• 제목/요약/키워드: Line Current

검색결과 3,819건 처리시간 0.032초

자기단 전원 임피던스 추정 기법을 사용한 병행 2회선 송전선로 고장점 표정 알고리즘 (A Fault Location Algorithm Using Adaptively Estimated Local Source Impedance for a Double-Circuit Transmission Line System)

  • 박건호;강상희;김석일;신종한
    • 전기학회논문지
    • /
    • 제61권3호
    • /
    • pp.373-379
    • /
    • 2012
  • This paper presents a fault location algorithm based on the adaptively estimated value of the local sequence source impedance for faults on a parallel transmission line. This algorithm uses only the local voltage and current signals of a faulted circuit. The remote current signals and the zero-sequence current of the healthy adjacent circuit are calculated by using the current distribution factors together with the local terminal currents of the faulted circuit. The current distribution factors consist of local equivalent source impedance and the others such as fault distance, line impedance and remote equivalent source impedance. It means that the values of the current distribution factors can change according to the operation condition of a power system. Consequently, the accuracy of the fault location algorithm is affected by the two values of equivalent source impedances, one is local source impedance and the other is remote source impedance. Nevertheless, only the local equivalent impedance can be estimated in this paper. A series of test results using EMTP simulation data show the effectiveness of the proposed algorithm. The proposed algorithm is valid for a double-circuit transmission line system where the equivalent source impedance changes continuously.

765 kV 송전선로에서의 이종 전압등급 병행 운전시의 유도현상 예측 및 실측 결과 (Prediction and Measurement of Induction Phenomena in the 765 kV Double Circuit Transmission Line operated with two voltage grades)

  • 곽주식;강연욱;심응보;전명렬;우정욱;방항권
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 A
    • /
    • pp.208-211
    • /
    • 2003
  • The western route of KEPCO's 765 kV transmission line has been tentatively operating as 345 kV voltage before commercial operation. KEPCO decided to operate the 765 kV line for commercial operation after completing the test operation of 765 kV substation in 2002. In the process of energizing the line as 765 kV voltage, double circuit transmission line will be operated with two voltage grades of 765 kV and 345 kV. As the earthing switches are installed on both ends of the line, electrostatic induction voltage and electromagnetic induction current were calculated prior to the line energizing in order to confirm the ratings. The induced voltage and current are important for the maintenance of the parallel circuit. This paper presents the simulation results of electrical phenomena such as electrostatic induction voltage and electromagnetic induction current from the parallel line. The transmission line was modeled by EMTP (Electro-Magnetic Transient Program). The simulation results were compared with the measured results at the field.

  • PDF

345kV 고장전류 저감을 위한 한류리액터 설치시 차단기 TRV(근거리 고장시) 검토 (A Study on the TRV(SLF) of Circuit Breakers According to Install Current Limit Reactors)

  • 박흥석;곽주식;주형준;유희영;한상옥
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 A
    • /
    • pp.371-373
    • /
    • 2005
  • An enhancement for a transmission and substation equipment in power system make the system impedance to be lower. In principle, if the system impedance become low, system stability will be better, but the fault current become very higher. It is a very big problem for CB operating. As a fact of CB operating performance, high amplitude of the fault current may cause CB operation failure because of exceeding standard value in TRV. So we simulated TRV by using the EMTP. Generally there are two types of TRV in actual power system. One is short line fault, the other is bus terminal fault. In this paper, we simulated the TRv at short line fault as installed current limit reactors to reduce fault current in 345kV ultra-high voltage system. Short line fault is caused from single line fault in transmission line.

