    • /
    • 제25권3호
    • /
    • pp.143-149
    • /
    • 2013
  • In this work, nucleate pool boiling heat transfer coefficients (HTCs) of R134a and R1234yf are measured, on flat plain, 26 fpi low fin, Turbo-B, Turbo-C and Thermoexcel-E surfaces. All data are taken at the liquid pool temperature of $7^{\circ}C$, on a small square copper plate ($9.53mm{\times}9.53mm$), at heat fluxes from $10kW/m^2$ to $200kW/m^2$, with an interval of $10kW/m^2$. Test results show that nucleate boiling HTCs of all enhanced surfaces are greatly improved, as compared to that of a plain surface. Nucleate pool boiling HTCs of R1234yf are very similar to those of R134a, for the five surfaces tested.