심매설 접지전극의 전류인가위치에 따른 과도접지임피던스 특성 (Transient impedance characteristics according to the injection position of deep-driven ground rods)

  • 이복희;이봉;이수봉;이승주;전병욱;엄주홍;조성철;이태형
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2008년도 춘계학술대회 논문집
    • /
    • pp.297-300
    • /
    • 2008
  • This paper presents the behaviors of transient and conventional grounding impedances of a deep-driven ground rods associated with the injection point of lightning impulse currents. The transient impedance of deep-driven ground rods under lightning impulse currents were higher than the static ground resistance. The transient grounding impedances strongly depend on the injection point and size of grounding electrodes and the rising time of impulse current. Reduction of ground system inductance is an important factor to lightning surge protection.

  • PDF

보조접지선 시공에 의한 송전선로의 내뢰성 향상효과 모의 (A Simulation of Lightning Faults Reducing Effects on the 154 kV Transmission Tower by Auxiliary Grounding)

  • 곽주식;심정운;심응보;최종기
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 하계학술대회 논문집 E
    • /
    • pp.1843-1846
    • /
    • 1997
  • This paper describes the fault reducing effects of the 154 kV transmission tower by auxiliary grounding from the top of the tower to ground. The grounding surge impedance of the auxiliary grounding system is calculated by CDEGS(:Current Distribution Electromagnetic Interference Grounding and Soil Structure Analysis), and the critical lightning back flashover current and arcing horn dynamic characteristics are simulated by EMTP/TACS(:Electromagnetic Transient Program/Transient Analysis of Control Systems). The calculated results of total LFOR(Lightning Flashover Rate) shows that the LFOR can be reduced from 5.2(count/100km. year) to 3.4 by auxiliary grounding on the 154 kV transmission tower with one ground wire shielding system.

  • PDF

전차선로에서의 뇌격에 의한 가공지선과 피뢰기의 차폐효과 (Effects of an Overhead Ground Wire and Surge Arrester in the Railway due to Lightning Strokes)

  • 임성정;한병덕;오정환;윤상윤;김재철;정용철
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 A
    • /
    • pp.468-470
    • /
    • 1999
  • Using the EMTP(Electro Magnetic Transient Program) for the analysis of lightning direct voltage on the railway system, the shielding effects of overhead grounding wire on the railway were studied quantitatively. Installation of overhead ground wire and sap-type arrester such as s-horn provides a 6.6kV HV distribution line with goof protection effects. Even severe lightning induced voltage were create, 6.6kV HV lines can be withstand.

  • PDF

ZnO 계열의 금속산화물 바리스터의 단락 방지용 소자 적용에 따른 제한전압 특성 분석 (Analysis of characteristics for clamping voltage fellowing the application of element for preventing the short circuit of Metal Oxide Varistors for ZnO)

  • 정태훈;최성욱;정제선;김재철
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 C
    • /
    • pp.1531-1532
    • /
    • 2006
  • Recently, the natural environment changes drastically, and the frequency of occurrence for lightning has gradually been increased. Such lightning delivers high volume of energy along the power line and communication line to the equipment in use. The high volume of energy arising from the lightning surge develops in fast velocity to destroy the facilities in power source and many other facilities in operation in sequential destruction with vast energy. In this thesis, the analysis on the change of clamping voltage characteristics by the contact resistance and lead inductance by using several case studies through the application of element for preventing the short circuit of Metal Oxide Varistor for ZnO.

  • PDF

배전용 변압기 고압측으로의 뇌서지 전파 (Propagation of Lightning Surges toward primary Side of Distribution Transformer)

  • 이복희;이수봉;김병근;이승칠;이동문;정동철
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2003년도 학술대회논문집
    • /
    • pp.269-272
    • /
    • 2003
  • The importance of the improving quality of electric power is being strongly raised, owing to an increasing use of sensitive and small-sized electronic devices and system. The transient overvoltage on low-voltage AC power distribution system are induced by direct or indirect lightning return strokes, and those can cause damage and/or malfunction of the utility system for borne automation, office automation and factory automation as well as medical equipments. The behavior of lightning surge transferred to the primary side from the primary side in distribution transformers were experimentally investigated the protection effect of low voltage SPD installed at the secondary side of distribution transformers was analyzed.