  • PDF

호남고속철도 전차선로의 이상 상태 분석 (Analysis for Catenary System with Focus on Abnomal Conditions on Honam High Speed Line)

  • 전재근;신승권;정호성;나경민;박영
    • 한국전기전자재료학회논문지
    • /
    • 제32권1호
    • /
    • pp.1-5
    • /
    • 2019
  • The overhead contact line (OCL) is a key piece of equipment for transmitting electrical energy to the pantograph of rail cars. Recently, a 400 km/h OCL was applied to the Honam high-speed line, and its performance was examined by running HEMU-430X. For the study, we analyzed the current of catenary wire concurrently while running HEMU-430X in the Honam high-speed line. Specifically, this study recorded the currents for each speed during operation of the railway vehicle. The analysis of the frequency of line current showed generation of third-harmonics, 15th-harmonics, 17th-harmonics, and 19th-harmonics. The current of catenary wire is a basic technology assessment used to determine the electrical safety of electric railway systems, and it can be used as a technology for analyzing circulating currents generated in the current configuration, as well as for analyzing electric fatigue of the OCL components.

Bus-voltage Sag Suppressing and Fault Current Limiting Characteristics of the SFCL Due to its Application Location in a Power Distribution System

  • Kim, Jin-Seok;Lim, Sung-Hun;Kim, Jae-Chul
    • Journal of Electrical Engineering and Technology
    • /
    • 제8권6호
    • /
    • pp.1305-1309
    • /
    • 2013
  • The application of the superconducting fault current limiter (SFCL) in a power distribution system is expected to contribute the voltage-sag suppression of the bus line as well as the fault-current reduction of the fault line. However, the application effects of the SFCL on the voltage sag of the bus line including the fault current are dependent on its application location in a power distribution system. In this paper, we investigated the fault current limiting and the voltage sag suppressing characteristics of the SFCL due to its application location such as the outgoing point of the feeder, the bus line, the neutral line and the 2nd side of the main transformer in a power distribution system, and analyzed the trace variations of the bus-voltage and fault-feeder current. The simulated power distribution system, which was composed of the universal power source, two transformers with the parallel connection and the impedance load banks connected with the 2nd side of the transformer through the power transmission lines, was constructed and the short-circuit tests for the constructed system were carried out. Through the analysis on the short-circuit tests for the simulated power distribution system with the SFCLs applied into its representative locations, the effects from the SFCL's application on the power distribution system were discussed from the viewpoints of both the suppression of the bus-voltage sag and the reduction of the fault current.

가공 배전선에 의한 전자유도 발생 전류 계산 방법 (Formulation of Calculation Method for Inducing Current by Aerial Power Distribution Line)

  • 이상무
    • 전자공학회논문지
    • /
    • 제52권4호
    • /
    • pp.30-36
    • /
    • 2015
  • 전력선 시설 중 가공 배전선에 의하여 인근 통신선에 전자유도를 발생시키는 전류를 계산하는 방식을 수립하였다. 가공 배전선의 중성선은 50 m 마다 접지되어 있어서 부하 전류의 귀로 성분이 대지로 누설되기 때문에 주변의 통신선에 전자유도 장해를 발생시키게 된다. 현재 국가 기술기준에서 정하고 있는 방법에 의하면 귀로 전류가 흐르는 중성선을 하나의 차폐 도체로 간주하여 기유도전류를 산정하므로 통신선의 병행 위치에 따른 대지 귀로 전류의 누적적 변화 특성이 반영되지 못하여 계산된 유도전압의 실측값에 대한 오차가 커지지만 실제로 유도를 발생시키는 원인이 되는 대지 귀로 전류를 계산하는 방식을 적용하면 1000 %가 넘는 기존 계산 편차를 100 % 이내로 현격히 줄여주는 효과를 나타내었다.

