고압 전동기 고정자 권선의 절연진단을 위한 운전중 부분방전 측정 시스템 개발 (Development of On-Line Partial Discharge Measuring System for Insulation Diagnosis of High-Voltage Motor Stator Windings)

  • 황돈하;강동식;신병철;이영진;이광식
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2006년도 춘계학술대회 논문집
    • /
    • pp.481-486
    • /
    • 2006
  • In this paper, a new on-line high-voltage motor monitoring system is proposed. This system monitors the insulation condition of the stator winding by on-line measurements of partial discharge (PD). And this system displays magnitude and phase angle distribution of PD. Sensor, CC (Ceramic Coupler) is used for PD measurement. PD signals are continuously measured and digitized with a A/D converter to build the database of the high-voltage motor's insulation condition. Also, this system can communicate with the central monitoring system via RS-232, 422, and TCP/IP. This helps more efficient operation and maintenance of the high-voltage motor.

  • PDF

변압기 상태의 온라인 감시 체계 구축에 대한 연구 동향 (A Research Trend on Multi-Agent Transformer Condition Monitoring System On-Line)

  • 김정훈;용형식;최용성;이경섭
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.2006-2007
    • /
    • 2007
  • On-line condition monitoring is a useful tool for maintaining and extending the longevity of power transformers. An intelligent diagnostic system is desirable for operational safety and reliability. Bringing these concepts together results in a powerful support tool for engineers, reducing the volume of data to deal with, and making the data more meaningful. This paper describes how a multi-agent system for diagnosing the cause of transformer partial discharge activity was coupled with a method of UHF partial discharge monitoring, creating an on-line condition monitoring system. The challenges presented by the on-site environment are discussed, along with the implications for the complete system.

  • PDF

지중배전케이블의 PD 검출용 필터 시험 연구 (Filter Test for Partial Discharge Detection of Underground Distribution Cables)

  • 이용성;김정윤;이관우;최용성;박대희
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2005년도 하계학술대회 논문집 Vol.6
    • /
    • pp.215-216
    • /
    • 2005
  • To decrease and remove of much noises that is detected in PD (partial discharge) measuring test. we forced on detection of those. We made W-LC filter for measuring PD. which adapted that to field test. We tested after design laboratory circumstances like field line. and then the phase change properties of detected signal in UHF sensor were measured by Lemke Probe and oscilloscope (TDS-3054. Tektronix). Eventually we checked decrement of noises from experimental result. Also from experimental result at the joint box of 22.9[kV] distribution line. we obtained reasonable data which enable noises to decrease. Hereafter those results will be adapted at ultra-high voltage for trouble prevention and on-line cable watch. diagnosis of those.

  • PDF

노이즈 제거 알고리즘을 적용한 변압기 초음파 상시 측정장치 개발 (Development of the On-line Ultrasonic Detecter for Transformer Applied Noise Rejection Algorithm)

  • 권동진;진상범;곽희로
    • 조명전기설비학회논문지
    • /
    • 제16권4호
    • /
    • pp.80-91
    • /
    • 2002
  • 운전중인 변압기 내부의 부분방전에 의한 초음파 신호를 상시 감시하기 위한 초음파 상시 측정장치를 개발하였다. 초음파 상시 측정장치는 변압기 외부에서 발생하는 전기적 및 기계적인 노이즈를 제거하고 변압기 내부의 부분방전에 의한 초음파 신호만을 측정하기 위하여 50~300[KHz] 주파수 대역만 집중 측정하도록 협대역 필터를 설계하였으며, 초음파 센서는 60[dB] 증폭도의 프리앰프 내장형으로 개발하였다. 부분방전에 의한 초음파 신호와 특성이 유사한 부하시 탭 절환장치의 동작에 의한 초음파 신호를 제거하기 위하여, 초음파 신호의 지속시간으로 판별하는 초음파 신호판별 알고리즘을 개발하였다. 본 연구에서 개발한 초음파 상시 측정장치는 실험실의 모의 변압기와 현장에서 운전중인 변압기에서 부분방전에 의한 초음파 신호를 측정하여 신뢰성을 확인하였다.

Electro Discharge Deposition (EDD)을 이용한 미세 구조물 제작 (Fabrication of Micro Structure Using Electro Discharge Deposition)

  • 오석훈;민병권;박성준;이상조
    • 한국정밀공학회:학술대회논문집
    • /
    • 한국정밀공학회 2003년도 춘계학술대회 논문집
    • /
    • pp.1865-1868
    • /
    • 2003
  • This paper provides a new method for hybrid machining, particularly suited to micro fabrication applications such as micro point, micro line, micro structure, micro partition and so on. Developed micro fabrication process by electrical discharge machining (EDM) and electrical discharge deposition (EDD) with metal powder (Ti, Fe) has been studied to build TiC or FeC structure. Titanium powder or iron powder is supplied from working fluid (kerosene or de-ionized water with powder) and adheres on a workpiece by the heat and electric power caused by the electrical discharge. The use of a tool electrode is expected to keep powder concentration high in the gap between a workpiece and a tool electrode and to accrete powder material on the workpiece. The deposition is tried under various electrical conditions (workpiece. tool electrode, working fluid, discharge current, voltage and powder etc.). On the other hand. using electrical discharge machining (EDM) with the same tool electrode, it can be used as a removal process (cutting) by electro erosion at the same time. Therefore. this new method can do a hybrid machining to build up and down a structure with the workpiece.

