Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 1999.07a
- /
- Pages.468-470
- /
- 1999
Effects of an Overhead Ground Wire and Surge Arrester in the Railway due to Lightning Strokes
전차선로에서의 뇌격에 의한 가공지선과 피뢰기의 차폐효과
- Rim, Seong-Jeong (Dept of Elec Eng. Soongsil University) ;
- Han, Byung-Duk (Dept of Elec Eng. Soongsil University) ;
- Oh, Jung-Hwan (Dept of Elec Eng. Soongsil University) ;
- Yun, Sang-Yun (Dept of Elec Eng. Soongsil University) ;
- Kim, Jae-Chul (Dept of Elec Eng. Soongsil University) ;
- Chung, Yong-Chul (Dept of Elec Eng. Soongsil University)
- 임성정 (숭실대학교 전기공학과) ;
- 한병덕 (숭실대학교 전기공학과) ;
- 오정환 (숭실대학교 전기공학과) ;
- 윤상윤 (숭실대학교 전기공학과) ;
- 김재철 (숭실대학교 전기공학과) ;
- 정용철 (철도청 전기과)
- Published : 1999.07.19
Abstract
Using the EMTP(Electro Magnetic Transient Program) for the analysis of lightning direct voltage on the railway system, the shielding effects of overhead grounding wire on the railway were studied quantitatively. Installation of overhead ground wire and sap-type arrester such as s-horn provides a 6.6kV HV distribution line with goof protection effects. Even severe lightning induced voltage were create, 6.6kV HV lines can be withstand.
Keywords