커패시터 필터를 갖는 3상 다이오드 정류회로의 불평형전원에서의 입력전류 특성 (Input Current Characteristics of a Three-Phase Diode Rectifier with Capacitive Filter under Line Voltage Unbalance Condition)

  • 정승기;이동기;박기원
    • 전력전자학회논문지
    • /
    • 제6권4호
    • /
    • pp.348-361
    • /
    • 2001
  • 커패시터 필터를 갖는 3 상 다이오드 정류회로는 입력전압의 불평형에 매우 민감한 특성을 가지고 있다. 이러한 정류회로는 그 동작의 비선형성으로 인해 작은 전압의 불평형에도 입력전류에는 큰 불평형이 나타날 수 있으며 이로 인해 전원품질에 악영향을 미친다. 본 논문에서는 이러한 불평형 증폭특성을 이론적으로 규명하고 불평형 정도에 따른 정류회로의 동작모드에 따라 재반 입력전류의 특성에 대한 모델을 도출하였다. 본 논문의 결과는 각종 전력변환 장치의 입력부로서 널리 사용되는 커패시터 필터형 3상 다이오드 정류회로를 최적 설계하는 데에 중요한 해석적 기초를 제공하고 있다.

  • PDF

A New Approach to On-Line Monitoring Device for ZnO Surge Arresters

  • Lee Bok-Hee;Gil Hyoung-Jun;Kang Sung-Man
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • 제5C권3호
    • /
    • pp.131-137
    • /
    • 2005
  • This paper describes a new approach to the algorithm and fundamental characteristics of the device for monitoring the leakage currents flowing through zinc oxide (ZnO) surge arresters. In order to obtain a technique for a new on-line monitoring device that can be used in the deterioration diagnosis of ZnO surge arresters, the new algorithm and on-line leakage current detection device for extracting the resistive and capacitive currents using the phase shift addition method were proposed. The computer-based on-line monitoring device can sense accurately the power frequency leakage currents flowing through ZnO surge arresters. The on-line leakage current monitoring device of ZnO surge arresters proposed in this work has the high sensitivity compared to the third harmonic leakage current detection devices. As a consequence, it was found that the proposed leakage current monitoring device would be useful for forecasting the defects and degradation of ZnO surge arresters.

Prediction of Flashover and Pollution Severity of High Voltage Transmission Line Insulators Using Wavelet Transform and Fuzzy C-Means Approach

  • Narayanan, V. Jayaprakash;Sivakumar, M.;Karpagavani, K.;Chandrasekar, S.
    • Journal of Electrical Engineering and Technology
    • /
    • 제9권5호
    • /
    • pp.1677-1685
    • /
    • 2014
  • Major problem in the high voltage power transmission line is the flashover due to polluted ceramic insulators which leads to failure of equipments, catastrophic fires and power outages. This paper deals with the development of a better diagnostic tool to predict the flashover and pollution severity of power transmission line insulators based on the wavelet transform and fuzzy c-means clustering approach. In this work, laboratory experiments were carried out on power transmission line porcelain insulators under AC voltages at different pollution conditions and corresponding leakage current patterns were measured. Discrete wavelet transform technique is employed to extract important features of leakage current signals. Variation of leakage current magnitude and distortion ratio at different pollution levels were analyzed. Fuzzy c-means algorithm is used to cluster the extracted features of the leakage current data. Test results clearly show that the flashover and pollution severity of power transmission line insulators can be effectively realized through fuzzy clustering technique and it will be useful to carry out preventive maintenance work.

765kV 2회선 송전선 활선 작업자의 차폐복 자계저감 특성검토 (Magnetic Field Reduction Characteristics of Hot-Line Worker's Shielding Wear for 765kV Double Circuit Transmission Line)

  • 민석원;박준형
    • 전기학회논문지
    • /
    • 제56권9호
    • /
    • pp.1632-1637
    • /
    • 2007
  • This paper analyses current densities induced inside human body of lineman for 765kV transmission line when he wears a protective cloth or not. Applying the boundary element method, we calculate current densities induced in organs inside a worker in case he was located at 15[cm], 30[cm], 50[cm], and 100[cm] far from a prefabricated jumper. As results of study, we find a maximum current density induced in all organs may be higher than $10[mA/m^2]$ if he does not wear protective clothes. We also know high permeability materials can lower current density more than high conductivity materials.