  • PDF

회전기 고정자 권선에서의 운전 중 절연열화 진단기법 (On-Line Insulation Diagnosis Techniques for Stator Winding of Rotating Machines)

  • 윤대희;황돈하;신병철;김용주;이광식
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2000년도 학술대회논문집
    • /
    • pp.89-93
    • /
    • 2000
  • Recently many research activities on the diagnosis of stator winding insulation of large rotating machines have been reported. Capacitive couplers are widely used as sensors for on-line partial discharge (PD) measurement of high voltage rotating machines. This paper presents laboratory test to compare Stator Slot Coupler (SSC), Resistance Temperature Detector (RTD), 80 [pF] coupler and 500 [pF] coupler for on-line PD measurement of rotating machines. And a novel on-line monitoring system for an insulation diagnosis is proposed.

  • PDF

765kV 교류 송전선로의 가청소음계산 예측식개발(I) (Predicting formula development of audible noise on a 765kV AC transmission line(I))

  • 이동일;구자윤
    • 대한전기학회논문지
    • /
    • 제45권4호
    • /
    • pp.612-615
    • /
    • 1996
  • Audible noise from corona discharge had been identified as one of the most important factors in the design of conductor configurations for high-voltage transmission lines. 500kV and above. Therefore this paper describes audible noise characteristics of 6 X 480mm conductor bundle in KEPRI 765kV Test Line and Corona Cage. Prediction formula for audible(corona) noise on a 765kV transmission Line was developed using this results.

  • PDF

PDP 스캔 전극 구동방식에 따른 방전 특성의 변화에 관한 연구 (A Study on the Discharge Characteristics of an Ac PDP with the Variation of Scan Electrode Driver)

  • 김중균
    • 조명전기설비학회논문지
    • /
    • 제19권8호
    • /
    • pp.13-18
    • /
    • 2005
  • 본 연구는 스캔 구동 회로의 변화에 따른 교류형 플라즈마 표시기의 구동 특성에 관한 것이다. 본 연구에서는 교류형 플라즈마 표시기의 용량성 부하 특성을 활용하여 스캔 라인 당 소요되는 스위치의 수를 줄일 수 있는 회로를 제안하고 그 적용 가능성을 고찰하였다. 제안된 방식의 실용화 가능성에 대한 검증을 위하여 방전 유지 전압의 변화에 따라 어드레싱 전압의 변화를 관찰하여 동적 전압 마진을 측정한 결과, 기존 방식에 비하여 9[V] 가량의 전압마진 감소가 관찰되었다. 이는 제안된 방식의 경우 선택된 전극의 스캔 기간에 이웃한 전극에 전위에 영향을 줌으로써 상호 간섭이 유발되는 효과에 의한 것으로 해석되었다. 최소 어드레싱 전압과 어드레싱 방전의 방전 지연 시간에 변화가 없는 점을 감안하면 제안된 방식의 실제 회로 적용은 가능할 것으로 사료된다.

BaTiO3 타겟의 R.F. 방전 중 변수에 따른 광반사분광 특성 (Optical Emission Spectroscopy with Parameters During R.F. Discharge of BaTiO3 Target)

  • 박상식
    • 한국재료학회지
    • /
    • 제21권9호
    • /
    • pp.509-514
    • /
    • 2011
  • In this study, optical emission spectroscopy was used to monitor the plasma produced during the RF magnetron sputtering of a $BaTiO_3$ target. The intensities of chemical species were measured by real time monitoring with various discharge parameters such as RF power, pressure, and discharge gas. The emission lines of elemental and ionized species from $BaTiO_3$ and Ti targets were analyzed to evaluate the film composition and the optimized growth conditions for $BaTiO_3$ films. The emissions from Ar(I, II), Ba(I, II) and Ti(I) were found during sputtering of the $BaTiO_3$ target in Ar atmosphere. With increasing RF power, all the line intensities increased because the electron density increased with increasing RF power. When the Ar pressure increased, the Ba(II) and Ti(I) line intensity increased, but the $Ar^+$ line intensity decreased with increasing pressure. This result shows that high pressure is of greater benefit for the ionization of Ba than for that of Ar. Oxygen depressed the intensity of the plasma more than Ar did. When the Ar/$O_2$ ratio decreased, the intensity of Ba decreased more sharply than that of Ti. This result indicates that the plasma composition strongly depends on the discharge gas atmosphere. When the oxygen increased, the Ba/Ti ratio and the thickness of the films decreased. The emission spectra showed consistent variation with applied power to the Ti target during co-sputtering of the $BaTiO_3$ and Ti targets. The co-sputtered films showed a Ba/Ti ratio of 1.05 to 0.73 with applied power to the Ti target. The films with different Ba/Ti ratios showed changes in grain size. Ti excess films annealed at $600^{\circ}C$ did not show the second phase such as $BaTi_2O_5$ and $TiO_2$.

ESD와 점착 롤 제진을 이용한 LGP 건식 세정 장치 개발 (Development of LGP Dry Cleaning Equipment using ESD and Adhesive Roll)

  • 구자일;전성호
    • 전자공학회논문지
    • /
    • 제51권8호
    • /
    • pp.195-201
    • /
    • 2014
  • 본 논문에서는 도광판(LGP, Light Guide Panel)의 미세먼지 세정을 위해 건식 점착롤 제진과 코로나 대전을 이용한 제전(ESD, electrostatic discharge) 방식을 적용한 건식 세정 장치를 개발한다. 이를 위해 점착롤 제진과 제전 방식을 혼합 적용할 수 있는 세정 메커니즘을 설계하고, LGP를 자동으로 로딩/언로딩 및 이송할 수 있는 장치를 설계하고 구현한다. 그리고 이물질 및 미세먼지 세정 실험을 통해 개발된 시스템이 안정적으로 동작함을 확인하였다.