• 제목/요약/키워드: Lightning Warning System

검색결과 12건 처리시간 0.016초

용량성 프로브와 광전송회로를 이용한 광대역 전압측정장치 (A Study on the Development of a Lightning Warning System by the Measurement of Electric Field at the Ground)

  • 길경석;송재용;박대원
    • 센서학회지
    • /
    • 제13권5호
    • /
    • pp.363-368
    • /
    • 2004
  • A reliable voltage measurement system is necessary to monitor status of power facilities in substations, which is easy to set up and is not influenced by electromagnetic interference in and around substation. In this paper, we described a voltage measurement system (VMS) which is composed of a capacitive voltage probe, an impedance converter, and an optical linker. To get a wide-band characteristic of the VMS, a high speed impedance converter was used, and the output impedance of the VMS was set at $50{\Omega}$ to match any types of observing instruments. The frequency bandwidth of the VMS. which was estimated by a step pulse, was ranges from 11.42 Hz to 13.65 MHz, and the VMS showed a good response characteristic in a high frequency domain such as impulse voltages as well as a commercial frequency voltage.

대지전계 측정을 위한 필드밀의 설계 및 제작 (Design and Fabrication of a Field Mill for Ground-Level Electric Field Measurement)

  • 길경석;송재용;김일권;권장우;안창환;이영근
    • 조명전기설비학회논문지
    • /
    • 제21권1호
    • /
    • pp.52-59
    • /
    • 2007
  • 본 논문에서는 뇌경보시스템에 적용하기 위한 센서로 대지전계의 극성과 크기의 측정이 가능한 필드밀에 대하여 연구하였다. 회전날개를 갖는 평면 셔터형 필드밀을 설계 제작하였으며, 필드밀의 교정은 대칭적인 구조의 원형 평판전극을 수직으로 배열하고 이때 얻어지는 평등전계 내에서 수행하였다. 교정실험에서 필드밀의 감도를 0.5[V/kV/m]로 조정하였으며, 측정 가능한 대지전계의 범위는 $200[V/m]{\sim}]20[kV/m]$가 된다. 교정실험 후, 건물 옥상에 필드밀을 설치하고, 뇌운에 의한 대지전계의 변화를 관측하였다. 2006년 7월 1일부터 7월 15일의 기간 중, 뇌운의 생성과 소멸, 이동에 따라 대지전계의 크기는 $+2[kV/m]{\sim}-6[kV/m]$의 범위에서 기록되었다. 적용실험결과로부터 제안한 필드밀은 직류 전계 측정에 충분한 성능이 있음을 확인하였다.