  • PDF

매설지선의 임펄스임피던스의 해석 (Analysis for the impulsive impedance of counterpoise)

  • 조정현;김종호;백영환;김동성;이강수;김기복;이복희
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2009년도 춘계학술대회 논문집
    • /
    • pp.88-91
    • /
    • 2009
  • For lightning currents, a grounding system shows the transient grounding impedance characteristics. A grounding system for protection against lightning should be evaluated by the transient grounding impedance, not it's ground resistance. The transient grounding impedance varies with the shape of ground electrode and earth characteristics as well as the waveform of lightning surge current. For the analysis and practical use of transient grounding impedance, the characteristics of transient grounding impedance should be analyzed theoretically and this paper suggests the theoretical analysis for the transient grounding impedance of counterpoise by using the distributed parameter circuit model. EMTP and Matlab are used to simulate the distributed parameter circuit model of counterpoise and the adequacy of the distributed parameter model of counterpoise is examined by comparing the simulated results with the measured results.

  • PDF

Impedance Analysis and Surge Characteristics of PV Array

  • Lee, Ki-Ok;So, Jeong-Hoon;Yu, Gwon-Jong;Park, Ju-Yeop
    • Journal of Power Electronics
    • /
    • 제3권4호
    • /
    • pp.259-264
    • /
    • 2003
  • Photovoltaic (PV) array, which is generally installed outside, has the possibility of being damaged by high voltage due to lightning. primarily because the electrical characteristics of PV array have not been fully identified by lightning yet, there is a very important issue whether PV array should be connected with a ground or not. In this paper, a basic model of PV array is provided considering the PV cell's barrier capacitance and ground capacitance for analysis of electrical characteristics by lightning.

서지임피던스 측정기의 설계 및 제작 (Design and Fabrication of a Surge Impedance Meter)

  • 길경석;류길수;김일권;문병두;김황국;박찬용
    • 한국철도학회논문집
    • /
    • 제10권6호
    • /
    • pp.645-649
    • /
    • 2007
  • 접지시스템은 고장전류를 대지로 방출시켜 대지전위상승을 억제하는 역할을 한다. 본 논문에서는 넓은 주파수 범위에서 접지임피던스를 분석하기 위하여 서지임피던스측정기를 설계 제작하였다. 본 측정기는 서지발생회로, 고속 샘플/홀드회로 및 주변 전자회로로 구성되어 있으며, 서지발생치고는 상승시간 $50ns\sim500ns$ 범위에서 최대 5kV까지 발생시킬 수 있다. 제작한 서지임피던스 측정기는 심타접지극으로 구성된 접지계에서 실질적 평가가 수행되었다. 실험 결과로부터 접지계의 서지임피던스는 인가전압의 상승시간에 따라 증가하는 경향을 나타내므로, 접지임피던스는 여러가지 고속의 서지파형으로 평가되어야함을 확인하였다.

저압용 서지 보호 장치(SPD)의 보호 거리 해석 (Analysis of the Protective Distance of Low-Voltage Surge Protective Device(SPD) to Equipment)

  • 이정우;오용택
    • 조명전기설비학회논문지
    • /
    • 제26권4호
    • /
    • pp.28-34
    • /
    • 2012
  • Installing surge protection devices for a low-voltage system is important to ensure the survival of electric or electronic devices and systems. If surge protection devices (SPD) are installed without consideration of the concept of lightning protection zones, the equipment to be protected might be damaged despite the correct energy coordination of SPDs. This damage is induced by the reflection phenomena on the cable connecting an external SPD and the load protected. These reflection phenomena depend on the characteristics of the output of the external SPD, the input of the loads, and the cables between the load and the external SPD. Therefore, the SPD has an effective protection distance under the condition of the specific load and the specific voltage protection level of SPD. In this paper, PSCAD/EMTDC software is used to simulate the residual voltage characteristics of SPD Entering the low-voltage device. And by applying a certain voltage level, the effective protection distances of SPD were analyzed according to the each load and length of connecting cable, and the effectiveness of SPD were verified.

MATLAB 프로그램을 이용한 배전계통에 사용되는 동봉 접지전극의 과도 접지임피던스 특성 분석 (Transient Grounding Impedance Characteristic Analysis of a Copper Rod-type Grounding Electrode Used for Electric Distribution Systems Using MATLAB Program)

  • 김경철;오경훈;이규진;심건보;최종기
    • 조명전기설비학회논문지
    • /
    • 제23권9호
    • /
    • pp.40-46
    • /
    • 2009
  • 비록 접지저항은 접지전극의 접지성능을 좌우하는 지수이기는 하지만, 과도상태에서는 접지 성능을 반영하지 못한다. 동봉은 배전계통에서 가장 많이 쓰이는 접지전극이다. 본 논문에서는 동봉의 접지 임피던스를 주파수 60[Hz]에서 100[kHz] 범위까지 측정하여 등가 접지임피던스 모델을 구하였다. 뇌격서지가 유입되었을 때 MATLAB 프로그램으로 과도접지임피던스의 수치와 파형을 시뮬레이션하였다.